Академический Документы
Профессиональный Документы
Культура Документы
Astl15a 25a 40a Bae2sp Spat.010.5023.en
Astl15a 25a 40a Bae2sp Spat.010.5023.en
BAE 2 SP (OPTION)
(Control and display unit)
Document
INSTRUCTION MANUAL
identification number >>> SPAT.010.5023.EN
Sparktester AST L 15A/25A/40A 12 ZUMBACH owned companies in Switzerland (H.Q.), Benelux, China, Czech Republic, France, Germany,
SPAT.010.5023.EN_20210827 India, Italy, Spain, Taiwan, United Kingdom and USA, plus agents and service in more than 40 countries.
About this manual
Chapter
4 Installation
5 Operating instructions
6 Maintenance
7 Repairing
Return for repairs, spare parts
8 Decommissioning / disposal
9 Service port
10 RS Interface
11 Ethernet
12 Profinet
14 Web visualisation
15 Index
2/114 12 ZUMBACH owned companies in Switzerland (H.Q.), Benelux, China, Czech Republic, France, Germany, Spark Tester AST L 15A/25A/40A
India, Italy, Spain, Taiwan, United Kingdom and USA, plus agents and service in more than 40 countries. 20210827_SPAT.010.5023.EN
Contents
1 INTRODUCTION 7
1.1 DEAR CUSTOMER����������������������������������������������������������������������������������������� 7
1.1.1 Risks and transportation����������������������������������������������������������������� 7
1.1.2 Inspection of goods upon arrival���������������������������������������������������� 7
1.1.3 Warranty�������������������������������������������������������������������������������������������� 7
1.2 ADDRESSES – THE ZUMBACH GROUP����������������������������������������������������� 8
1.3 SYMBOLS������������������������������������������������������������������������������������������������������ 9
1.4 ZUMBACH PRODUCT OVERVIEW������������������������������������������������������������� 10
1.5 EU DECLARATION OF CONFORMITY (Copy)������������������������������������������� 12
2 SAFETY 13
2.1 SAFETY�������������������������������������������������������������������������������������������������������� 13
2.1.1 Safety measures in the unit����������������������������������������������������������� 13
2.2 USE ACCORDING TO DESTINATION��������������������������������������������������������� 14
2.3 PROHIBITED USE���������������������������������������������������������������������������������������� 14
2.4 RESIDUAL RISK������������������������������������������������������������������������������������������ 15
2.4.1 High voltage������������������������������������������������������������������������������������ 15
2.4.2 Fire hazard due to deposits and water in the electrode unit ����� 16
2.4.3 Ozone���������������������������������������������������������������������������������������������� 16
2.4.4 EMC������������������������������������������������������������������������������������������������� 17
3 TECHNICAL DESCRIPTION 18
3.1 SYSTEM OVERVIEW����������������������������������������������������������������������������������� 18
3.2 SPARK TEST PRINCIPLE���������������������������������������������������������������������������� 18
3.2.1 Production line to manufacture cables and wires���������������������� 18
3.3 COMPONENTS OF THE AST L 15A / 25A / 40A SPARK TESTER�������������� 19
3.3.1 Control and display unit BAE 2 SP����������������������������������������������� 20
3.3.1.1 Dimensional drawing BAE 2 SP���������������������������������������������� 21
3.3.2 Electrode unit��������������������������������������������������������������������������������� 22
3.3.2.1 Dimensional drawing AST.xxA.50 and AST.xxA.90��������������� 24
3.3.2.2 Dimensional drawing AST.xxA.250����������������������������������������� 25
3.4 TECHNICAL DATA��������������������������������������������������������������������������������������� 26
3.5 REQUIREMENTS FOR UL CERTIFICATION OF WIRE AND CABLE
PRODUCTS ������������������������������������������������������������������������������������������������� 27
3.6 SPARK TEST STANDARDS APPLYING TO AST L 15A / 25A / 40A
SPARK TESTERS���������������������������������������������������������������������������������������� 27
3.7 ELECTRODE LENGTH AND TEST FREQUENCY�������������������������������������� 27
3.8 FAULT DETECTION������������������������������������������������������������������������������������� 28
3.9 EXTRUDING AND REWIND MODE������������������������������������������������������������� 30
3.10 ACTIVATION OF CONTROL POSITIONS��������������������������������������������������� 30
Spark Tester AST L 15A/25A/40A 12 ZUMBACH owned companies in Switzerland (H.Q.), Benelux, China, Czech Republic, France, Germany, 3/111
SPAT.010.5023.EN_20210827 India, Italy, Spain, Taiwan, United Kingdom and USA, plus agents and service in more than 40 countries.
