Electrical Power
Cooling
Security/Surveillance and monitoring
24 by forever demand of Electrical Power in Data
Center is achieved with the following.
K-Electric Commercial Supply
H.V Room
Transformers
L.V Room
Generators
UPS
STS
PDU
Rectifier
DC DB
K-Electric provides 3 phase, 11 KV Electric
power to the Data Center which further goes to
the H.V room
Incoming from K-Electric comes in the H.V
room through Vacuum Circuit Breaker (VCB)
of 11 KV and 630 A. and further goes to the
transformers. H.V
room contains
panels for
switching.
1500 KVA each, Transformer Step-Down 11KV
to 220V Phase voltage and 380 Line to Line
voltages and output goes to
L.V Room
Here incoming from
transformers or
Generators goes
through series of panels
which improves Power
Factor, Synchronize
power and distributes
power to the UPS, Main
PDU’s, HVAC,
Building AC’s, Lighting
systems
In case of Failure of Primary power Supply
Diesel Generators of 1540 KVA each, gives
power to the Data Center Facility
LD Panel
For maintaining
building’s inside
temperature 27 Ac’s of
4 tons both floor
mounted and ceiling
mounted are installed
inside the building
Inside unit
Outer of 4ton
floor mounted
AC’s
Outers
To make Data Center Secure, from
unauthorized access and disaster, following
equipments are used.