GENERATOR PROTECTION
CLASSIFICATION
A. PROTECTION AGAINST ELECTRICAL
FAULTS
I. INTERNAL FAULTS
Short Circuit, Earth Fault, Interturn Faults, Rotor
Earth Fault, Unit Protections such as Differential,
REF, Interturn Fault Protections, Rotor Earth Fault
Protection.
II. EXTERNAL UNCLEARED FAULTS
Unbalanced Loading.
Field Failure
Pole Slipping
Over Voltage.
INFLUENCING FACTORS
Type of connection / neutral earthing.
Generator rating:
= 5.1875MVA, 4.15MW
X1=35%, X2=25%, X0=10%
Earthfault MVA = 3x Base MVA x 100
X1+ X2+ X0
= 3 x 5.1875 x 100 = 2.23MVA
35+25+10
Earthfault current = 22.23 x 103=1945A.
3 x 6.6