4 INSTALLATION 32
4.1 INSTRUCTION FOR LIFTING AND CARRYING����������������������������������������� 32
4.2 LOCATION OF THE SPARK TESTER��������������������������������������������������������� 32
4.3 MOUNTING INSTRUCTIONS����������������������������������������������������������������������� 33
4.4 CONNECTIONS TO THE SPARK TESTER������������������������������������������������� 34
4.4.1 Connections to the electrode unit������������������������������������������������ 34
4.4.2 Connection to mains���������������������������������������������������������������������� 35
4.4.3 Mounting the control and display unit BAE 2 SP������������������������ 35
4.5 CORRECT EARTHING OF THE SPARK TESTER�������������������������������������� 36
4.6 SETTINGS AND USER INTERFACES��������������������������������������������������������� 38
4.6.1 Operating mode of the control and display unit BAE 2 SP�������� 39
4.6.2 Configuration menu of the control and display unit BAE 2 SP�� 40
4.6.3 Emergency stop connector����������������������������������������������������������� 42
4.6.4 Encoder������������������������������������������������������������������������������������������� 44
4.6.5 Setting up the Service Ethernet interface������������������������������������ 46
4.6.6 Potential free analog / digital input / output����������������������������������� 47
4.6.7 Setting up the user configuration for RS host interface������������� 50
4.6.8 Setting up the Ethernet interface�������������������������������������������������� 51
4.6.9 Setting up the user configuration for Profibus DP interface������ 52
4.6.10 Setting up the Profinet interface��������������������������������������������������� 54
4.7 PROTECTION AGAINST OZONE ��������������������������������������������������������������� 55
5 OPERATING INSTRUCTIONS 56
5.1 EARTHING OF THE PRODUCT TO BE TESTED��������������������������������������� 56
5.2 CLEANING OF THE ELECTRODE�������������������������������������������������������������� 56
5.3 TEST VOLTAGE������������������������������������������������������������������������������������������� 57
5.4 IF YOU RUN INTO PROBLEMS IN YOUR APPLICATION�������������������������� 57
5.5 USING THE SPARK TESTER WITH CONTROL AND DISPLAY
UNIT BAE 2 SP��������������������������������������������������������������������������������������������� 58
5.5.1 Front panel of the control and display unit BAE 2 SP���������������� 58
5.5.2 Control spark testers with control and display
unit BAE 2 SP���������������������������������������������������������������������������������� 61
5.5.3 Using the control and display unit BAE 2 SP as local
display��������������������������������������������������������������������������������������������� 63
5.6 OPERATING SPARK TESTERS WITH POTENTIAL FREE I / O����������������� 63
5.7 OPERATING SPARK TESTERS WITH RS OR ETHERNET
HOST INTERFACE��������������������������������������������������������������������������������������� 64
5.8 OPERATING SPARK TESTERS WITH PROFIBUS DP OR
PROFINET HOST INTERFACE ������������������������������������������������������������������� 65
4/114 12 ZUMBACH owned companies in Switzerland (H.Q.), Benelux, China, Czech Republic, France, Germany, Spark Tester AST L 15A/25A/40A
India, Italy, Spain, Taiwan, United Kingdom and USA, plus agents and service in more than 40 countries. 20210827_SPAT.010.5023.EN
6 MAINTENANCE 66
6.1 REGULAR MAINTENANCE������������������������������������������������������������������������� 66
6.2 SAFETY CHECK OF THE SPARK TESTER������������������������������������������������ 67
6.3 CALIBRATION OF SPARK TESTERS��������������������������������������������������������� 67
6.4 SPARK TESTER CALIBRATOR������������������������������������������������������������������ 68
6.5 CALIBRATION FORM FOR SPARK TESTER��������������������������������������������� 69
6.6 CALIBRATION WITH CONTROL AND DISPLAY UNIT BAE 2 SP������������� 70
6.6.1 Calibration of the test voltage������������������������������������������������������� 70
6.6.2 Calibration of the analog input nominal��������������������������������������� 71
6.6.3 Calibration of the analog output actual���������������������������������������� 72
6.7 CALIBRATION VIA INTERFACE����������������������������������������������������������������� 74
6.7.1 Calibration of the test voltage������������������������������������������������������� 74
6.7.2 Calibration of the analog input nominal��������������������������������������� 75
6.7.3 Calibration of the analog output actual���������������������������������������� 75
7 REPAIRING 76
7.1 RETURN FOR REPAIRS������������������������������������������������������������������������������ 76
7.2 CONDITIONS APPLYING TO SPARE PARTS��������������������������������������������� 76
7.3 TROUBLE-SHOOTING�������������������������������������������������������������������������������� 77
7.4 LIST OF SPARE PARTS OF THE ELECTRODE UNIT
AST L 15A / 25A / 40A������������������������������������������������������������������������������������ 78
7.4.1 Common spare parts for all AST L 15A / 25A / 40A
electrode units�������������������������������������������������������������������������������� 78
7.4.2 Spare electrodes and component parts of electrodes��������������� 79
8 DECOMMISSIONING / DISPOSAL 82
8.1 DECOMMISSIONING����������������������������������������������������������������������������������� 82
8.2 GENERAL DISPOSAL��������������������������������������������������������������������������������� 82
9 SERVICE PORT 83
9.1 SETTING UP THE LAPTOP������������������������������������������������������������������������� 83
9.2 SETTING UP THE TERMINAL PROGRAM������������������������������������������������� 84
9.3 USING THE SERVICE PORT����������������������������������������������������������������������� 85
10 RS INTERFACE 86
10.1 SERIAL LINK������������������������������������������������������������������������������������������������ 86
10.2 COMMUNICATION SYNTAX������������������������������������������������������������������������ 88
10.3 GENERAL DEFINITIONS����������������������������������������������������������������������������� 88
10.3.1 Data and parameter access����������������������������������������������������������� 89
Spark Tester AST L 15A/25A/40A 12 ZUMBACH owned companies in Switzerland (H.Q.), Benelux, China, Czech Republic, France, Germany, 5/111
SPAT.010.5023.EN_20210827 India, Italy, Spain, Taiwan, United Kingdom and USA, plus agents and service in more than 40 countries.
10.4 ZUMBACH ASCII PROTOCOL�������������������������������������������������������������������� 90
10.4.1 Upload��������������������������������������������������������������������������������������������� 90
10.5 ANSI X3.28-2.5-A4 STANDARD PROTOCOL��������������������������������������������� 91
10.5.1 Upload��������������������������������������������������������������������������������������������� 91
10.5.2 Download���������������������������������������������������������������������������������������� 92
11 ETHERNET 94
12 PROFINET 95
15 INDEX 109
6/114 12 ZUMBACH owned companies in Switzerland (H.Q.), Benelux, China, Czech Republic, France, Germany, Spark Tester AST L 15A/25A/40A
India, Italy, Spain, Taiwan, United Kingdom and USA, plus agents and service in more than 40 countries. 20210827_SPAT.010.5023.EN
1 INTRODUCTION
▶ The commercial terms and conditions of the document "General terms and
conditions of sale" (ZUMB.540.0003.E) are binding.
1.1.3 Warranty
As far as practically possible and in our opinion deemed necessary, each part of the
equipment is tested for its proper working condition prior to shipment.
The general warranty regulations can found in our "General sales and delivery terms"
(ZUMB.540.0003.E).
Certified Quality
In addition to conforming to ISO 9001:2015, Zumbach's quality standards
guarantee a highly precise, robust and reliable product. The goal of the
ZUMBACH group is to offer industry the most complete line of measuring
and monitoring instruments of the highest quality and technology. Worldwide
support by competent advisors and reliable service is provided by 11
ZUMBACH owned enterprises and by over 40 agencies, we are committed
to Total Customer Satisfaction. ISO 9001:2015
Spark Tester AST L 15A/25A/40A 12 ZUMBACH owned companies in Switzerland (H.Q.), Benelux, China, Czech Republic, France, Germany, 7/111
SPAT.010.5023.EN_20210827 India, Italy, Spain, Taiwan, United Kingdom and USA, plus agents and service in more than 40 countries.
