Lecture-03
Text Book
“Electric Machinery Fundamentals”
By
Stephen J. Chapman
Impedance Transformation
(to simplify the circuit for calculations)
THE IDEAL TRANSFORMER (cont…..
VP 1600
a 8 turns ratio (Transforma tion ratio)
VS 200
Ip
R / a 2R
VP=1600V R/ R/= 128k
R / 8 2 x 2k 128k
1600V IS 100mA
Now IP 0.0125A 12.5mA OR IP 12.5mA
128k a 8
Example-2
Rsource=512 Rsource=512 Ispeaker
Isource
V=120V
R/ R(speaker)=8
V=120V R(speaker)=8 Source
Isource
8 :1
Source
NP
a 8 (8 : 1 ratio)
120 V NS
Isource 230.8mA
512 8I R / a 2R ( spea ker) 8 2.8 512
2
Re fered to the primary
Power to the spea ker isource R( spea ker)
2 Rsource=512 Isource
( 230.8mA ) .8 0.43W
R/ = 512
V=120V
Source
2
Power to the spea ker isource R / ( spea ker) 120V
Isource 117 .19mA
(117 .19mA) 2 .512 7.032W 512 512I
Example 3
A 100-kVA, 2400/240-V, 60-Hz step-down transformer (ideal) is used between
a transmission line and a distribution system.
(i) Determine turns ratio. (a=?)
Ip = Is /a = 416.67 / 10 = 41.67 A
In Example 2
(a) Transform Primary side (source) impedance to the
secondary side.
(b)Transform the source to the secondary side.
(c) Find the secondary side (Ispeaker) current.
(d)Find the source current
(e) Why transformers rating (capacity) are given in VA (KVA)
Line Losses?
Vload?
V =480/0o
-37.8o
Iline =90.8/-37.8o
V =480/0o
-0.9o
Vload =454/-0.9o
Do We consider
Load Losses???
Solution (b)
Solution (b)
Solution (b)
Solution (b)
Solution (b)
Solution (b)
Without With
Transformer Transformer
Transmission 1484 Watts 16.4 Watts
Line Losses
Load Voltage 454/-0.9o V 479.7/-0.01o V
• Some of the Flux lines leave the iron core and pass
through the air are responsible for leakage flux.