Академический Документы
Профессиональный Документы
Культура Документы
Ig Schneider PDF
Ig Schneider PDF
HVX
Vacuum circuit-breaker 12 - 17,5 kV (≤ 2500 A, ≤ 31,5 kA)
Installation
Operation Maintenance
Technical instruction
No. DRC NTV 142
Issue 02/10
www.schneider-electric.com
IMPORTANT NOTE
The Technical Instructions, which are exclusively valid are always supplied by Schneider Electric together with the product in question. Our
products may only be commissioned, operated, serviced, repaired or decommissioned together with Operating Instructions which have been
directly enclosed to the product in question by the factory.
On the other hand, this electronic version of the Technical Instruction is provided to the customer at his/her request for information only. None of
our products may be commissioned, operated, serviced, repaired or decommissioned on the basis of this electronic version.
Non-compliance with this instruction may entail serious damage to the product, the objects pertaining to it, as well as health hazard or mortal
danger. Schneider Electric shall not be held liable for any such damage.
Manufacturer:
Schneider Electric Xiamen
Switchgear CO.,Ltd.
Manufacturer:
No.24, Huo ju Bei Lu
361006 Xiamen
China
+86 (0)592 5775316-0
+86 (0)592 5775139
„WARNING“
This symbol is used for instructions non-compliance with which
may result in serious injury, death or serious material damage.
„IMPORTANT“
This symbol is used for information which is important to avoid
damage.
Disclaimer of liability
The manufacturer shall not be held responsible for damage which occurs if
■■ instructions in this Technical Instruction are not complied with,
■■ the circuit-breaker is not operated according to its intended use (see
above),
■■ the circuit-breaker is assembled, connected or operated improperly,
■■ accessories or spare parts are used which have not been approved by
the manufacturer,
■■ the circuit-breaker is converted without the manufacturer’s approval, or if
inadmissible parts are attached.
Ambient conditions
Ambient temperature min./max. -25 / 40oC 1)
Average value over 24 hours (max.) 35oC 1)
Max. installation altitude above sea level 1000m 1)
1)
higher values on request
WARNING:
There is a risk of injury when working on the drive
mechanism.Before commencing work, release the
energy-storing device by performing the operating
sequence OFF-ON-OFF.
Series HVX
Fig. 2.1
Example of rating plate
1 Type designation
2 Serial number
3 Year of manufacturing
4 Technical data
Motor
■■ for charging the energy-storing device (spiral spring).
Opening release
■■ 2 units max.
Undervoltage release
■■ 1 unit.
Closing release
■■ 1 unit.
Secondary release
(Transformer-operated release)
■■ 1 unit max.
Blocking coil
■■ Blocking coils prevent the circuit breaker from being closed and opened
via the push-buttons ”ON” or ”OFF”, as well as manual actuation of the
withdrawable unit.
If the rated auxiliary voltage has fallen or is shut off, all blocking coils are in
”blocked” position.
Technical data, auxiliary switch
DC [V] AC [V]
Rated auxiliary voltage
[V] ≤ 48 125 220 120 230
Switching capacity [A] 10 3,8 2 10
Time factor T=L/R [ms] 10 20 -
Rated short-time current 250 A / 3 s
Rated continuous current [A] 15 -
Operating times *
Times for solenoids and motor
Minimum command time “OFF” el. tripping [ms] 20
Minimum command time “ON” el. tripping [ms] 20
Motor charging time [s] ≤ 12
* Rated frequency according to specification on rating plate (50/60 Hz)
Auxiliary switches
Auxiliary switches are always actuated directly by the switch shaft via an
intermediate linkage. Their position always corresponds to that of the main
contacts. As standard, the circuit-breaker is equipped with two auxiliary
switches with 8 contact elements each.
The switching functions have been set in the factory according to the wiring diagram.
Anti-pumping relay
If an ON and OFF command is simultaneously and permanently present at
the circuit-breaker, the latter returns to its initial position after closing. It
remains in this initial position until the ON command is issued anew. This
prevents continuous closing and opening (”pumping”).
DRC NTV 142 - HVX Compact - EN 7
HVX 3 Variants
1 Conductor bar
10 2 Circuit-breaker housing
5 3 Rating plate
4 Operator interface
1
6
5 Low voltage socket
6 Drive housing
4
7 Rollers
2
3 8 Withdrawable unit
9 Insertion opening for crank to move the circuit-breaker into its
11
disconnected/service position / manually
10 ”IP” protection sheet (optional)
9
7 11 Shutter rail (optional)
8
Fig. 3.1
Vacuum circuit-breaker HVX 17,5 kV - 31,5 kA - 1250 A
withdrawable unit with low voltage socket
9
7
8
Fig. 3.2
Vacuum circuit-breaker HVX 17,5 kV - 31,5 kA - 2500 A
withdrawable unit with low voltage socket
4.1 Delivery
■■ Handle shipping units carefully when unloading and unpacking them.
