Академический Документы
Профессиональный Документы
Культура Документы
1. Conventional
A conventional fire alarm
system is often the
natural choice for smaller
applications or where
budget constraints exist.
Conventional systems
use zoning to define
areas and where
detectors are considered
as one circuit.
2. Break glass call points should be located so that no person need travel more than
30m from any position within the premises in order to give an alarm.
3. Generally, call points should be fixed at a height of 1.4m above the floor, at easily
accessible, well-illuminated and conspicuous positions free from obstruction.
4. The method of operation of all call points in an installation should be identical unless
there is a special reason for differentiation.
5. Manual and automatic devices may be installed on the same system although it may
be advisable to install the manual call points on separate zones for speed of
identification.
The following notes give guidance for the correct use of alarm sounders:
3. All audible warning devices used in the same system should have a similar
sound and be distinct from any other audible alarms used for other
purposes. Except in noisy areas where high performance sounders may be
required.
4. A large number of quieter sounders rather than a few very loud sounders
may be preferable to prevent noise levels in some areas from becoming too
loud.
5. It is unlikely that sounder noise levels in a room will be
satisfactory if more than one dividing wall or door separates it
from the nearest sounders.
At least one sounder per fire compartment will be necessary.