The ZUMBACH Group
1.2 ADDRESSES – THE ZUMBACH GROUP
Switzerland Zumbach Electronic AG France ZUMBACH Bureau France
(H.Q.) P.O. Box (vente) 6 rue de l'Avenir
CH-2552 Orpund FR-77760 La Chapelle La Reine
Phone +41 (0)32 356 04 00 Tél. +33 (0)1 64 24 46 31
Fax: +41 (0)32 356 04 30 Fax +33 (0)1 64 24 46 26
E-mail: sales@zumbach.ch E-mail: ventes@zumbach.com.fr
Benelux Zumbach Electronic AG Service ZUMELEC Sarl
P.O. Box après-vente: 6 rue de l'Avenir
CH-2552 Orpund FR-77760 La Chapelle La Reine
Tel. +32 (0)52 31 18 81 Tél. +33 (0)1 64 24 42 69
Fax +41 (0)32 356 04 30 Fax +33 (0)1 64 24 46 26
E-mail: sales@zumbach.be E-mail: service@zumbach.com.fr
China Zumbach Electronic (Shanghai) Co., Ltd. India Zumbach Electronic India Pvt. Ltd.
2F, Building 18 S No: 106/2/1, 2nd lane, "Daffodils" Society
No. 481 Guiping Road Row House No: 7, Near Karnataka Bank,
200233 Shanghai, P.R. China Behind D mart, Baner Mahalunge Road,
Tel. +86 (0)21 542 60 443 Baner, Pune - 411045
Fax +86 (0)21 542 61 151 Maharashtra
E-mail: sales@zumbach.com.cn Mobile +91 9890 100 813
E-mail: sales@zumbachindia.com
Czech Zumbach Czech Office
Republic Hutska 126 Italia Zumbach Electronic Srl
CZ-27201 Kladno Via Adua, 19
Tel. +420 608 474 664 IT-21045 Gazzada Schianno (VA)
Fax: +41 (0)32 356 04 30 Tel. +39 0332 870 102
E-mail: jvorlicek@zumbach.cz Fax +39 0332 464 605
E-mail: zumit@zumbach.it
Deutschland Zumbach Electronic GmbH
Kesselsgasse 2 Taiwan Zumbach Electronics Far East
DE-50259 Pulheim 4F., No. 262, Sec. 6
Tel. +49 (0)2238 8099-0 Ming-Chuan E. Road
Fax +49 (0)2238 8099-49 Taipei
E-mail: verkauf@zumbach.de Taiwan R.O.C.
Tel. +886 2 2630 5530
Büro in Gera: Fax +886 2 2630 5529
Robert-Leube-Weg 3 E-mail: info@zumbach.tw
DE-07548 Gera
Tel. +49 (0)365 8320265 UK Zumbach Electronics Ltd.
Fax +49 (0)365 8320268 Registered Office Address:
Mobil +49 (0)172 9318525 22 Cromwell Business Centre
E-mail: fwohlfeld@zumbach.de Howard Way, Newport Pagnell
Milton Keynes, MK16 9QS.
España Zumbach Electrónica S.L. Phone: +44 (0)870 774 3301
Avinguda de Cornellà, 144, 3o, 3a Fax: +44 (0)870 774 3302
ES-08950 Esplugues de Llobregat E-mail: sales@zumbach.co.uk
(Barcelona) Company Registered in England
Tel. +34 93 666 93 61 Company Registration Number: 1233358
E-mail: gestion@zumbach.es
USA Zumbach Electronics Corp.
140 Kisco Avenue
Mount Kisco, NY 10549-1407
Phone: +1 914 241 7080
Fax: +1 914 241 7096
E-mail: sales@zumbach.com
www.zumbach.com
20190429 blog.zumbach.com
8/114 12 ZUMBACH owned companies in Switzerland (H.Q.), Benelux, China, Czech Republic, France, Germany, Spark Tester AST L 15A/25A/40A
India, Italy, Spain, Taiwan, United Kingdom and USA, plus agents and service in more than 40 countries. 20210827_SPAT.010.5023.EN
1.3 SYMBOLS
Spark Tester AST L 15A/25A/40A 12 ZUMBACH owned companies in Switzerland (H.Q.), Benelux, China, Czech Republic, France, Germany, 9/111
SPAT.010.5023.EN_20210827 India, Italy, Spain, Taiwan, United Kingdom and USA, plus agents and service in more than 40 countries.
1.4
1.1 ZUMBACH PRODUCT OVERVIEW
ZUMBACH Measuring and Control Systems for On-line and Off-line Use in the Wire
and Cable Industry, Plastics and Rubber Industry, Steel and Metal Industry, for Medical
and Laboratory Applications and more.
AST L
AST H 15A Spark Testers
DST 28A
Spark Tester AST L 15A/25A/40A 12 ZUMBACH owned companies in Switzerland (H.Q.), Benelux, China, Czech Republic, France, Germany, 11/111
SPAT.010.5023.EN_20210827 India, Italy, Spain, Taiwan, United Kingdom and USA, plus agents and service in more than 40 countries.
1.5 EU DECLARATION OF CONFORMITY (Copy)
The following EU declaration of conformity is a content report of the original document
only, which is keep and available at the Zumbach Electronic AG. The document has
no serial number or signing.
EU DECLARATION OF CONFORMITY
The manufacturer:
Zumbach Electronic AG
Hauptstrasse 93
CH-2552 Orpund
and furthermore declares that the following harmonised standards and other standards (or parts/
clauses thereof) have been applied:
IEC 61326-1 Electrical equipment for measurement, control and laboratory use –
EMC requirements – Part 1: General requirements
12/114 12 ZUMBACH owned companies in Switzerland (H.Q.), Benelux, China, Czech Republic, France, Germany, Spark Tester AST L 15A/25A/40A
India, Italy, Spain, Taiwan, United Kingdom and USA, plus agents and service in more than 40 countries. 20210827_SPAT.010.5023.EN
2 SAFETY
2.1 SAFETY
The spark tester AST L 15A / 25A / 40A fulfils the requirements of European directives
for low voltage and EMC.
• Installing,
• Operating,
• Maintaining,
• Servicing and
• Placing out of operation.
WARNING
High voltage. Danger to life. Observe the safety instructions given in the instruction
manual and the general precautions for working with hazardous live voltages.
Do not modify or disable components which serve to fulfil a safety function. All
safety components must be intact.
Spark Tester AST L 15A/25A/40A 12 ZUMBACH owned companies in Switzerland (H.Q.), Benelux, China, Czech Republic, France, Germany, 13/111
SPAT.010.5023.EN_20210827 India, Italy, Spain, Taiwan, United Kingdom and USA, plus agents and service in more than 40 countries.