■■ Shipping units must be unpacked immediately after receipt. Any damage
occurred in transit must be recorded and reported immediately to the
manufacturer.
■■ On delivery, the consignment must be checked for completeness.
■■ The supplier must be notified in writing about any discrepancies.
Fig. 4.1
Shipping unit
4.2 Storage
The transport packaging is not intended for storage. The risk of storing the
parts in packed condition shall be the consignee’s responsibility!
Fig. 4.2
Transport and lifting 4.3 Transport
Transport using a forklift truck: Only transport the circuit-breaker within its
shipping unit on a pallet.
Transport without pallet:
Lift circuit-breaker acc. to Fig 4.2. A rope (not a metallic steel cable) Ø 12 to
15 mm or a strap is required to this effect.
WARNING:
Make sure the rope or strap is strong enough to bear
the weight of the circuit-breaker and do not touch the
circuit-breaker.
Weights [kg]
Rated Current [A]
Type
Ir ≤ 1250 1250 < Ir ≤ 2500
HVX - withdrawable Unit 100 kg 150 kg
(Guide values without packaging)
The circuit-breaker is supplied in position ”OFF” and with the energy storing
device ”released”.
WARNING:
The energy storing device must not be charged until
assembly is finished. Risk of injuries.
WARNING:
The safety provisions of chapter 1.5 must be observed.
Earth terminal
The circuit-braker is linked to the panel via the wheels of the trolley.
Optionally, the HVX circuit-breaker is available with short-circuit proof
earthing.
IMPORTANT:
Comply with the tightening torques specified for screw-fastening
(refer to Annex).
Fig. 5.4
1 Control connector on terminal strip
IMPORTANT:
The energy storing device of motorized circuit-breakers is charged
automatically once the auxiliary voltage is applied.
IMPORTANT:
Undervoltage releases / blocking coils (optional) enable switching
tests only to be performed with the auxiliary voltage applied.
6.1 HVX
(withdrawable unit)
Perform functional tests:
1. Charge energy-storing device using the crank (Fig. 9.1 rep. 2). Check
the spring position indicator.
2. Switch circuit-breaker on and off several times by hand. Check position
indicator.
3. Move the withdrawable unit to its service and disconnected position via
the crank handle (Fig. 9.1 rep. 3).
□□ Check mechanical interlocks between the HVX and the cell. Check
position indication.
4. Check electrical functions of control and operating devices.
Apply auxiliary voltage.
Actuate the releases to perform switching operations and check functions /
interlocks. Watch position indicators.
5. Racking the circuit-breaker in and out. At the same time, check the
position indicators and the interlocks in the circuit-breaker and with
regard to other devices.
Fig. 7.1
Operator interface of HVX circuit-breaker
Fig. 7.2
Control elements for the circuit-breaker
3 released ON O
4 charged ON O-C-O
7.2 Interlocks
(where applicable)
Mechanical interlocks
The HVX switch features basic interlocks to prevent operating errors.
WARNING:
You must be familiar with these interlocks before operating the circuit-breaker.
Electrical interlocks
have been designed according to the circuit diagram.
Opening (OFF)
IMPORTANT:
The circuit-breaker operating company is responsible for complying
with the specified maintenance intervals and for performing
maintenance according to the actual operating and ambient
conditions.
WARNING:
The safety provisions of Chapter 1.5 must be
observed.
WARNING:
The circuit-breaker must not be disassembled for
maintenance work (see Disclaimer of liability, section
1.3).
Safety provisions
1. On principle, the 5 safety rules applicable for electrical engineering must
be complied with before maintenance work on the circuit-breaker is
started:
■■ Isolate switchgear from power supply
■■ Prevent it from reclosing
■■ Verify it for zero voltage
■■ Earth and short-circuit it
■■ Cover or bar off adjacent live components.
These rules apply for the upper and lower circuit-breaker terminals alike.
2. Switch off the auxiliary voltage for the circuit-breaker drive and secure it
against reclosing.
