Вы находитесь на странице: 1из 28

SIPROTEC 4

7SA6 Distance Protection


Tutorial

Specialist Power System Protection


Gustav Steynberg
PTD PA13 Nuremberg
Phone: +49 911 433 7012
Fax: +49 911 433 8301
Email: Gustav.Steynberg@siemens.com

Info - 1
Distance protection PTD PA13/ Steynberg/ 11.01.01
Using the 7SA6 Device Manual and
SIPROTEC System Description
• The Table of Contents is useful to jump to the desired description

• Protection Information is in Chapter 2: FUNCTIONS

• In the table of contents all the chapters for the individual protection
functions are listed

• For each protection function there are the sections


Method of Operation (description of the function)
Setting Notes (information for each individual setting)
Settings (table of settings and information applying to this function)

• Extensive use is made of logic diagrams to explain the


individual protection functions

Info - 2
Distance protection PTD PA13/ Steynberg/ 11.01.01
Practical Application Example for 7SA6

220 kV
100 km OHL

Z1 = 0,25 Ohm/km 85


Z0 = 0,8 Ohm/km 75
7SA6 IF Min = 2 kA (phase)
1&3 Pole trip IF Min = 0,5 kA (earth)
21 with Quadrilateral
Teleprotection - POTT

Info - 3
Distance protection PTD PA13/ Steynberg/ 11.01.01
Configuration

First step is configuration - Functions that are disabled here will not appear later.
Refer to Manual - Chapter 2.1 General
Info - 4
Distance protection PTD PA13/ Steynberg/ 11.01.01
Binary I/O
Refer to
System Description
Chapter 5
Relay PICKUP
Distance teleprotection send

Allocate the required


Trip L1
functions to the Trip L2
available binary Trip L3

inputs and outputs AR Close

The number of General supervision alarm


available binary
inputs and outputs
Relay alarm/live contact
depends on the
hardware version

Info - 5
Distance protection PTD PA13/ Steynberg/ 11.01.01
Routing in DIGSI Matrix

Route the selected functions to the binary inputs and outputs in the matrix
Info - 6
Distance protection PTD PA13/ Steynberg/ 11.01.01
Plant Data
220 kV
1200 / 1 220 kV / 0.1 kV Make a diagram
L1 of how the plant
L2 is connected to
L3 the relay
220 kV / 0.1 kV

L1 L2 L3

Info - 7
Distance protection PTD PA13/ Steynberg/ 11.01.01
Set Power system data1 - Transformers

Make sure the entered settings match the plant data


Refer to Manual - Chapter 2.1 General
Info - 8
Distance protection PTD PA13/ Steynberg/ 11.01.01
Power system data1 - Power system

Select the mode for zero sequence compensation: RE/RL and XE/XL or
K0 and angle K0 Refer to Manual - Chapter 2.1

Info - 9
Distance protection PTD PA13/ Steynberg/ 11.01.01
Power system data 1 - Breaker

Enter closing time of breaker if sync check with async closing is used
Refer to Manual - Chapter 2.1

Info - 10
Distance protection PTD PA13/ Steynberg/ 11.01.01
Setting Group A

Setting blocks for the functions enabled during configuration


are available in Setting Group A
(if setting group changeover is selected, also Group B, C and D)
Refer to Manual - Chapter 2.1

Info - 11
Distance protection PTD PA13/ Steynberg/ 11.01.01
Setting Group A: Power System Data 2
Select entry of impedance in primary or secondary values.
CT and VT ratio may not change after entry with primary values

Separate setting
for Z1 and
remaining zones

Refer to Manual Incorrect entries may lead to wrong protection operation


Chapter 2.1 or incorrect measured value / fault location data

Info - 12
Distance protection PTD PA13/ Steynberg/ 11.01.01
Calculation of residual compensation factors
Use the RE/RL and XE/XL or K0 and angle K0 setting (selected during configuration)

RE 1 R0 XE 1 X0
= - 1 = - 1
RL 3 R1 XL 3 X1
As only ratios are used either primary or secondary impedance may be used. The
values may apply to the whole line or be per unit length

R1 = 0,25 cos 85 = 0,022  R0 = 0,8 cos 75 = 0,207 


X1 = 0,25 sin 85 = 0,249  X0 = 0,8 sin 75 = 0,773 

RE/RL = 1/3 (0,207/0,022 - 1) XE/XL = 1/3 (0,773/0,249 - 1)


RE/RL = 2,80* XE/XL = 0,70
* Note that RE/RL setting increases earth fault reach in R direction. Recommend set < 2

In this example the same setting is used for Zone 1 and the other Zones
Info - 13
Distance protection PTD PA13/ Steynberg/ 11.01.01
Setting Group A: Line Status
The line status (open/closed) is required by several functions
(e.g. E/F protection blocking during single pole open).

Current, voltage and


auxiliary contacts
may be used to
check the line status.

