In the mid-1800 s, Thomas Edison changed everyone's life where he perfected his invention of the electric light bulb. After 1879, George Westinghouse developed a device called a transformer to send the power over long distance. The transformer is based on two principles.
- First, that an electric current can produce a magnetic field (electromagnetism), - Second, that a changing magnetic field within a coil of wire induces a voltage across the ends of the coil (electromagnetic induction).
Power Transformer monitoring 2. New experience in the Transformer Diagnostics 3. Transformers of the Future 4. 3-Days stay: Experience at Hannover
Introduction
DGA enables to track the condition & gives
an early indication of transformer failures. Standard guidelines: IEC 60599: Guide to the interpretation of dissolved and free gases analysis IEEE Std C57.104-2008: IEEE Guide for the Interpretation of Gases Generated in OilImmersed Transformers CIGRE [http://www.cigre-a2.org/]
degradation C2H2/H2 >2: in main tank indicates OLTC contamination Rogers ratio method Duvals Triangle method
Introduction
The fault must be located if increased
proportions of hydrocarbon gases are found in the oil. preventative maintenance must be performed in time to avoid an unexpected total failure The most frequent sources of faults are the tap changers, bushings, the paper-oil insulation and the accessory equipment.
strands and high contact resistance in tap changers. The deviations between switching upwards and switching downwards are almost same. High deviations indicates high contact resistances caused by the contacts of the tap selector switches.
be analyzed. measures the peak of the ripple (ImaxImin) and the slope (di/dt) of the measuring current, as these are important criteria for correct switching. If the switching process is interrupted, even for less than 500us, the ripple and the slope of the current change dramatically.
and slope measurements for all three phases tapping UP should be similar as for tapping DOWN.
windings and clamping structures within power transformers by measuring their electrical transfer functions over a wide frequency range. 5 Hz up to 10 kHz defect in core & magnetic circuit 10 kHz up to 600 kHz deformation in winding geometry 600 kHz up to 10MHz abnormalities on the inter-connection and test system
filling into transformer Testing & commissioning Operating condition & condition monitoring [DGA, Oil & winding temperature, current loading]
- DGA testing ( for oil-filled transformer) - Additional Diagnostic testing ( such as SFRA,