DEE 2961: INDUSTRIAL INSTALLATION (Wiring)

Prepared by: Noor Zaihah Jamal 09-4242158

Content
Schematic diagram Wiring diagram i, lighting ii, switch socket outlet iii, Door bell circuit iv, DOL circuit

Schematic drawing
To show the distribution of electric power from source to customer final circuit (distribution fused board, DFB) How to draw i) The symbol must be balanced/ same size

ii) The current rating, voltage rating and types of component shall be stated on the symbol

Schematic drawing (cont)


iii) Drawing direction shall begin from top to bottom or left to right depends on normal reading style.

Schematic drawing (cont)


iv) DFB shall include fuses and circuit breakers used or spare c/w current rating.

v) Cable size shall be stated including Type and cable size Circuit and wiring type

Schematic drawing (cont)


iv) Each final circuit shall state the load type, current rating & quantity.

Main circuit
Incoming supply Neutral Link Services fuse

Shall complied IEE Regulation


Isolation & over current protection Over current protection Residual Current or Earth Leakage current protection

Kilowatthour meter

kWh

Main switch & Fuse

RCCB

Distribution Board

Main circuit
Symbol Name
Services Fuse & Neutral Link

Function
To Limit maximum current rating

kWh

Kilowatt-Hour meter
Main Switch & fuse

To record usage of total energy

1. 2.

To switch off customer circuit when needed To disconnect circuit when short circuit and over current occurred

Main circuit
Symbol Name
RCCB

Function
To cut off circuit when have leakages current to earth.

Distribution Box To locate a Miniature Circuit Breaker (MCB) and Fuse.

Main wiring circuit


Electrical circuit Kilowatthour meter Fuse / MCB

Services fuse

kWh

Main switch & Fuse

Distribution Board RCCB

incoming

Neutral Link Earthing Electrode

Final Circuit

Main Switch

6A RCCB 16A

Schematic Diagram

30A SPN

40A 100 mA

16A

Final Circuit

Wiring Diagram

Final Circuit
Reference for final circuit:
Circuit Type Over Current Protection Rating (Fuse or MCB) Cable size (mm2) Cable type (w/o conduit) Maximum Floor Area (m2) Maximum total number of fittings -

Main circuit

60A or 63A (refer to maximum demand)


30A or 32A (refer to maximum demand) 6A or 10A 30A or 32A 30A or 32A 30A or 32A 20A

16/25

PVC/PVC

Main circuit

6/10

PVC/PVC

Lighting Cooker/heater Socket Outlet 13A (Ring circuit) Socket Outlet 13A (Radial circuit) Socket Outlet 13A (Radial circuit)

1.5 4.0 2.5 4.0 2.5

PVC/PVC PVC/PVC PVC/PVC PVC/PVC PVC/PVC

100 50 20

10 1 10 6 2

Wiring diagram

Lighting Circuit Power Circuit DOL Circuit Door Bell Circuit

Lighting Circuit
FUSE/MCB (Amp) 10A CABLE SIZE (mm) -1.5 mm MAX POWER(watt) - 1000/1200

Single light point controlled by a one way switch (S1 Control L1)

MCB 10A

(S1 Control L1)..Cont

MCB 10A

Two light points controlled by a one way switch (S1 Control L1 & L2)

MCB 10A

(S1 Control L1 & L2)..Cont

MCB 10A

Two light points controlled by two one way switches (S1 Ctrl L1 & S2 Ctrl L2)

MCB 10A

(S1 Control L1 & S2 Control L2)..Cont

MCB 10A

Single light point controlled by two way switch (S1 & S2 Control L1)

MCB 10A

(S1 & S2 Control L1)..Cont.

MCB 10A

Two light points controlled by two way switch and intermediate switch (S1, S2 & S3 Control L1 & L2)

MCB 10A

(S1, S2 & S3 Control L1 & L2)..Cont

MCB 10A

Socket Outlet Single Socket

MCB 20A

Socket Outlet Single Socket

MCB 20A

Socket Outlet Radial Connection

MCB 20A

Socket Outlet Radial Connection

MCB 20A

Socket Outlet Ring Connection

MCB 32A

DOOR BELL CIRCUIT

MCB 6A

D.O.L Direct On Line Circuit

MCB 32A 3 Phase