Академический Документы
Профессиональный Документы
Культура Документы
1. 2. 3. 4. 5. 6.
Core Number of conductors. Insulation Impregnated paper. Metallica sheath To avoid entering of moisture. Bedding To prevent the sheath from mechanical injury. Armouring To prevent cable from mechanical injury. Serving Layers of fibrous material similar to bedding but named as serving.
INSULATING MATERIALS Rubber better mechanical props., but easily affected by moisture. Vulcanized India Rubber good mechanical strength but quickly
reacts with copper.
Impregnated Paper high insulation strength but hygroscopic. Varnished Cambric called as empire tape and is a hygroscopic. Polyvinylchloride high insulation resistance but low mechanical
properties.
Cross Linked polyethylene (XLPE): An electrical cable insulation is provided for a submersible pump used in oil and gas wells which is stable at moderately high temperatures, does not swell or deteriorate when subjected to well fluids, which can be obtained by using XLPE as insulating material. Advantages:
Excellent corrosion resistance. Reduces the potential of leaks. Can balance the water pressure. Better flexibility.
Parameters of cables: a. Physical Parameters. b. Fundamental Electrical parameters. Physical parameters: Outside diameter of inner conductor, d. Inside diameter of shield, D. Dielectric constant of the insulator, . The dielectric constant is often quoted as the relative dielectric constant r referred to the dielectric constant of free space 0: = r 0. When the insulator is a mixture of different dielectric materials (e.g., polyethylene foam is a mixture of polyethylene and air), then the term effective dielectric constant eff is often used. Permeability of the insulator. Permeability is often quoted as the relative permeability r referred to the permeability of free space 0: = r 0. The relative permeability of air will almost always be 1.
Shunt Capacitance per unit length, in. C=2 /ln(D/d) in farads per metre. Series Inductance per unit length, L=0 ln(D/d)/2 in Henrys per metre. Series Resistance per unit length, in ohms per metre. The resistance per unit length is just the resistance of inner conductor and the shield at low frequencies. At higher frequencies, skin effect increases the effective resistance by confining the conduction to a thin layer of each conductor. Shunt Conductance per unit length, in mhos per metre. The shunt conductance is usually very small because insulators with good dielectric properties are used (a very low loss tangent). At high frequencies, a dielectric can have a significant resistive loss.
Selection of cables
Cables are selected based on following parameters System voltage. Conditions of installation. Current rating. Short circuit level of the system. Bending radius. Current rating: Current ratings are chosen based on normal laying conditions, such as Maximum operating conductor temperature, Ambient air temperature, Ground temperature, thermal resistivity of soil and depth of laying.
Short circuit Ratings: Short circuit ratings can be calculated by using the following formula, Ish = kA/t Where, Ish = short circuit current in amps. A = area of the conductor in sq mm. t = duration of short circuit in seconds. K = 75.8 and 109 for aluminum and copper cables, respectively. Bending radius: While installing the cables, they should not be bent at radius less than 12*D, (D overall diameter of the cable).
Classification:
a. POWER CABLES
Low Tension Cable High Tension Cable Belted cables Screened cables Pressure Cables Up to 66 KV. Beyond 66 KV.
Low Tension Cable: up to 1 kv. one core of tinned stranded copper. serving layer made of fibrous material. not armoured, so as to avoid excessive Advantages: Simple construction with large copper section.
Suitable for 11 to 22 KV. Cores are insulated from each other by impregnated paper and another layer of impregnated paper tape i.e. paper belt, is wound around the grouped cores.
Gap is filled with fibrous insulating material. Belt is covered by Lead sheath. Low insulation resistance.
Disadvantages:
Screened Cables
H-Type cables
H-Type cables:
Has 3-core, where each core insulated by impregnated paper that is covered by aluminum foil. Additional conduction belt is provided over the cores.
Advantages:
Eliminates formation of air pockets or voids Utilization of aluminum foil increase the heat dissipating power of the cable.
Advantages:
Separate sheath minimized the core-to-core break down in effective manner. Bending of cables becomes easy due to limitation of overall sheath.
Disadvantages:
Thickness of these type of cables are very thin, so should be take more care while manufacturing.
Pressure Cables
Cables which are used beyond 66 kv are called as Pressure cables, and these are divided as two types namely OIL FILLED CABLES and GAS PRESSURE CABELS.
Has channels of ducts for oil circulation. Oil under pressure is kept constantly by means of external reservoirs, where the pressure suppress the insulation layers and is forced into voids, which is formed between the layers.
So, these cables are suitable for higher voltages in the range between 66 230 kv. Has three types like single core conductor channel, single core sheath channel and three core filler space channels.
Advantages:
Can carry heavy load current and operate at higher voltages . Low maintenance cost.
INSTRUMENTATION CABLES
Cables used for transmitting, receiving and controlling signals are called as instrumentation cables.
When many cables collect behind equipment or travel together under floor tiles or through cable trunking, other cables will cause interference and interrupt the data flowing through it. This type of interference is known as Electromagnetic Interference (EMI).
Shielded Twisted-Pair (STP) cables use a thin layer of foil wrapped between the twisted pairs and the outer sheath to prevent excessive EMI from interfering with the data.
Single foil or braided screen surrounding all four pairs in order to minimize EMI radiation and susceptibility to outside noise. Screened twisted pair is also called Foil Twisted Pair (FTP), or Screened UTP (sUTP).
UTP is the most common form of twisted pair wiring, because it is less expensive and easier to work with than STP (Shielded Twisted Pair).
UTP is used in Ethernet 10Base-T and 100Base-T networks, as well as in home and office telephone wiring.
The twist in UTP helps to reduce crosstalk interference between wire pairs.
FIRE RESISTANT CABLES: WHERE WE ARE USING? WHY WE ARE USING? WHAT IS THE CONSTRUCTION OF THIS?