2.2 USE ACCORDING TO DESTINATION
The spark tester AST L 15A / 25A / 40A is exclusively intended for the applications listed
below. Zumbach Electronic AG disclaims liability for all other applications.
• The spark tester AST L 15A / 25A / 40A is intended for testing cable sheaths and
conductor insulation during extrusion, sheathing or rewinding.
The layer to be tested must be electrically insulating (nonconducting) and the
leakage currents must be sufficiently low.
Zumbach spark testers detect the small pinholes as well as bare patches in
cable sheaths and conductor insulation.
• The spark tester AST L 15A / 25A / 40A allows spark-testing with test voltages up
to 15 kV, 25 kV or 40 kV and there are electrode units available for diameters up to
50 mm, 90 mm or 250 mm.
• The spark tester electrode units are designed exclusively for operation with the
Zumbach control and display unit BAE 2 SP and user interfaces as described into
this instruction manual.
• The spark testers are only provided for operation in fixed installed facilities.
The installation must be carried out and tested by qualified personnel.
The instruction manual must be respected.
• The spark testers must exclusively be operated by healthy persons.
WARNING
Operating the electrode unit with disabled safety means and testing conductors
which are not earthed are strictly forbidden.
14/114 12 ZUMBACH owned companies in Switzerland (H.Q.), Benelux, China, Czech Republic, France, Germany, Spark Tester AST L 15A/25A/40A
India, Italy, Spain, Taiwan, United Kingdom and USA, plus agents and service in more than 40 countries. 20210827_SPAT.010.5023.EN
2.4 RESIDUAL RISK
Please refer to chapter 4.5 for more information on the correct protective earthing of
spark testers.
Always earth the conductor or shielding of the cable to be tested on both sides.
WARNING
Do not insert body parts or other objects into the openings for product inlet and
outlet (except products to be tested and earthing rods).
Do not touch the cable to be tested when the spark tester is switched on.
Touching the spark tester or the control unit BAE 2 SP can be hazardous to the user
if there is high voltage between the user and earth. The control and display unit
BAE 2 SP works with non-hazardous voltages close to earth. The insulation between
BAE 2 SP and the user is not intended to be used with high voltages.
When it is necessary to touch the cable for operational reasons, the following additional
security measures must be applied in order to protect the operators:
– The floor or floor covering in the area of the operating personnel must be made of
insulating material
– All tangible objects within the area of the workplace must be insulated, e.g.
control devices of rewinding or extrusion equipment
he corresponding isolations must be sufficiently sized for the nominal test voltage
T
of the spark tester.
Explanation:
• As a difference of potential between the conductors (floating potential) and
the earth always exists whenever the conductors are not earthed, an electric
discharge may occur if a person touches the conductor or the cable. The current
flowing through the human body can result in involuntary muscular contractions
or immobilization and therefore cause subsequent injuries. The physiological
effects depend on the health of the person, body part and surface area of
contact, duration of the electric shock etc. but usually no organic damage is to be
expected. (IEC TS 60479-1,-2).
Spark Tester AST L 15A/25A/40A 12 ZUMBACH owned companies in Switzerland (H.Q.), Benelux, China, Czech Republic, France, Germany, 15/111
SPAT.010.5023.EN_20210827 India, Italy, Spain, Taiwan, United Kingdom and USA, plus agents and service in more than 40 countries.
• It is not sufficient to earth the conductor only on one side because there is risk of
electrical shock if:
– only the roll away coil side is earthed and the cable head leaves the roll away
coil
– the conductor is not continuous, e.g. broken.
2.4.2 Fire hazard due to deposits and water in the electrode unit
Deposits of dirt, talc, abrasion of products, etc. in the electrode unit and on the insulators
can cause creeping currents and thus induce a fire. Particularly critical are conductive
deposits and moisture.
Due to the spark-test method with high voltage, it is mandatory that the products
must be dry when entering into the electrode. A water film on the cable may results
in short-circuiting the test voltage and therefore impairing the proper operation of the
spark tester.
If the voltage of the spark tester is much lower than the preset test voltage, the unit
must immediately be switched off and the area of the electrodes must be inspected
for contamination and damaged isolators. If the voltage is still below the preset value,
do not operate the spark tester anymore and return the spark tester for repair.
In case of fire, switch off immediately the spark tester and remove the mains plug.
Before extinguishing the fire, make sure that the spark tester is separated from the
mains.
2.4.3 Ozone
For reliable detection of small insulation faults, the air surrounding the cable must be
ionized. This unavoidably produces ozone. The quantity of ozone produced depends,
among other things, on the following factors:
16/114 12 ZUMBACH owned companies in Switzerland (H.Q.), Benelux, China, Czech Republic, France, Germany, Spark Tester AST L 15A/25A/40A
India, Italy, Spain, Taiwan, United Kingdom and USA, plus agents and service in more than 40 countries. 20210827_SPAT.010.5023.EN
The ozone concentration in the close workshop environment should not be allowed to
exceed 0.1 ppm (parts of ozone per one million parts of air by volume; IEC 62230), or
the value given in national industrial hygienic standard, whichever is lower.
The ozone concentration can be tested by taking a smell at the air: Ozone smells
sweet and in higher concentration like chlorine. The olfactory threshold for ozone is
0.01 ppm (0.02 mg / m3), i.e. 10 times lower than the tolerance.
When operating spark testers, precautions to ensure that the maximum permis-
sible values for ozone are not exceeded must be taken if the ozone concentration
is too high.
In case of ozone like odour, the following measures must be applied to minimize
exposure of personnel:
When persons are exposed to high ozone concentrations the symptoms can vary
from dryness in the mouth and throat, coughing, headache and chest restriction.
2.4.4 EMC
When a spark tester is operating, electromagnetic emission is generated due to the
test method (air ionized in the electrode, corona discharges and a long cable being
fed through).
By correctly earthing the spark testers and the product to be tested, it is possible
to reduce the interference to values not causing problems. The spark tester itself is
immune against such interference.
Please refer to chapter 4.5 "Correct Earthing of the spark tester" for further
information regarding correct EMC installation.
The spark tester complies the following standards or parts / clauses there of:
Spark testers are class A equipment and intended for use in an industrial en-
vironment. In other environments (domestic), there is may be a potential of
electromagnetic interference, e.g. radio or TV reception disturbed if too close
to the spark tester.
