Calibration of Tr-Rec

ESP
CONTENT

 INTRODUCTION OF MCS II
 CALIBRATION OF TR-REC
 SUMMARY
MCS II SPECIFICATION

 - Input Voltage 20 – 0 – 20 V ac +10% -25%.


 - Supply Frequency 47 – 63Hz.
 - Power Consumption 20VA max at nominal input voltage.
 - Analogue Inputs 6.
 - Analogue Outputs 2. 4-20mA or 0 – 20mA
 - Digital Inputs 16 Mode selectable 24V DC or 110V ac.(8 Pre-defined
function, 8 Configurable)
 - Digital Outputs 6 110 V ac +10% - 25%.
 - SCR Drivers 2 Mains supply 700V RMS Max.
 - Communication Ports 3 CAN bus Network connection.
RS422 Asynchronous Serial port.
RS422 Synchronous serial port.
 - Display LCD 320 x 240 Pixel
ESP control system

ID

NEXT
Function of MCS II

NEXT
System of MCS II

 MCS II keypad MCS II controller

CANbus

BACK TO CONTENT
CONTENT

 INTRODUCTION OF MCS II
 CALIBRATION OF TR-REC
 SUMMARY
Don’t forget about PPE and LOTO

NEXT
LOTO

NEXT
PPE Electric

Safety helmet Rubber gloves


Safety shoes for electric

glasses Ear plug BACK


PREPARE TOOL
Display castlet and analog
meter

NEXT
Setting Tr-Rec by Castlet
1. Select manual mode from the selector switch
2. Use password for open menu castlet
3. Turn-on the Tr-Rec
4. select continues parameter on menu then choose program
no. 10
5. Wait for 3-5 minutes
6. Setting primary current on analog meter up to 300A by keypad
(on the manual setting menu)
7. Select meter calibration then designation set Vp Ip on the
caslet display to suit with analog meters.
8. For Is and Vs, it’s must measuring level voltage from the sensor
on TR-REC control panel.
NEXT
9. Adjust the Vs and Is with the display parameter on castlet.
Then adjust the display castlet with analog meter.
Setting Tr-Rec by Castlet

9. Choose continues parameter then setting Is to be


1600 mA.
10. Select manual menu, then change manual setting
to be auto
11. Stop the Tr-Rec, then back to main menu
12. Start again the Tr-Rec
13. Change program number from no.10 to be no.5
14. If needed, adjust again parameter of Vp, Ip, Vs
and Is between display of castlet and the analog
meter.
15. Finish
BACK TO CONTENT
CONTENT

 INTRODUCTION OF MCS II
 CALIBRATION OF TR-REC
 SUMMARY
Summary

 MCS II is a controller, it’s used for setting output of Tr-


Rec
 Calibration and setting of Tr-Rec can doing by keypad
castlet
 When we’ll do the calibration, do it with correctly step
 Don’t forget about PPE and LOTO

NEXT
Q&A
Thank’s for your attentions