PEC UNIVERSITY OF TECHNOLOGY, CHANDIGARH

O/I
FIRE SAFETY
BY
Amit Sindher
(ASSISTANT PROFESSOR,CED)
 INSTALLATION OF FIRE SAFETY EQUIPMENT

1 COMPUTER CENTER

2 CENTRAL LIBRARY

3 INFORMATION TECHNOLOGY

4 E& EC BLOCK

5 ADMINISTATIVE BLOCK
 TECHNICAL SPECIFICATIONS OF FIRE PREVENTION AND FIRE SAFETY
MEASURES-

Sr. Name of TECHNICAL SPECIFICATION EMD


Building

Hose Reel/Down Comer, manually


1 Administrative operated electric fire alarm system,
block terrace water tank, fire brigade
connection (two way) with NRV (one 3000/-
complete unit)

a) Hose Reel/Down Comer, manually


2 Central Library operated electric fire alarm system,
terrace water tank, fire brigade
connection (two way) with NRV (one 6000/-
complete unit)
b) Automatic detection system on all
floors
c) Illuminated type Exit sign board
a) Manually operated electric fire alarm
system
3 Computer Centre b) Sprinkle system in basement 2000/-
c) Co2 Modular in server room
d) Illuminated type Exit Sign board

a) Hose Reel/Down Comer, manually


operated electric fire alarm system,
4 Information terrace water tank, fire brigade 2500/-
Technology connection (two way) with NRV (one
Deptt. complete unit)
b) Illuminated type Exit Sign Board

a) Hose Reel/Down Comer, manually


operated electric fire alarm system,
5 E&EC Deptt. terrace water tank, fire brigade 3500/-
connection (two way) with NRV (one
complete unit)
b) Illuminated type Exit Sign Board (two
blocks)
DRAWBACK OF TENDER
1 LACKNESS IN TECHNICAL SPECIFICATIONS

2 LACK OF KNOWLEDGE
 IMPROVED TECHICAL SPECIFICATIONS
ADMINISTATIVE BLOCK

Sr. Description
No. UOM Qty.
Fire Hydrant System
providing and fixing M.S pipes including all fittings
like couplings, bends, elbows, offsets, blind flanges,
plugs, tees flanges (flanges wall/ tank), etc. welding
joints (all type) as required, supports, cutting holes
and chases in brick or RCC walls/floors and making
good complete with excavating trenches of required
width for pipes etc. in any type of soil
(hard/dense/soft/muddy) including excavation for
socket stand dressing of sides ramming of bottoms,
1 depth up to 1 m including getting out the excavated
soil, and then returning the soil as required in layers
not exceeding 20 cms in depth including
consolidating each deposited layer by ramming,
watering etc. and disposing of surplus excavated soil
as directed with in a lead of 2 m.
Pipes confirming to I.S 1239 (Medium class)
1.1
a) 80 mm dia Meter 1
b) 100 mm dia Meter 30

Air Vessel for Fire Pump:


Supplying and fixing of air vessel of he following specifications
a. Diameter 200 mm
b. Shell Thickness: 10 mm
2 c. Dish Ends: 12 mm EACH
d. Height: 1500 mm
e. Finishing: Two coats of red enamel paint over primer out side and 1
two coats of epoxy coating inside.
f. Material of construction : M.S
g. Test Pressure: 20 KG/Sqcm.
h. Size of inspection flange: 150 mm dia
i. Height of supporting legs: 300 mm

Providing and fixing arch vibration elimination pads for pumps,


3. including bolting to foundations.
a. Type ‘A’ (For Jockey/Main pump). Each 8
Providing and fixing heavy duty PVC insulated,
PVC copper conductor cables 1100 v grade
including necessary support clamps and
4 connection lugs complete in all respects. Meter 50
a. Power cable 3 core 6 sqmm