Spark Tester AST L 15A/25A/40A 12 ZUMBACH owned companies in Switzerland (H.Q.), Benelux, China, Czech Republic, France, Germany, 17/111
SPAT.010.5023.EN_20210827 India, Italy, Spain, Taiwan, United Kingdom and USA, plus agents and service in more than 40 countries.
3 TECHNICAL DESCRIPTION
Sheathing
Rewinding
Spark tester
Pay-off reel Cable to Take up reel
be tested
Earthing of the
spark tester
Earthing of the conductor, Earthing of the conductor,
sheath or armour sheath or armour
The conductor, metallic sheathing or armoured shield must be earthed on both sides.
Also the spark tester itself must be earthed.
18/114 12 ZUMBACH owned companies in Switzerland (H.Q.), Benelux, China, Czech Republic, France, Germany, Spark Tester AST L 15A/25A/40A
India, Italy, Spain, Taiwan, United Kingdom and USA, plus agents and service in more than 40 countries. 20210827_SPAT.010.5023.EN
3.3 COMPONENTS OF THE AST L 15A / 25A / 40A SPARK TESTER
Spark Tester AST L 15A/25A/40A 12 ZUMBACH owned companies in Switzerland (H.Q.), Benelux, China, Czech Republic, France, Germany, 19/111
SPAT.010.5023.EN_20210827 India, Italy, Spain, Taiwan, United Kingdom and USA, plus agents and service in more than 40 countries.
3.3.1 Control and display unit BAE 2 SP
The electrode units AST L 15A / 25A / 40A can be controlled via BAE 2 SP or service
port or one of several remote interfaces.
The BAE 2 SP has two operating modes, whereas one can be selected with an internal
changeover switch:
In control mode (C), the spark tester is controlled via BAE 2 SP, e.g.:
– Set the desired test voltage
– Switch on and off the test voltage
– Displays the actual test voltage, number of faults etc.
– Reset the fault counter
– Calibrate the spark tester
– Settings and configuration of the spark tester
If the BAE 2 SP is in control mode, the service port and the remote interface is
deactivated.
In display mode (D), the spark tester is controlled via service port or the remote
interface. The control via BAE 2 SP is deactivated (No test voltage on / off commands,
no reset the fault counter etc.). The BAE 2 SP serves for monitoring values only:
– Displays the test voltage, actual value and set point value
– Displays the number of faults, pin holes and bare patch
– Displays the actual length and the fault positions
In display mode, all controls and settings are to be done via service port or via the
host port built-in in the electrode unit.
20/114 12 ZUMBACH owned companies in Switzerland (H.Q.), Benelux, China, Czech Republic, France, Germany, Spark Tester AST L 15A/25A/40A
India, Italy, Spain, Taiwan, United Kingdom and USA, plus agents and service in more than 40 countries. 20210827_SPAT.010.5023.EN
305 12.01
Option 1 65.2 2.57
241 9.49
36.2 1.43
Pivotable
SPAT.010.5023.EN_20210827
Spark Tester AST L 15A/25A/40A
Schwenkbar
Pivotant
122.2 4.81
171.5 6.75
3.3.1.1 Dimensional drawing BAE 2 SP
Pivotable
Optional mountig angle
Schwenkbar
Montagewinkel optional
Pivotant
Angle on option
Option 2
25
M5 Screw 2x
M5 Schrauben 2x
0.9
8
M5 Visser 2x
25 0.98
M5 Screw 2x
M5 Schrauben 2x
M5 Visser 2x
India, Italy, Spain, Taiwan, United Kingdom and USA, plus agents and service in more than 40 countries.
12 ZUMBACH owned companies in Switzerland (H.Q.), Benelux, China, Czech Republic, France, Germany,
Projection
(1 : 2)
• Subject to modifications
21/111
• Dimensions in mm (inch)
3.3.2 Electrode unit
The AST L 15A / 25A / 40A electrode unit consists of the following:
• The high voltage test electrode in a earthed and closed housing to provide
protection against electrical shock
• Charge removal devices at inlet and outlet for removing static charges.
• Safety switch to switch off the test voltage when the electrode is open
• Signalization lamps:
– Yellow indicator lamp, lights up when the test voltage is switched on
– Red indicator lamp "Alarm", lights up during the set alarm prolongation after
each fault. If another fault is detected within this time, the time duration will be
prolonged again by the alarm prolongation..
• High voltage generator and associated control electronics
Signalization lamps
Machine feet
22/114 12 ZUMBACH owned companies in Switzerland (H.Q.), Benelux, China, Czech Republic, France, Germany, Spark Tester AST L 15A/25A/40A
India, Italy, Spain, Taiwan, United Kingdom and USA, plus agents and service in more than 40 countries. 20210827_SPAT.010.5023.EN
The electrode unit is equipped with one out of the following remote interfaces:
Interface x: Suffix in y: Suffix in
the model the order
number number
RS interface; for USYS 200,
RS 2
USYS IPC 1e / 2e or Host
Profibus DP DP 3
Ethernet EN 4
Profinet PN 5
Ethernet IP EI 7
Spark Tester AST L 15A/25A/40A 12 ZUMBACH owned companies in Switzerland (H.Q.), Benelux, China, Czech Republic, France, Germany, 23/111
SPAT.010.5023.EN_20210827 India, Italy, Spain, Taiwan, United Kingdom and USA, plus agents and service in more than 40 countries.
3.3.2.1 Dimensional drawing AST.xxA.50 and AST.xxA.90
B - 20 400
A max.
3.15
11 0.43
65 2.56 15.16
24/114 12 ZUMBACH owned companies in Switzerland (H.Q.), Benelux, China, Czech Republic, France, Germany, Spark Tester AST L 15A/25A/40A
India, Italy, Spain, Taiwan, United Kingdom and USA, plus agents and service in more than 40 countries. 20210827_SPAT.010.5023.EN
3.3.2.2 Dimensional drawing AST.xxA.250
• Dimensions in mm (inch)
• Subject to modifications
Projection
650
30.51
1006
645
13.5 0.53
100
16.02
Spark Tester AST L 15A/25A/40A 12 ZUMBACH owned companies in Switzerland (H.Q.), Benelux, China, Czech Republic, France, Germany, 25/111
SPAT.010.5023.EN_20210827 India, Italy, Spain, Taiwan, United Kingdom and USA, plus agents and service in more than 40 countries.
3.4 TECHNICAL DATA
Mains
100 – 127 Vac, 200 – 240 Vac
Mains voltage
Automatic switch over between both ranges
Mains voltage operation* 90 – 146 Vac, 180 – 276 Vac typical
Mains frequency 47 – 63 Hz
Power consumption 20 – 150 W typical, load-dependent
Current consumption 2.1 A max.
