Вы находитесь на странице: 1из 4

GW15080

GW22-126



CATALOG
OF OUTDOOR HV AC DISCONNECTING SWITCH

CHINT ELECTRIC CO.,LTD.

GW15080

.
1 Abstract
1.1
1.1 General
GW22-126 3-
50
.
Type GW22-126 Single-Pillar Vertical Telescopic the level of open-type outdoor AC high voltage
disconnector is 3-phase AC 50HZ outdoor high voltage apparatus for opening and closing high voltage
line at no load.
CJ6 ,
CS20G .
Main Disconnector Knife can matched with type CJ6 motor actuator institution, also can be
matched with type CS20Gmanual operation institution.
,
, .
.
Disconnector switches tripping insulation single vertical fracture, the switch open and close shows
clearly for routine check. The disconnector with a small footprint and has saving advantages of lead.
GW22-126 GB1985 "
" IEC129 "AC
swithches" .
Type GW22-126 disconnector is used in accordance with GB1985AC High Voltage disconnector
and ground switch and IEC129AC disconnectors and ground swithches standards and relevant
requirement.
.
2.1.
2.2.
2.3.
2.4.
2.5.
2.6.
/ .

2. Working environment and operation conditions


: <1000 , 2500m ( )
Altitude above sea level:
1000, 2500( special type )
: -40 ~ + 40
Ambient temperature:
-40+ 40
: <35m / S.
Wind velocity: 35S.
: <8 .
Earthquake intensity:
8 degree.
:
10mm.
Ice-thickness:
10mm.
: 2,5 / .., 3.1cm

Pillars insulator leakage ration: Pollution Resistance type 2.5cm/KV3.1cm/KV.


2.7. , ,

Inappropriate to use in flammable substances, explosion, chemical corrosion and severe vibration
place
2.8.
Inappropriate in non-level installation

GW15080

.
3. Technical parameters
3.1
3.1

1-2
The main technical parameters of disconnector are shown in tables1-2
1:

126

1600

2000

()

100

100

4
()

40

40

1000

1000

750

1000

750

1000

1,1
,
2000

Table 1: the main technical parameters


Items

Main specification and technical parameters

Rated voltage KV

126

Rated current A

1600

2000

100

100

40

40

Rated peak withstand current


(peak)

kA

4S rated short time withstand


current (rms)

kA

Horizontal vertical: 1000


Rated static mechanical load of
terminals

Radio interference level

Horizontal Vertical: 1000

Horizontal Level: 750

Horizontal Level:750

Vertical:1000

Vertical:1000

At 1.1 times the maximum operating phase voltage,


sunny day not more than 2000

4.
4. Ordering instruction
GW22-126 Single-Pillar
, , .
When ordering type GW22-126 Single-Pillar Vertical Telescopic High Voltage Disconnector, please

GW15080

specify the followings clearly.


4.1 ,
4.1 Type, specification and quantity of disconnector
4.1.1 .
4.1.1 rated current.
4.1.2 .
4.1.2 Quantity of equipped earthing switch.
4.1.3 , , ,
. ( ,
( 2500)
4.1.3 If special requirement is requested, please make it clear so as to avoid incorrect supply.(the
insulator is a common type, fog type or special type ( can be used for altitude 2500m) or other
requirements
4.1.4 :
4.1.4 Operating mechanism: unipole or three pole operation linkage operation