Providing and fixings gunmetal landing valve


confirming to IS-5290 with 63 mm dia
instantaneous female coupling on the outlet
with S.S orifice 6 mm thick as required to
5 maintain 3.5 Kg/sq.cm, blank cap and chain, Each 4
necessary companion flanges (as per table “
E”) nuts, bolts, washer and gasket complete as
per specification. (ISI marked)
a. Single outlet

Providing and fixing first aid fire hose reel wall


mounting swinging type fitted with 20 mm dia
30 mtr. long high pressure hose IS. 5132 with 5
6 mm outlet gunmetal nozzle with shut off valve Each 3
conforming to I.S. 884-1969.
Providing and fixing 63 mm dia 15 mtr. long
rubberized fabric lined hose including male and
female instantaneous type coupling approved by
7 fire authority, machine wound with copper wire Each 8
complete in all respects. Hose shall confirm to
IS636 Type and coupling to IS 903-1975 (ISI
marked)
Providing and fixing standard short size branch
pipe nozzle 16 mm dia outlet with standard
8 instantaneous type 63 mm dia coupling. (ISI Each 4
marked)

Providing and fixing brass ball valve full bore type


with plastic coated lever and screwed female ends
tested to 20 kg cm 2 of approved quality as
9 specified.
a. 25 mm dia Each 4
b. 50 mm dia Each 4

Providing and fixing fire hose cabinet fabricated


from 16 gauge M.S. sheet with single or double
10 glazed front door and locking arrangement, Each 4
painted “Fire Red”.
Providing and fixing dial pressure Gauge with
isolation cock and copper pipe at hydrant station.
11 Dial diameter Each 4
a. 100 mm celebration 0-10 Kg/sq.cm.

Providing and fixing cast iron dual plate wafer type


non return valves of PN. 1.6 including nuts, bolts, 1.5
12 mm thick compressed asbestos gasket including
matching flanges as per table “E” complete
a. 100 mm dia Each 2
Providing and fixing gunmetal fire brigade inlet
breaching head as per IS: 904 specification tested for
13 20 kg/cm2 with 63 mm dia instantaneous type inlet
and 100 mm dia flanged outlet with built- in check
valve for fire brigade connection to underground
tanks and fire rises including companion flanges as
per table “E” including nuts, bolts and washers etc.
a) Two way Each 1
b) Four way Each 1
Providing and fixing C.I butter fly valves PN 1.6
complete with bolts, nuts 1.5 mm thick compressed
asbestos gasket companion flanges as per table E
14 complete.
a. 100 mm dia Each 4

Providing and fixing flow indicating switch on


sprinkler branch by cutting hole perpendicular to
flow line and inserting vane complete as per
15 manufacturer’s details.
a. 100 mm dia Each 4
b. 150 mm dia Each 4

Providing and fixing standard fire man’s axe (tested


16 for 20,000 Volts) with heavy insulated rubber Each 3
handle.

Providing and fixing 150 mm dia installation control


17 valve complete with all accessories i.e drain valve, Each 1
pressure gauge etc.
Jockey Pump:
fixing multi stage horizontal centifugal pump with
volute fronze impellerconnected to TEFC induction
moter suitable for 400/410 Volts, 3 Phase, 50 Cycles,
AC supply with the following specifications:
18 a) Capacity: 180 LPM
b) Head: 40 mtr.
c) HP: As required Each 1
d) RPM: 2900
e) Mover : Electric Moter driven
f) Pump foundation as per manufacturer

Main Fire Pump


Providing and fixing single stage horizontal centrifugal
pumping set withvolute bronze impeller connected to
a TEFC induction moter suitable for 410/440 volts, 3
phase, 50 cycles AC supply as per the detailed given
19 below:
a. Capacity : 450 LPM
b. Head: 40 meter Each 1
c. HP: as required
d. No of stages: single
e. RPM: 2900
Providing and fixing electric fire pump auto
20 panel. Main pump and Jokey pump auto start Each 1

21 Provding and fixing water storage tank with Each 1


foundation, capacity 5000 litre (Triple layer)

22 Providing and fixing pressure switch Each 2