2 fuses inside the appliance inlet,
Fuse
250 VAC / 5 x 20 mm 3.15 A slow blow
Output
Sinusoidal alternating voltage
AST.15A: 0.5 kV - 15 kVacrms
High voltage
AST.25A: 0.5 kV - 25 kVacrms
AST.40A: 0.5 kV - 1540kVacrms
Accuracy < +/- 4 %
Test frequency 50 - 120 Hz adjustable
Short circuit output current < 10 mArms
Electrode units
Zumbach AST L 15A / 25A / 40A electrode
units, refer to chapter 3.3.2
AST.xxA.50 / 90: approx. 110 kg (242.5 lbs)
Weight
AST.xxA.250: approx. 300 kg (661.4 lbs)
Control and display unit
For all electrode units BAE 2 SP, see chapter 3.3.1
Environmental conditions
Temperature + 5 ... + 50 °C
(+ 41 ... 122 °F)
No wetness, no direct exposure to sunlight.
Operating temperature, pollution
Only low non-conductive pollution, casually
temporary condensation (pollution degree 2)..
Designed for indoor use only.
Temperature when shipping / storing -20 ... 50 °C (4 ... 122 °F)
Humidity max. 95 % (not condensing)
* The test voltage is switched off as long as the mains voltage is outside the operating
range. The test voltage remains off after interruption and re-establishment of the mains
voltage.
26/114 12 ZUMBACH owned companies in Switzerland (H.Q.), Benelux, China, Czech Republic, France, Germany, Spark Tester AST L 15A/25A/40A
India, Italy, Spain, Taiwan, United Kingdom and USA, plus agents and service in more than 40 countries. 20210827_SPAT.010.5023.EN
3.5 REQUIREMENTS FOR UL CERTIFICATION OF WIRE AND CABLE
PRODUCTS
For UL certification of wire and cable products, refer to the website of UL.
The table below shows accordingly the maximum wire line speed in m / min for the
given standards.
Spark Tester AST L 15A/25A/40A 12 ZUMBACH owned companies in Switzerland (H.Q.), Benelux, China, Czech Republic, France, Germany, 27/111
SPAT.010.5023.EN_20210827 India, Italy, Spain, Taiwan, United Kingdom and USA, plus agents and service in more than 40 countries.
Some standards require a number of cycles and the test frequency is not limited to
the usual mains frequencies of 40 Hz to 62 Hz. Therefore, higher wire line speeds
can be applied for the same length of the electrode if the test frequency is increased.
Both standards require that the product should be in contact with the electrode during
9 cycles and there are no limitations for the test frequency.
The table below shows accordingly the maximum wire line speed in m / min for the
standards UL1581 and UL2556 at different test frequencies.
With AST L 15A / 25A / 40A spark testers, the test frequency can be adjusted from 50 Hz
to 120 Hz, the factory setting is 50 Hz.
The test frequency should be set as low as possible to reduce the capacitive loading
and the amount of ozone.
• If the wire line speed is lower than the values shown in the table above for
50 / 60 Hz, the spark test should be done at 50 Hz or 60 Hz.
• If the wire line speed is higher than the values shown in the table above for
50 / 60 Hz, the test frequency can be increased up to 120 Hz maximum for small
product diameters,
– at dielectric coefficient < 3 up to a product diameter of 28 mm
– at dielectric coefficient 3 to 6 up to a product diameter of 14 mm
At higher test frequencies, the output loading capability for capacitive loads is lower.
When testing cables with too high capacitance, the spark tester does not reach the
desired value of the test voltage and the maximum achievable test frequency is lower.
Normative reference: UL1581 Reference Standard for Electrical Wires, Cables, and
Flexible Cords, section 910.10: A breakdown is defined as decrease of 25 % or more
from the test voltage applied between the electrode and the earth-grounded conductor.
The fault detector is in compliance with IEC62230: Test with an artificial fault device
according to IEC62230.
28/114 12 ZUMBACH owned companies in Switzerland (H.Q.), Benelux, China, Czech Republic, France, Germany, Spark Tester AST L 15A/25A/40A
India, Italy, Spain, Taiwan, United Kingdom and USA, plus agents and service in more than 40 countries. 20210827_SPAT.010.5023.EN
Adjustment of the sensitivity of the fault detector
The adjustment range for the sensitivity is 10 % to 40 % drop of the test voltage. A
voltage drop of 10 % of the test voltage corresponds to the highest sensitivity and
40 % drop corresponds to the lowest sensitivity, which is more immune against corona
discharges.
Very high test voltages or specific insulating materials may cause strong corona
discharges during spark test. These corona discharges can result in false triggering
of the fault detector. In the majority of cases, there are no specific customer settings
for the sensitivity needed.
The factory setting (highest sensitivity, 10 % voltage drop) is suitable for most of the
products.
If there are false fault indications caused by corona discharges or capacitive loading,
the sensitivity should be decreased.
After changing the sensitivity setting, the proper fault detection should be tested with
the same cable and an artificial fault device (e.g. Calibrator SP).
One count per discrete fault is registered in the fault counter and indicated with the
control and display unit BAE 2 SP as "Total faults".
In addition, if the fault duration is shorter than the time duration of a bare patch event
a fault named "pin hole" is registered, else a "bare patch" is registered.
Via interface, the total number of faults and the number of bare patch events can be
readout.
Fault position
To localize the position of the faults, the length from the beginning of the product to
the fault position can be captured. Therefore, an incremental rotary encoder must be
connected to the spark tester, refer to chapter 4.6.4. The positions of the last faults
(up to 20 faults) can be registered and readout via BAE 2 SP or interface.
Fault resolution
The fault detector detects two consecutive faults with time interval 30ms.
Spark Tester AST L 15A/25A/40A 12 ZUMBACH owned companies in Switzerland (H.Q.), Benelux, China, Czech Republic, France, Germany, 29/111
SPAT.010.5023.EN_20210827 India, Italy, Spain, Taiwan, United Kingdom and USA, plus agents and service in more than 40 countries.
3.9 EXTRUDING AND REWIND MODE
One out of two modes can be selected by a changeover switch located on the rear
panel of the electrode unit:
• Extruding mode:
A fault is counted for each insulation fault.
The red indicator lamp "Alarm" on the electrode unit lights up during the fault and
the set alarm prolongation after each fault. If another fault is detected within this
time, the time duration will be prolonged again by the alarm prolongation.
