Академический Документы
Профессиональный Документы
Культура Документы
GCB
UAT Trans.
26/11 kV Excitation
26/1.14
kV
load 11 kV
Generator
26 kV
load 3.3 kV
load 415V
Generator
TOSHIBA
Three Phase Synchronous Generator
Phase 3
Pole 2
Rated Power 934000 kVA
Armature Current 20741 A
Voltage 26 kV+5%
Rated Speed 3000 rpm
Frequency 50 Hz
Power Factor 0.85
Excitation Voltage 590 V
Field Current 5550 A
Stator Connection Y
Stator Winding Coolant Water
Rotor Winding Coolant Hydrogen
Stator Insulation Class F
Rotor Insulation Class F
Generator
Generator system Monitor
Inspection Carbon Brush
Monitor the temperature of stator winding, rotor
winding, stator core and bearing metal
Monitor the pressure temperature inlet/outlet of
water stator cooler
Monitor the pressure and temperature inlet/outlet
of hydrogen rotor cooler
Monitor the conductivity of water stator cooler
Monitor the purity of the hydrogen
Monitor the temperature inlet/outlet cooler of
hydrogen and water cooler
Monitor the pressure (difference with pressure H2)
and temperature of the hydrogen Sealing oil system
Monitoring the pressure and temperature of oil
lubrication
Monitor the Partial Discharge
Monitor the shaft voltage
Monitor the vibration
Generator Protection (REG 216)
21 Minimal Impedance Protection
24G Saturation (V/Hz) Protection
27 Undervoltage Protection
32.1 Reverse Power Protection (High Setting)
32.2 Reverse Power Protection (low setting)
40 Loss of excitation protection
46 Negative Sequence Protection
50BF Breaker Failure
51VVoltage Control Overcurrent Protection
59GN 95% Stator Ground Fault Protection
59 Overvoltage
64GN 100% Stator Ground Fault Protection
78 Pole Slipping Protection
81H Overfrequency Protection
81L.1 Overfrequency Protection (47.5Hz/10sec)
81L.2 Overfrequency Protection (47Hz/Inst)
87G Generator Differensial Protection
60 (VTFF) Voltage Balance Protection (VT fuse loss detection)
50 O/L Generator Overload Protection
Generator Protection
Neutral
Grounding
Transformer
To protect the generator from
the damage caused of fault
current.
Generator Transformator
TMT&D Transformator
YNd1
Freq 50Hz
Phase 3
Type of Cooling ONAN/ODAF
Rated Power 445/890 MVA
HV 525 kV
LV 26 kV
Tap-changer On-load
Oil
• Transformer 90000 L
• Tap-changer 600 L
• Radiator Bank 22400 L
Generator Transformer Monitor
Monitor any defect, abnormality sound (at fan, bushing, transformer body), leakage etc
Monitor the Partial Discharge and DGA (on-line)
Take a sampling oil to testing DGA and Dielectric Strengh test and also detect some
moisture at the oil (at lab)
Monitor the oil temperature, HV winding temperature and LV winding temperature
Monitor the Changing of the silica gel (color)
Generator Transformer Protection (REG 216)
From To
Generator Grid
To excit.
trans
87OA
Motor
To convert the electrical energy to mechanical energy
AC Motor DC Motor
Power
High or Low ambient Temperature
High Altitude
Duty Cycle
Excessive start
High Inertia Motor
Voltage and Frequency variation
Variable speed
Overload (SF)
Temperature that expose to the motor (insulation)
Name plate of Motor
Manufacturer’s name
Serial number
Number of phase
Rated Output
Rated Voltage
Rated Current
Frequency
Rated Speed or range of speed
Rated power factor
IP, IC, IM
SF
IP (Index Protection)
IC – Method of Cooling
IC8A1W7
Circuit Arrangment
Primary Coolant
Secondary Coolant
A Air
F Freon
H Hydrogen
N Nitrogen
C Carbon dioxide
W Water
U Oil
IC – Method of Cooling
Method of Movement
IM
Type of Constructions and
Mounting Arragment
IM V1 IM V2
Operating Motor
STARTING
M M
Operating Motor
Variable Speed
For AC motor
Partial Discharge
DGA online monitoring
Carbon Monoxide
Overheated Cellulose can
cause large quantities of
carbon monoxide
Overheated Cellulose
DGA online monitoring
Ethylene
Thermal in oil can cause
decomposition of oil that
produce ethylene and
methane
Overheated Oil
DGA online monitoring
Acethylene
Arcing can produce large
hydrogen and Acethylene
in oil. CO and CO2 may
also be formed if the fault
involves cellulose.
Arcing
DGA online monitoring
We do the on-line monitoring once a month to monitor and analize, in
normal condition
If there is a high alarm (one or some of gas increase), DGA offline will be
performed
DGA online monitoring
But when it need to take the sample for the offline DGA test, we have
make sure all (H2 CH4 C2H6 C2H4 C2H2 CO2 and CO) the gas have to
measure, so we can calculate the ratio of gas.
The use of gas ratio to indicate a single possible fault type inside
transformer
We can use evaluation of possble fault type by the Duval triangle or
Doernenburg ratio method or by Roger ratio method
Defect electrical yang terjadi di TBPP
Bearing motor
Motor (have to rewinding)
Lingting, hvac
VCB cannot operated (terlalu tidak pernah dan sering open-close)
NSPB short circuit (air masuk ke dalam)
GCB cannot operated (spring tdak charge)
Hydrogen leakage ( check using freon gas and freon detector, bocor di kabel
CT)
MOV (card rusak)
Change Excitation transformer (DGA result is not in good condition)
ESP short circuit in plate and discharge wire (the bolt is not to tighten and
the age)
MCCB, MCB broken
Transformer trip but no fault, because there are water inside the control box
Implementation for Banten Plant
For generator, during operation, we have to do the visual inspection
on carbon brush every week. Measure the length of the carbon brush
so we can calculate the consumption of brush for spare availability.
We have to monitor the shaft voltage. The limit is 10V. And we have
to clean the area shaft that grounded for once a month, so the
voltage can be grounded clearly. We have to monitor partial
discharge that happened inside generator for once a month. And
then, we have to compare the data to another data that similar to
our generator or we compare to the previous data so we can see
quality insulation of the generator by time.
Implementation for Banten Plant
For small to medium motor, we have to choose a proper
grease to greasing the bearing. Type of grease that will uses
is depend speed of the motor, temperature, load, type of
bearing. In choice of proper grease, we have to consider
availability of grease in our area, how many type of grease
that will we use, how much the grease will used so we can
keep our spare of grease in warehouse.
Implementation for Banten Plant
For transformer, during operation, we have to online monitor the
dissolve gases in oil transformer for once a month and we analize
so we can make a conclusion the condition of transformer and the
action that we have to take. In my plan, according IEEE C57, we
make four condition (Condition I, II, III, IV) it depend of evaluation
evaluation using individual gas and TDCG concentrations. To detect
some possible fault type, fisrt we can see the key gas that arise and
second is by analysis of the separate combustible gases generated.
We can use doernenburg ratio method or rogers ratio method or
duval triangle method or the other method. But we have to use two
or three method to take the final conclusion of possible fault type
in transformer. For off line condition monitoring, we can take the
sample of oil for once a year. We do some test such as DGA,
dielectric streght, moisture and etc to know the quality of the oil
and take action such as purifying the oil or change the oil.
Thank You
PT. LESTARI BANTEN ENERGI