WHY WATER CONSERVATION ?

PLEASE REMEMBER Only 2.5 % of the worlds water is fresh water. And a tiny fraction (0.007%) of all water on earth is accessible for direct human uses. Wet Condenser cooling for 1000 MW plant requires 3000 M3/ Hr water, which can feed Rural Population of ONE Million.
Air Cooled Condensor/adp 1

Please Ponder
Power generators will benefit by water conservation as local & regional supplies will last longer. So future plant operation will be guaranteed.

Accelerated approval of construction permit.


Shortened project schedule.(No large barrage & Pipelines or canals for raw water )

Better economics and Siting options.

Air Cooled Condensor/adp

WATER WILL BE SCARCE & COSTLY


As water will become scares & costlier,TPS may be compelled to go for RETROFIT dry cooling towers. This will be an avoidable extra cost. Dry cooling worldwide has grown 20 times in last 5 years. China already has 30,000 MW Dry cooling installations. As per National Policy , USA is adopting Dry Cooling Systems even for Non-Arid Regions.

Air Cooled Condensor/adp

VIDARBHA
Just think about 35000 40000 MW upcoming Thermal Projects in Vidarbha. H.C.S.D. system for ash disposal and Dry Cooling can ensure water supply for DRINKING AND IRRIGATION in this dry area. The State can have POWER and save precious water for Drinking & Irrigation. Water pollution will greatly reduce.
Air Cooled Condensor/adp 4

Water needs of a Thermal Power Station A 210 MW TPS needs water for-

1. 2. 3. 4. 5. 6.

Boiler water make-up (D.M. Water-25 M3 / Hr) Drinking Water ( 5.0 M3 / Hr) Water for Wet Ash Handling (750 M3 / Hr) Cooling Tower water Make-up ( 650 M3 / Hr) Service Water ( 10 M3 / Hr) Total = 1440 M / Hr.

Air Cooled Condensor/adp

Air Cooled Condensor


A T.P.S. needs large quantity of Cooling Water. Recently, during last summer(2010), six units of Chandrapur TPS were shut down due to water shortage. Also, water is getting costlier and scarce. An air cooled condenser overcomes these limitations. Site restrictions are also overcome. No expenditure on chemicals for water treatment. Life time cost of a dry cooling tower is surely less than conventional evaporative cooling tower. Dry cooling tower cost may be 2.5 times that of a conventional evaporative cooling tower.
Air Cooled Condensor/adp 6

H.C.S.D. FOR WATER CONSERVATION

Typical lean slurry disposal has slurry concentration of 15-20 % only.(20% ash in slurry). i.e. 100 M.T. of ash needs 400 M3 of Water. But High Concentration Slurry Disposal system need only 65-70 M3 of Water for 100 MT ash. A reduction of 330 M3 of water consumption for 100 MT of Ash. MORE THAN 80% SAVING OF WATER. HCSD system is running successfully at Khaperkheda TPS for last 11 years.
Air Cooled Condensor/adp 7

COOLING TOWER MAKE-UP


Conventional Cooling Tower cools the water by Evaporative Cooling. Hourly evaporation = Hourly steam flow to condenser. In addition, there are 2-3 % drift loss and Blow down loss to maintain water quality. The DRY AIR COOLING eliminates this water consumption almost totally. The make up reduces by 95 % or more.

Air Cooled Condensor/adp

Forced Draft Dry C.T.

Air Cooled Condensor/adp

Site selection and water clearances


The pragmatic developer may select dry cooling early in a project because, It increases plant siting options and, Its use can significantly accelerate approval of construction permits, Because water use issues are taken off the table. Shortening a project schedule by even six months can completely change the economics of a project and, Easily balance the increased capital cost of dry cooling options
Air Cooled Condensor/adp 10

Examples of EXTRA COST 1. Parli TPS Huge barrage on Godavari and two stage pumping of water. Reservoir at Naikotwadi. 2. Paras TPS Barrage. 3. Koradi & Khaperkheda TPS 7 day reservoir and 22 Km long pipe line of 1600 mm dia.Bridges on Kolar & Kanhan rivers. 4. Also construction of Salt Lagoons at all power stations and Soften Water plants. 5. Chlorination plants. (Ozonization Plants.) 6. Serious damages to Cooling Towers and repair costs at Nasik & Koradi TPS.
Air Cooled Condensor/adp 11

Some Costing Evaporative Cooling Tower- 270 MW unit 22.0 Crores Total Plant cost 270 x 6.0 =1620.0 Cr. Dry Cooling Tower 22 x 2.5 = 55.0 Cr. Extra expenditure = 33.0 Cr.only Salt consumption 2000 MT/Yr, @ Rs.2000 /MT, Cost Rs.40 lakhs/year. 25 years cost = 10 Cr. There is saving in cost of salt lagoons, Godowns, Softening plant etc. Huge saving in annual cost of water itself.(Next slide) No blow downs and water pollution.
Air Cooled Condensor/adp 12

COST OF MAKE-UP WATER


Unit Capacity MW C.W. Make-up M3/Hr ANNUAL-CW Make-up in Mn. M3 Plant PLF NET ANNUAL-CW Make-up Mn. M3 RATE-Rs./Cub.Mtr ANNUAL COST OF WATER in Rs.Cr 210 500 4.38 0.90 3.94 5 1.97 270 643 5.63 0.90 5.07 5 2.53 300 714 6.26 0.90 5.63 5 2.82 500 1190 10.43 0.90 9.39 5 4.69 660 1571 13.77 0.90 12.39 5 6.19

Water cost may escalate @ 4-5 % per year.


