Вы находитесь на странице: 1из 12

FIexi BTS backup soIution

2 Nokia Siemens Networks Presentation / Author / Date


For internal use
Backup time 5-10 minutesBackup time 2.5 hours Backup time 3.6 hours
!ower and backup soIution exampIes for
2G/3G Nokia FIexi BTS Sites
Nokia
Flexi
power
module
Micro BBU
with 3 kW
rectifier and
62 Ah
battery
capacity
Wall and
pole
mountable
Nokia Flexi outdoor cabinet Nokia Flexi outdoor cabinet
with MIBBU with MIBBU
Nokia Flexi power Nokia Flexi power
module module
Micro BBU Micro BBU
3 Nokia Siemens Networks Presentation / Author / Date
For internal use
FIexi !ower ModuIe F!MA
Example configuration from FPMA with:
3 Flexi Power AC/DC sub-modules FPAA (230VAC -> 48VDC)
1 Flexi Power Battery FPBA
+
-
48VDC
output to
BTS
AC input
cabling
to FPMA
AC feed to
FPAA (3pcs)
4 Nokia Siemens Networks Presentation / Author / Date
For internal use
FIexi !ower Battery sub-moduIe F!BA
Features
Light weight / small size
System Compatibility
High Reliability sub-module
No Periodical Maintenance
No hazardous material for Environment
Long life cycle
Excellent discharge rate characteristics
Advantage
Space saving
Less construction cost
Easy handling and high safety
Environment friendly
High operational reliability
Excellent battery performance
Usable with any indoor/outdoor BTS Site
Option to FIexi !ower ModuIe F!MA for
WCDMA HSPA BTS
GSM/EDGE BTS
WiMax BTS
any 48 VDC equipment
5 Nokia Siemens Networks Presentation / Author / Date
For internal use
OptionaI FIexi AC !ower ModuIe F!MA
FPMA is AC/DC Power Module frame
with 4 sub-module slots for rectifiers and batteries
RF Module
RF Module
System module
Power Module
AC in
DC
Sector 2
Sector 3
FPMA with
FPAA
FPBA
AC in
DC
A
C
Flexi Power AC/DC rectifier FPAA
1 kW DC power per FPAA
B
Optional Flexi Power Battery FPBA
5-10 minutes for 2+2+2 (1*FPBA)
B
A
C
Example configuration for 2+2+2
2 x FPAA (AC/DC rectifiers)
2 x FPBA (Lithium-on batteries)
About 15 minutes back up
FPAA supports voltage range 184 . 276 VAC
FPAA supports voltage range 0 . 276 VAC with FPBA
FPF
System ModuIe *
RF Module Sector 1
6 Nokia Siemens Networks Presentation / Author / Date
For internal use
FIexi AC !ower ModuIe usage aIternative x
Big back up time:
-No additional cabinet
- Space, constructions, time, crane, work etc
savings
Back up solution for Remote RF-heads use, if
hours are needed also for long distance RF
heads
RF Module
RF Module
RF Module
System module
Power Module
RF Module
RF Module
RF Module
AC in
DC
A
C
A
C
B
System ModuIe
B
Power Module
B B B B
Locally sourced
connection box
P55 box needed if outdoors
7 Nokia Siemens Networks Presentation / Author / Date
For internal use
To System Module DC input
Locally sourced
DC cable connection
and optional Fuses
P55 box needed if
outdoors
FSEC can/may re-used if
new type of inlets can be
found.
Anyway with four screw
terminals this can be done
FPAA FPAA FPBA
230 VAC
48 VDC
48 VDC
48 VDC
+ +
- -
FPMA #1
FPMA #2
FPMA #3
FPBA
FPBA FPBAFPBAFPBA
FPBA FPBAFPBAFPBA
FIexi AC !ower ModuIe usage aIternative 5
when more battery back-up time is needed
8 Nokia Siemens Networks Presentation / Author / Date
For internal use
ong-term Integrated Battery Back-up Options
FCSA
FRMx 6000 + batteries
(new)
Requires aIways a cabinet
I!20 rectifier => FCSA needed in
Outdoor cabinet instaIIation
MiBBU
New rectifier moduIe fitting both
cabinet and moduIe instaIIations
3 * 2000W
With the I!54 rectifier variant, no
need for extra I! protection
Fast and easy instaIIation
Nokia Siemens Networks Presentation / Author / Date
For internal use
FRMx FIexi Rectifier ModuIe 6000 (New)
FRMx is going to be available in two different HW variants
P20 based solution for indoor applications
P55 based solution for outdoor applications
x= B/C; code for OEM manufacture Supplier1/Supplier2 as in MBBU
FRMx is meant to be a common solution for all Flexi 2G and 3G platforms
Aim to replace current MBBU in Flexi applications
FRMx will be equal to Flexi module in terms of dimensions and weight supporting
Flexi platform modularity
Same fixing points
Same mounting options
Wall, pole, stack
FRMx brings some new possibilities for Flexi applications
FRMx outside FCSA => more LTE space inside FCSA
FRMx inside FCOA => more space for Flexi modules inside the cabinet
10 Nokia Siemens Networks Presentation / Author / Date
For internal use
FRMx TechnicaI Content
FRMx have a scalable output power up to 6kW
Max 3pcs of 2kW rectifiers
AC connection either single or three phase
Operating temperature range -35 to +55C
Wide operating voltage range from 85 to 310VAC
FRMx includes DC connection points for
Max 2 BTS's
Max 3 battery strings
No space for batteries inside FRMx
Battery banks reside in- or outside of the BTS cabinet or beside the
stack
11 Nokia Siemens Networks Presentation / Author / Date
For internal use
Targeted FRMx AppIications
FCSA
Any 3
rd
party 19" rack
WaII/!oIe instaIIation with FIexi
Stack instaIIation with FIexi
FIexi OD cabinet
(in/outside FCSA)
FIexi ID or 3
rd
party cabinet
12 Nokia Siemens Networks Presentation / Author / Date
For internal use

Вам также может понравиться