Cooling
towers are heat removal device used to transfer waste heat to the atmosphere.
NATURAL
DRAFT
MECHANICAL
DRAFT
INDUCED DRAFT
INDUCED DRAFT CROSS FLOW INDUCED DRAFT, SINGLE FLOW CROSS FLOW TOWER INDUCED DRAFT, DOUBLE FLOW CROSS FLOW TOWER INDUCED DRAFT COUNTER FLOW
FORCED DRAFT
No fan required.
Concrete tower nearly 200 m.
Cross flow
Mechanical draft, which uses power driven fan motors to force or draw air through the tower. Large fans to force air through circulated water Can be grouped, e.g. 8-cell tower
mechanical draft tower with a fan at the discharge which pulls air through tower.
fan induces hot moist air out the discharge.
The
Types
Hot
Air blown through tower by centrifugal fan at air inlet Advantages: Suited for high air resistance due to Centrifugal fans Disadvantages: recirculation due to high air-entry and low air-exit velocities
Range
Approach Effectiveness Cooling
capacity loss
Range
Difference between cooling tower outlet cold water temperature and ambient wet bulb temperature:
Approach
= 100 x (CW temp CW out temp) / (CW in temp Wet bulb temp) High effectiveness = good performance EFFECTIVENESS= = {9.4/(9.4+4)}*100 = 70.14%
Approach
WET BULB TEMPARATURE: The minimum temp to which water can be cooled is the wet bulb temp. of the ambient air.
Water quantity (m3/hr) evaporated for cooling duty = theoretically, 1.8 m3 for every 10,000,000 k Cal heat rejected
Ratio of dissolved solids in circulating water to the dissolved solids in make up water
Capacity, Hot Water Temperature Cold Water Temperature Wet Bulb Temperature Evaporation Loss % Drift Loss Maximum % Nominal Dimensions Width Length Height
One
plus an additional one for each 300 m2 One for each 30 m of perimeter of the structure protected. Condition 1:
Area of Cooling Tower = 176.64 x 16.56 = 2925.1584 Sq Mtrs Number of Down Conductors = 1 + (2925.1584-100)/300 = 10.42 No's ~ 11 Nos
Condition
2:
The perimeter of Cooling Tower = 2 (176.64 + 16.56) = 386.4 Mtrs Number of Down Conductors = 386.4/30 =12.88 No's ~ 13 No's 12 down conductors are to be considered
No of Motors Make
: 13(11W+1 Stand by+1 Spare) : MARATHON ELECTRIC MOTORS(INDIA) LIMITED Output : 75KW (100HP) Phase : 3 Voltage : 440 V Frequency : 50 Hz Sync. Speed : 1500 rpm Duty : S1 Full Load amps : 128Amps Insulation Class : F
Cooling Towers