The potential free output "Alarm" is activated accordingly.
After the fault travels out of the electrode, the spark tester resumes operation and
the test voltage recovers to the desired value.
• Rewind mode:
After detecting a fault, test voltage is switched off immediately and a fault is
counted (bare patch is not indicated in rewind mode).
The red indicator lamp "Alarm" on the electrode unit is switched on. The
potential free output "Alarm" is activated and the output "Test voltage enabled"
deactivated.
A test voltage off-on sequence reactivates the test voltage and deactivates the
red indicator lamp "Alarm". The potential free output "Alarm" is deactivated and
the output "Test voltage enabled" activated.
Active control like switch the test voltage on / off or reset the fault counter can only be
done via the active control position.
The deactivated control positions serve for monitoring values only, e.g. deactivated
control positions indicate the test voltage, actual value and set point value or display
the number of faults, pin holes and bare patches.
30/114 12 ZUMBACH owned companies in Switzerland (H.Q.), Benelux, China, Czech Republic, France, Germany, Spark Tester AST L 15A/25A/40A
India, Italy, Spain, Taiwan, United Kingdom and USA, plus agents and service in more than 40 countries. 20210827_SPAT.010.5023.EN
To activate a desired control position, the following must be done:
The following arrow diagram can be used to identify which control position is the active
control position, whereas the other control positions are deactivated:
Spark Tester AST L 15A/25A/40A 12 ZUMBACH owned companies in Switzerland (H.Q.), Benelux, China, Czech Republic, France, Germany, 31/111
SPAT.010.5023.EN_20210827 India, Italy, Spain, Taiwan, United Kingdom and USA, plus agents and service in more than 40 countries.
4 INSTALLATION
WARNING
When working on the open system, be aware that certain parts of the circuitry
are hazardous life. Disconnect from mains before access.
Follow the indications in this chapter for the installation and initial operation of the
spark tester.
32/114 12 ZUMBACH owned companies in Switzerland (H.Q.), Benelux, China, Czech Republic, France, Germany, Spark Tester AST L 15A/25A/40A
India, Italy, Spain, Taiwan, United Kingdom and USA, plus agents and service in more than 40 countries. 20210827_SPAT.010.5023.EN
4.3 MOUNTING INSTRUCTIONS
Attach the spark tester to the floor with 4 appropriate screws. Use the 11 mm mounting
holes in the mounting brackets of the mounting foot.
• Lift the electrode unit and place the machine mount under the tapped through
hole of the frame.
• Insert the levelling bolt into the tapped through hole and turn it by hand until the
bolt hits bottom. Apply the grease supplied for added lubrication and protection
against corrosion of the levelling bolt.
• Add a nut and a washer between frame and machine mount before turning
the levelling bolt into the machine mount. Screw down the counter nut and the
machine mount as shown above to attach the levelling bolt to the upper part of
the machine mount.
• Balance the electrode unit by using a water level and turning the levelling bolts.
• Lock the levelling bolts by using the remaining nut and washer.
Spark Tester AST L 15A/25A/40A 12 ZUMBACH owned companies in Switzerland (H.Q.), Benelux, China, Czech Republic, France, Germany, 33/111
SPAT.010.5023.EN_20210827 India, Italy, Spain, Taiwan, United Kingdom and USA, plus agents and service in more than 40 countries.
4.4 CONNECTIONS TO THE SPARK TESTER
Host port
Service port
Changeover switch
Extrusion / Rewind
Positioning mark
BAE 2 SP connector
34/114 12 ZUMBACH owned companies in Switzerland (H.Q.), Benelux, China, Czech Republic, France, Germany, Spark Tester AST L 15A/25A/40A
India, Italy, Spain, Taiwan, United Kingdom and USA, plus agents and service in more than 40 countries. 20210827_SPAT.010.5023.EN
4.4.2 Connection to mains
Before connecting to mains, check that your mains voltage corresponds to the input
voltage range specified on the type label.
Use a mains cord that meets the requirements of IEC 60227 or IEC 60245, i.e. rated
voltage at least 300 Vac, three wires with cross section at least 1 mm2 and conductors
coloured brown, blue and green-and-yellow, operating temperature at least 70° C.
The brown conductor must be connected to the phase, the blue conductor to neutral
and the green-and-yellow conductor to protective earth. When the local applicable
regulations are different, then these local regulations must be applied.
The cord must be equipped with a C13 mains connector and the conductors must be
connected as indicated on the rear panel of the electrode unit.
To isolate the spark tester from the electricity supply, unplug the mains connector in
the rear of the electrode unit.
If it is impossible to access this connector, the customer must install a suitable device
for external disconnection.
The BAE 2 SP is pivot-mounted and can be pivoted in horizontal and vertical direction.
Spark Tester AST L 15A/25A/40A 12 ZUMBACH owned companies in Switzerland (H.Q.), Benelux, China, Czech Republic, France, Germany, 35/111
SPAT.010.5023.EN_20210827 India, Italy, Spain, Taiwan, United Kingdom and USA, plus agents and service in more than 40 countries.
Connection to the Positioning
electrode unit mark
The connector on both sides is a quick connecting device. Align the positioning mark
of plug and socket, plug in and turn the locking jacket by about one half turn.
Connect the electrode unit to the control and display unit BAE 2 SP only with the cable
supplied by Zumbach Electronic AG.
Follow the recommendations below for earthing the spark tester in order to avoid
interference caused by the current of the spark tester to earth.
The wire cross section for the earth connections depend on the current carrying capacity
of the installation on the users site. The minimum cross section is 1 mm2. When the
local applicable regulations are different, then these local regulations must be applied.
36/114 12 ZUMBACH owned companies in Switzerland (H.Q.), Benelux, China, Czech Republic, France, Germany, Spark Tester AST L 15A/25A/40A
India, Italy, Spain, Taiwan, United Kingdom and USA, plus agents and service in more than 40 countries. 20210827_SPAT.010.5023.EN
• Directly earth the cable to be tested to the M6 earth screw in the rear of the
electrode unit. This will prevent earth currents caused by spark tests in your
facilities.
• The electrode unit is earthed via the protective earth connection of the mains
cord. Connect an additional earth wire between the earthing of the building and
the M6 earth screw in the rear of the electrode unit.
• The cable between the electrode unit and the control and display unit BAE 2 SP
does not constitute an earth connection.
