MECHANICAL AUXILIARY SYSTEMS COMPRISES FOLLOWING : 1. SEAL OIL SYSTEM 2. GAS SYSTEM 3. PRIMARY WATER SYSTEM 4.

WASTE GAS SYSTEM 5. WASTE FLUID SYSTEM

SEAL OIL SYSTEM IS DOUBLE FLOW TYPE, HAVING SEPARATE HYDROGEN SIDE SEAL OIL CIRCUIT AND AIR SIDE SEAL OIL CIRCUIT .

ADVANTAGES OF DOUBLE FLOW SEAL OIL SYSTEM PERFECT SEALING RESULTING TO BARE MIN. HYDROGEN LOSS BETTER HYDROGEN PURITY .

VACUUM TREATMENT OF THE SEAL OIL AND RESULTING HYDROGEN LOSSES ARE AVOIDED.

SHAFT SEAL

HYDROGEN SIDE SEAL OIL CIRCUIT

SEAL OIL TANK AC SEAL OIL PUMP 2X100% DUTY SEAL OIL COOLERS DUPLEX OIL FILTER DEFFERENTIAL PRESSURE REGULATING VALVE PRESSURE EQUALISING VALVE EE PRESSURE EQUALISING VALVE TE

AIR SIDE SEAL OIL CIRCUIT MAIN SEAL OIL PUMP DRIVEN BY AC MOTOR STANDBY SEAL OIL PUMP DRIVEN BY AC MOTOR EMERGENCY SEAL OIL PUMP DRIVEN BY DC MOTOR 2X100% AIR SIDE COOLERS

DUPLEX OIL FILTER DIFFERENTIAL PRESSURE REGULATING VALVES

SEAL OIL EQUIPMENTS SEAL OIL SYSTEM EQUIPMENTS ARE MOUNTED BASICALLY ON THE FOUR UNITS SEAL OIL UNIT SEAL OIL PUMP MOTOR UNIT SEAL OIL VALVE RACK MEASURING INSTRUMENT RACK

SEAL OIL SYSYTEM

SEAL OIL SYSTEM

THE GAS SYSTEM GAS UNIT HYDROGEN DISTRIBUTOR CO2 DISTRIBUTOR NITROGEN DISTRIBUTOR GAS DRIER

GAS SYSTEM

C02 SUPPLY

CO2 IS REQUIRED IN THE GENERATOR TO CREATE AN INERT ENVIRONMENT IN THE GENERATOR CO2 AVAILABLE WITH A PURITY GREATER THAN OR EQUAL TO 99.9%. GAUGE PRESSURE:1-2.5 BAR VOLUMETRIC FLOW RATE:144-216M3/HR.

H2 SUPPLY
HYDROGEN

SHALL BE AVAILABLE WITH A PURITY LEVEL OF 99.9% GAUGE PRESSURE: 8-9 BAR VOLUMETRIC FLOW RATE:144216M3/HR. CYLINDER CAPACITY:7M3.

N2 SUPPLY

NITROGEN SHALL BE AVAILABLE WITH A PURITY OF 99.9%. NITROGEN IS REQUIRED FOR REMOVING AIR ABOVE THE WATER LEVEL IN THE PW TANK. REMOVAL OF AIR ENSURES REMOVAL OF OXYGEN DISSOLVED IN PRIMARY WATER THUS ELIMINATING RISK OF CORROSION.

GAS DRIER

GAS DRIER

TECHNICAL DATA
MEDIUM: FLOW RATE: DEW POINT OF OUTLET GAS: SILICA GEL FILLING: HYDROGEN 50 M3/HR. (-) 40 DEG C 19KG/ TOWER

ABSORPTION TIME:
REGENERATION TIME: HEATER RATING: TOWER SIZE: NO. OF DESSICANT TOWERS:

8 HOURS
3.5HOURS 3KW, 415V DIA219.1X750 TWO

DESIGN PERSSURE: HEIGHT OF DESSICANT COLUMN:

10 BAR 750 MM

CONTACT TIME OF HYDROGEN


WITH DESSICANT: PRESSURE DROP ACROSS DESSICANT BED: AIR BLOWER CAPACITY:

4.7 SEC.

40 MMWC

90 M3/HR.,100-50MBAR

THE PRIMARY WATER SYSTEM PRIMARY WATER PUMP & FILTER UNIT PRIMARY WATER COOLER UNIT PRIMARY WATER TANK PRIMARY WATER MEASURING INSRUMENT RACK ALKALYSER UNIT

THE PRIMARY WATER PUMP & FILTER UNIT COMRISES OF THE FOLLOWING COMPONENTS : PRIMARY W ATER PUMPS PRIMARY W ATER FILTER FINE FILTER MIXED BED ION EXCHANGER FLOW METER PRESSURE GAUGE CONDUCTIVITY TRANSMETTER VALVES

1. PRIMARY WATER TANK 2. PRESSURE REGULATOR 3. WASTE GAS EXIT 4. PUMP 5. COOLER 6. FILTER 7. ION EXCHANGER 8. ALKALISATION UNIT 9. BYPASS LINE 10. C.W. FOR STATOR WINDIN 11. C.W. FOR BUSHINGS 12. WATER TREATMENT 13. TEFLON HOSE 14. C.W. MANIFOLD

PRIMARY WATER SYSTEM

PRIMARY WATER SYSTEM

PW PUMP & FILTER UNIT

ALKALYSER UNIT

ALKALYSER UNIT

PRIMARY WATER TANK

THE WASTE GAS SYSTEM COMPRISES OF THE FOLLOWING COMPONENTS : VAPOUR EXHAUSTERS VACUUM SWITCHES VALVES

WASTE GAS SYSTEM

VAPOUR EXHAUSTER

THE WASTE FLUID SYSTEM COMRISES OF THE FOLLOWING COMPONENTS : DRAIL OIL COLLECTOR LEVEL SWITCH VALVES

WASTE FLUID SYSTEM