3. Release the energy-storing device by performing the corresponding
operating sequence on the circuit-breaker. ON - OFF - ON (see Chapter 7)
Servicing schedule
Maintenance
intervals Qualification /
(ambient Maintenance position
conditions work performing the
according to IEC work
60 694)
■■ Check for
contamination /
condensation and
damage
Every 4 years ■■ If necessary, clean
circuit-breaker (see
section 8.3) and
perform several Staff qualified
switching tests accordingly for the
■■ Clean, grease work to be done
circuit-breaker (see
Chapter 8.3 and 8.6)
and perform several
After 20 years
switching tests
■■ Check releases and
blocking coils for
proper working order
Once the summation
current limit has been Replace vacuum Manufacturer’s
reached (refer to interrupters Service Center
Chapter 8.7)
Replacement of
After 10.000 operating
mechanism and / or Manufacturer’s
cycles of the
parts of the circuit- Service Center
circuit-breaker
breaker
After 1000 operating Replacement of the
Manufacturer’s
cycles of the withdrawable part and
Service Center
withdrawable part other relevant parts
WARNING:
Circuit-breakers and drives must not be disassembled
for service and maintenance work (see Disclaimer of
liability, section 1.3).
Remove the withdrawable unit from the switchgear cubicle for inspection
(see instructions for the panel concerned). Remove the cover plate of the
circuit-breaker drive.
Lubricants
IMPORTANT:
Only approved lubricants may be used (section 9.2).
○ Cryogenic grease
□ High-pressure grease
∆ Contact lubricant
● Silicon grease
Lubrication procedure
1. Clean the points of lubrication (Fig. 8.1 to 8.3) using a lint-free cotton cloth;
in case of serious contamination, use a cleaning agent (see section 8.3).
2. Apply a thin coat of lubricant, using e.g. a paintbrush.
Points of lubrication
IMPORTANT:
The following elements must not be lubricated:
■■ Motor
■■ Electric releases
■■ Push switches
■■ Blocking coils
■■ Auxiliary switches
■■ Ball bearings
Fig. 8.1
Circuit-breaker drive mechanism
□ High-pressure grease
○ Cryogenic grease
● Cryogenic grease
Fig. 8.2
Rack-in mechanism
□ High-pressure grease
1 Spindle
Fig. 8.3
Finger contacts
∆ Contact lubricant
Fig. 8.4
Tulip contacts
∆ Contact lubricant
Final steps
Re-mount the cover plate and insert the circuit-breaker in the panel (see
section 5).
Check circuit-breaker according to section 6 ”Commissioning”.
10 00 0
operations n n
5000
Ausschaltzahl 1000
50 0
Number of breaking
10 0
50
10
Ir I SC
Breaking current
Ausschaltstrom log II a
a
For the data regarding the rated normal current Ir and the short-circuit
breaking current Isc, please refer to the rating plate (Fig. 8.4).
Fig. 8.5
Data for rated normal current Ir (1) and short-circuit breaking current Isc (2) on the
rating plate
9.1 Accessories
5
3
1 2
Fig. 9.1
Accessories for HVX circuit-breaker
The accessories depend on the panel type used, and must be enquired about if
necessary.
1 ON/OFF operating rod
2 Spring charging crank for spring operating mechanism
3 Moving crank handle
4 Lifting brackets (x2)
5 Lifting beam (optional)
WARNING:
Danger of injury when wrong handling the auxiliary
products.Comply with the safety data sheets supplied
by the manufacturers of the auxiliary products.
IMPORTANT:
Contact areas coated with lubricant Kontasynth should not be
touched, if possible.
Material of contact
Pre-treatment
surfaces
Silver-plated contact surfaces Clean 1)
Copper or copper alloy Clean 1), expose metallic surface 2)
Aluminium Clean 1), expose metallic surface 2)
Remove passivation, not,
Zinc-plated steel
however, the zinc layer 3)
Clean 1), passivation need not be
Hot-galvanized sheet-metal
removed
1)
Clean by means of lint-free cloth; use cleaning agent in case of serious
contamination (see above)
2)
Expose metallic surface
□□ by treating the entire surface with emery cloth or a rotating grinding tool (grain
size 100 or 80) or
□□ using a wire brush which is clearly marked for use exclusively for aluminium or
exclusively for copper
3)
using a brass brush, steel brush
Schneider Electric As standards, specifications and designs change from time to time, please ask for
35, rue Joseph Monier confirmation of the information given in this publication.
CS 30323
92506 Rueil-Malmaison Cedex, France This document has been printed
on ecological paper
RCS Nanterre 954 503 439 Publishing: Schneider Electric
Capital social 896 313 776 € Design: Schneider Electric
www.schneider-electric.com Printing:
DRC NTV 142 - HVX Compact - EN 03-2011