Air Cooled Condensor/adp 13

Life Cycle Cost

Considering all the costs, HELLER cooling system cost can be as low as 2/3rd of Conventional Wet Cooling System.

Air Cooled Condensor/adp

14

In US and Europe
Dry cooling in the U.S. is not limited to arid regions but is also specified for plants sited in eastern, northern, and mountain areas where water is abundant. In recent years, there are many more reasons to consider dry cooling in general, and the air-cooled condenser (ACC) in particular, than just the lack of available water. Dry cooling applications are becoming a standard power plant design option. In fact, even areas with abundant water resources--like England, Ireland, Belgium, Luxemburg, and northern Italy are adopting the technology. The largest combined-cycle plant in Europe is rated at 1,200 MW and uses an air-cooled condenser.
Air Cooled Condensor/adp 15

Natural Draft Dry Cooling Tower

Air Cooled Condensor/adp

16

Dry Steam Condenser or Dry C.T.


Steam may be condensed in the cooling tower . OR, A surface(or Jet) condenser may be used and the cooling water is cooled in the dry C.T. In both cases Evaporative Water Loss is eliminated. Because the water circuit is a closed one and there is no loss. Just consider a modern car.Earlier the radiator had to be topped up daily. Now, one can travel thousands of miles without topping up the radiator.
Air Cooled Condensor/adp 17

FREE COOLING
. An indirect dry-cooling system was installed at the 6 x 686-MW power plant in Kendal, South Africa. In this cooling system design, water is circulated from a standard condenser to the tower, where it enters a series of heat exchange elements on the base. Air enters the bottom periphery of the tower, passing over heat exchange elements. The heated air rises inside the tower, pulling in more cool air. No fans are required.

Air Cooled Condensor/adp

18

Waterless condensing
Steam enters the air-cooled condenser at the top (blue pipe) of the heat exchangers, flows downward through the heat exchanger tubes, and it condenses and is captured in pipes at the base of the heat exchangers. The condensate is then returned to the boiler water system. Mechanical fans force air over the heat exchangers.
Air Cooled Condensor/adp 19

DRY COOLING MAY BE N.D.C.T. OR I.D.C.T. Heller system is an indirect dry cooling plant. The Power Plant Waste Heat is initially transferred in a Condenser (Preferably Jet Type) to a CLOSED C.W.Circuit. Heat pick-up by the C.W. Water is rejected to Ambient Air in FIN TUBE type heat exchanger. Air moving can be either Natural or Forced. i.e. N.D.C.T. OR I.D.C.T.
Air Cooled Condensor/adp 20

Initial Temperature Difference


I.T.D. is the Temperature difference between CONDENSING STEAM and Ambient Air. I.T.D. is the driving force for Heat Transfer in Dry Cooling. Typical ITD value range : 28 36 Deg.C. The difference between ITD values of DC Jet Condenser and Surface Condenser is : 3.5 4.5 Deg.C. This is about 15 % of the Driving Force. Therefore, Dry Systems with SURFACE CONDENSER need a LARGER COOLING TOWER. [ water flow rate, heat exchanger surface area, mechanical equipment,and civil construction.]

Air Cooled Condensor/adp

21

Largest Dry Cooled CCPP 3 x 770 MW GEBZE & ADAPAZARI 2002 TURKEY.

Air Cooled Condensor/adp

22

HELLER SYSTEM (With Supplemental Spray)

Air Cooled Condensor/adp

23

Heller System (With assisting wet cells)

Air Cooled Condensor/adp

24

200 MW Trakya CCPP, Turkey (ABB)

Air Cooled Condensor/adp

25

2 x 600 MW coal fired Yangcheng P.S. China.

Air Cooled Condensor/adp

26

Russia : Strogino Co-Gen CCPP , 2 x 200 MW. With supplemental spray.

Air Cooled Condensor/adp

27

Modugno CCPP 800 MW, Italy (2008) IDCT.

Air Cooled Condensor/adp

28

Modugno CCPP 800 MW, Italy (2008) IDCT. front view

Air Cooled Condensor/adp

29

Air Cooled Condensor/adp

30

Air Cooled Condensor/adp

31

Air Cooled Condensor/adp

32

Air Cooled Condensor/adp

33

Air Cooled Condensor/adp

34

Air Cooled Condensor/adp

35

Air Cooled Condensor/adp

36

Air Cooled Condensor/adp

37

Air Cooled Condensor/adp

38

Air Cooled Condensor/adp

39

Air Cooled Condensor/adp

40

Вам также может понравиться