Вы находитесь на странице: 1из 18

IEC 61850 Primer Communication Networks and Systems In Substations

February 16, 2005

GE Multilin Copyright

61850 Scope

GE Multilin Copyright

2 February 16, 2005

Abstract Communications Service Interface ACSI


Defines a set of Objects Defines a set of Services to manipulate and access those objects Defines a base set of data types for describing objects

GE Multilin Copyright

3 February 16, 2005

Anatomy of an IEC61850 Object Name


V
MX

A
MX

Functional Constraint

Logical Nodes
MMXU1 MMXU2

Logical Device (e.g. Relay1)

Physical Device
(network address)

MMXU2$MX$A =
Feeder #2 Current Measurements

GE Multilin Copyright

4 February 16, 2005

Logical node groups


L System LN (2) P Protection (28) R Protection related (10) C Control (5) G Generic (3) I Interfacing and archiving (4) A Automatic Examples: control (4) PDIF: Differential protection RBRF: Breaker failure XCBR: Circuit breaker CSWI: Switch controller MMXU: Measurement unit YPTR: Power transformer M Metering and measurement (8) S Sensor and monitoring (4) X Switchgear (2) T Instrument transformers (2) Y Power transformers (4) Z Further power system
equipment (15)

GE Multilin Copyright

5 February 16, 2005

Services Examples
GetData Read SetDataValues Write GetDataDirectory Read list of object names

GE Multilin Copyright

6 February 16, 2005

ACSI Services
ACSI Services LogicalDeviceDirectory GetAllDataValues GetDataValues SetDataValues GetDataDirectory GetDataDefinition GetDataSetValues SetDataSetValues CreateDataSet DeleteDataSet GetDataSetDirectory Report (Buffered and Unbuffered) GetBRCBValues/GetURCBValues SetBRCBValues/SetURCBValues GetLCBValues SetLCBValues QueryLogByTime QueryLogAfter GetLogStatusValues Select SelectWithValue Cancel Operate Command-Termination MMS Services GetNameList Read Read Write GetNameList GetVariableAccessAttributes Read Write CreateNamedVariableList DeleteNamedVariableList GetNameList InformationReport Read Write Read Write ReadJournal ReadJournal GetJournalStatus Read/Write Read/Write Write Write Write
7 February 16, 2005

Enable Self Describing Devices

GE Multilin Copyright

IEC61850 Profiles

GE Multilin Copyright

8 February 16, 2005

IEC61850 Documents
Basic principles Glossary General Requirements System and project management Communication requirements Substation Automation System Configuration Basic Communication Structure Part 8 Part 1 Part 2 Part 3 Part 4 Part 5 Part 6 Part 7

Mapping to MMS and Ethernet

Sampled Measured Values


Mapping to Ethernet

Part 9

Conformance testing

Part 10

GE Multilin Copyright

9 February 16, 2005

IEC61850 Primary Parts


Part 6-1: Substation Configuration Language (SCL) Part 7-2: Abstract Communications Service Interface (ACSI) and base types Part 7-3: Common Data Classes (CDC) Part 7-4: Logical Nodes Part 8-1: Specific Communications Service Mappings (SCSM) - MMS & Ethernet Part 9-2: SCSM - Sampled Values over Ethernet Part 10-1: Conformance Testing

GE Multilin Copyright

10 February 16, 2005

IEC61850 Substation Architecture


Station Bus 10/100/1000 MB Ethernet
Relay(s) Subscribe to Datasets

Relay IE

Relay IE Process Bus .1/1/10GB Ethernet

Relay IE

Remote Access

MU Publishes V/I/Status Datasets

Network

Clk1

MU

MU

MU

Clk2

PT1 I/O Optical PT2 I/O CT2 CT MU = Merging Unit

Optical I/O Optical PT CT

GE Multilin Copyright

11 February 16, 2005

Sampled Measured Values

GE Multilin Copyright

12 February 16, 2005

Peer to Peer Communications Functional Requirements


Relay
Bkr 1

Relay
Bkr 2

Relay
Bkr 3

Relay

...

Bkr N

Trip

BFI Message delivery to multiple devices simultaneously Fast Delivery (< 4ms)
GE Multilin Copyright
13 February 16, 2005

IEC61850 Generic Object Oriented Substation Event - GOOSE


Device to multi-device communication Local or Wide Area Bridgeable but Non-routable User-defined Dataset sent in an Ethernet Multicast message Message sent on change of state as well periodically to enable detection of device failure Reliability effected through message repeat GOOSE Header:
Multicast Address Name Time Until Next GOOSE Etc.

User-Defined Dataset
Status Information Analog Values Data Quality Time

GE Multilin Copyright

14 February 16, 2005

SCL Substation Configuration Language


Description language for communication in electrical substations related to the IEDs XML based language that allows a formal description of Substation automation system and the switchyard and the relation between them IED configuration
GE Multilin Copyright
15 February 16, 2005

SCL File Types


SSD: System Specification Description.
XML description of the entire system.

SCD: Substation Configuration Description. XML description of a single substation. ICD: IED Capability Description.
XML description of items supported by an IED.

CID: Configured IED Description.


XML configuration for a specific IED.

GE Multilin Copyright

16 February 16, 2005

Benefits of IEC61850
High-level services enable self-describing devices & automatic object discovery saving $$$$$ in configuration, setup and maintenance. Standardized naming conventions with power system context eliminates device dependencies and tag mapping saving $$$$ in config., setup, and maint. Standardized configuration file formats enables exchange of device configuration saving $$$$ in design, specification, config., setup, and maint.
GE Multilin Copyright
17 February 16, 2005

Benefits of IEC61850 - 2
Higher performance multi-cast messaging for inter-relay communications enables functions not possible with hard wires and save $$$$ in wiring and maintenance. Multi-cast messaging enables sharing of transducer (CT/PT) signals saving $$$$ by reducing wiring and connection costs
GE Multilin Copyright
18 February 16, 2005