After line closure


special protection
functions may be
activated for a set
Time (SOTF)

Refer to Manual
Chapter 2.1 Release of manual close command may be subject to sync check

Info - 14
Distance protection PTD PA13/ Steynberg/ 11.01.01
Setting Group A: Trip 1-/3-pole
The 3 pole coupling of a trip signal may be selected to with trip (e.g. simultaneous
earth fault on two parallel lines is tripped single pole) or to fault detection
(e.g. if the simultaneous fault on the parallel line can cause 3 pole coupling)

2 phase faults
without ground
may be tripped
single phase

This selection
is needed to
display all
setting options
Refer to Manual Chapter 2.1

Info - 15
Distance protection PTD PA13/ Steynberg/ 11.01.01
Setting Group A: Distance protection, general settings

This is similar
to ON/OFF with
binary input

Used to set
load area in
polygon

Single pole trip


in Zone 2 can
be selected

Refer to Manual
The overreach zone Z1b may be controlled by the recloser Chapter 2.2

Info - 16
Distance protection PTD PA13/ Steynberg/ 11.01.01
Calculate the Load Area setting
Maximum load current = 2200 A
Minimum operating voltage = 90%
Min Power factor cos = 0,85

RLOAD (min) = Umin / 3 ILmax

RLOAD (min) = 0,9  220 kV / 3  2200 A


= 95  (prim.)

Max Load Angle = 1,2 * arccos (cos  )


RLOAD (min)

Max Load Angle = 1,2* arccos ( 0,85)


= 38º Max Load Angle

Info - 17
Distance protection PTD PA13/ Steynberg/ 11.01.01
Setting Group A: Distance protection, Earth faults

Set the threshold


for earth fault
pickup

Additional
settings have the
supplement A

Refer to Manual
Chapter 2.2

Info - 18
Distance protection PTD PA13/ Steynberg/ 11.01.01
Reach and time co-ordination

Zone 1
Zone 2
Zone 3
Zone 4
Zone 5
t

-75% 0% 85% 100% 120% 150%


Info - 19
Distance protection PTD PA13/ Steynberg/ 11.01.01
Setting Group A: Distance protection, Time Delays

Set the zone


timers:
Separate
setting for
1 and multi
phase faults
in Z1, Z2 and
Z1b

The same parameters are Setting infinity () may be


also shown with the applied for clarity to
individual zone settings. unused zones.

Info - 20
Distance protection PTD PA13/ Steynberg/ 11.01.01
Setting Group A: Distance zones, Zone 1

Set mode for Zone1


- Forward
- Reverse
- Non-directional
- Inactive

Set reach for


Zone1 Primary
or secondary

Set time delay


for Zone1 The zone reduction angle is only available for Zone1
(Same as under (Used to prevent overreach resulting from load current
general settings in the presence of resistive faults)

Settings for further Zones is similar


Info - 21
Distance protection PTD PA13/ Steynberg/ 11.01.01
Distance zones, Reach Calculation
Line pos. seq. impedance XL1 = 0,25 /km at 85  i.e. 0,022 + j0,249 /km
Line zero seq. impedance XL0 = 0,8 /km at 75  i.e. 0,207 + j0,773 /km
Arc Voltage = 6 kV CTR = 1200/1 VTR = 220/0,1
Rline
For the resistance reach settings,
use only the arc resistance Rarc
Line resistance is covered
by the line angle setting

Rset
Zone 1: X1 = 0,85  XL1  100 km R1 = 1/2 Rarc = 1/2  6kV / 2kA
= 21,16  prim. = 1,5  prim.

Z sec = Z prim  CTR/VTR


Info - 22
Distance protection PTD PA13/ Steynberg/ 11.01.01
Setting Group A: Distance zones, Zone 1b
Zone1b is a controlled zone: Normally used as
overreach zone with tele-protection

Zone1b may be controlled by the automatic re-closer (internal or external)


for zone extension schemes

Info - 23
Distance protection PTD PA13/ Steynberg/ 11.01.01
Tele-protection : POTT
Zone 1
Zone 1b
Zone 3

Zone 1
Zone 1b
Zone 3

-75% 20% 0% 15% 85% 100% 120% 150%


Info - 24
Distance protection PTD PA13/ Steynberg/ 11.01.01
Setting Group A: Tele-protection for Distance prot.
The tele-protection scheme type was selected
during the configuration (POTT)

Two or three
terminal lines
can be
configured

Additional settings allows access to the timer settings: In most


cases the default settings are adequate

Info - 25
Distance protection PTD PA13/ Steynberg/ 11.01.01
Setting Group A: Fault Locator

The fault locator can be initiated by pick-up or trip

Load compensation may be activated (improves FL


output in the event of resistive faults with load current)
Refer to Manual
Chapter 2.18

Info - 26
Distance protection PTD PA13/ Steynberg/ 11.01.01
Setting Group A: High Current Switch on to Fault
Following energisation of the line (recognition of CB close)
the high speed SOTF clears bolted faults.

Function must be switched ON

Pick-up setting must be above


maximum expected charging current

Info - 27
Distance protection PTD PA13/ Steynberg/ 11.01.01
Saving and transfer of settings
Save the settings with the FILE Menu

To transfer settings to
the RELAY mode must
be ONLINE

Icon lights up when


settings in PC do not
match the settings in
the relay. Click icon to
transfer settings to
the RELAY

Information retrieval from the relay or file (if info was saved) is
possible here: event log, trip log etc. / primary and secondary
measured values / oscillographic recordings
Info - 28
Distance protection PTD PA13/ Steynberg/ 11.01.01

Вам также может понравиться