Bad: Good:
• Set up the earth connection between the cable to be tested and the spark
tester in such a way that the surface (designated by A and marked in gray in the
previous figure) limited by the current loop (current loop: test electrode – cable
– earth connection – test electrode) is as small as possible. This will reduce
electromagnetic interference (EMC) during operation.
• After installation, verify electrically the proper operation of the earthing.
Spark Tester AST L 15A/25A/40A 12 ZUMBACH owned companies in Switzerland (H.Q.), Benelux, China, Czech Republic, France, Germany, 37/111
SPAT.010.5023.EN_20210827 India, Italy, Spain, Taiwan, United Kingdom and USA, plus agents and service in more than 40 countries.
4.6 SETTINGS AND USER INTERFACES
The following connectors and user interfaces are available on the rear panel:
BAE 2 SP
Control and display unit, refer to chapter 4.6.1
Emergency stop
Remote start / stop and emergency stop input, refer to chapter 4.6.3
Encoder
To localise the position of faults, refer to chapter 4.6.4
Service
The Ethernet based service port can be used for the web visualisation to configure
and calibrate the spark tester. Refer to chapters 4.6.5, 9 and 14
The electrode unit is equipped with one of the following interfaces, according to the
version of the electrode unit:
RS interface
Refer to chapters 4.6.7 and 10
Ethernet
For the Ethernet host port, refer to chapters 4.6.8 and 11
For the host protocol description refer to chapter 10
Profibus DP
Refer to chapter 4.6.9 and the Profibus DP software instruction manual ZUMB.011.0700.E
Profinet
Refer to chapter 4.6.10 and 12
Ethernet IP
Refer to the Ethernet IP Adapter instruction manual SPAT.010.0003.EN
38/114 12 ZUMBACH owned companies in Switzerland (H.Q.), Benelux, China, Czech Republic, France, Germany, Spark Tester AST L 15A/25A/40A
India, Italy, Spain, Taiwan, United Kingdom and USA, plus agents and service in more than 40 countries. 20210827_SPAT.010.5023.EN
4.6.1 Operating mode of the control and display unit BAE 2 SP
The BAE 2 SP can be used in one of the two following modes:
If the BAE 2 SP is not connected to the electrode unit, one out of the interfaces can
be selected to be the active control position.
The changeover switch for selecting the desired mode is located inside the BAE 2 SP:
Remove the small anthracite end caps of the two screws on the left side and unscrew
the side frame on the left (Torx T10) to access the changeover switch.
Spark Tester AST L 15A/25A/40A 12 ZUMBACH owned companies in Switzerland (H.Q.), Benelux, China, Czech Republic, France, Germany, 39/111
SPAT.010.5023.EN_20210827 India, Italy, Spain, Taiwan, United Kingdom and USA, plus agents and service in more than 40 countries.
4.6.2 Configuration menu of the control and display unit BAE 2 SP
Refer to chapter 5.5.1 on how to use the BAE 2 SP.
– Push the "Config." key until the page 1 / 6 of the configuration menu appears
– Select the desired language by entering the corresponding digit and terminate
with the key "Enter"
– Adjust the brightness of the display
– Push the "Config." key until the page 2 / 6 of the configuration menu appears
– Activate or deactivate the encoder
– Select the desired unit of length
– Incremental rotary encoder input: adjust the length of product between 2 pulses.
– Push the "Config." key until the page 3 / 6 of the configuration menu appears
– Activate or deactivate the password protection for the menu "Nominal"
– Set the desired password for the menu "Nominal", 6 digits
40/114 12 ZUMBACH owned companies in Switzerland (H.Q.), Benelux, China, Czech Republic, France, Germany, Spark Tester AST L 15A/25A/40A
India, Italy, Spain, Taiwan, United Kingdom and USA, plus agents and service in more than 40 countries. 20210827_SPAT.010.5023.EN
– Push the "Config." key until the page 4 / 6 of the configuration menu appears
– Activate or deactivate the password protection for the menu "Configuration"
– Set the desired password for the menu "Configuration"
– Push the "Config." key until the page 5 / 6 of the configuration menu appears
– Activate or deactivate the password protection for the menu "Calibration"
– Set the desired password for the menu "Calibration"
– Push the "Config." key until the page 6 / 6 of the configuration menu appears
– Set the IP address of the spark tester, factory setting 192.168.001.009
– Set the subnet mask, factory setting 255.255.255.000
– Set the gateway address, factory setting 192.168.001.001
Spark Tester AST L 15A/25A/40A 12 ZUMBACH owned companies in Switzerland (H.Q.), Benelux, China, Czech Republic, France, Germany, 41/111
SPAT.010.5023.EN_20210827 India, Italy, Spain, Taiwan, United Kingdom and USA, plus agents and service in more than 40 countries.
4.6.3 Emergency stop connector
This remote input can be used for one of the following applications:
• Remote start / stop:
This potential free 24 Vdc input can be used to activate the test voltage (24 Vdc)
and to deactivate the test voltage (pin 2, 3 free from tension).
This input allows to activate and deactivate several equipment together in one
wire line.
•Emergency stop:
If one or several emergency stops are needed for a given installation, the
emergency stop devices can be connected to the connector "Emergency stop".
The emergency stop device must be equipped with a potential free normally
closed contact and the contact must sustain open after activation, until the
operator disengages the stop command.
WARNING
Electronic control via normal serial interfaces is not accepted by safety standards
to be the sole means of inhibition. Always use the emergency stop interface (or
open the electrode or remove the power cord) before touching the product to
be tested.
42/114 12 ZUMBACH owned companies in Switzerland (H.Q.), Benelux, China, Czech Republic, France, Germany, Spark Tester AST L 15A/25A/40A
India, Italy, Spain, Taiwan, United Kingdom and USA, plus agents and service in more than 40 countries. 20210827_SPAT.010.5023.EN
The circuit diagram below shows on how to use the emergency stop interface.
Spark Tester AST L 15A/25A/40A 12 ZUMBACH owned companies in Switzerland (H.Q.), Benelux, China, Czech Republic, France, Germany, 43/111
SPAT.010.5023.EN_20210827 India, Italy, Spain, Taiwan, United Kingdom and USA, plus agents and service in more than 40 countries.
4.6.4 Encoder
To localize the position of the faults, the length from the beginning of the product to
the fault position can be captured. Therefore, an incremental rotary encoder must be
connected to the encoder input.
The encoder must provide the following two quadrature signals, phase A and phase B:
Viewed from the end of the shaft, if the shaft is rotated clockwise (CW), phase A
normally leads phase B in this rotation direction and the counter increments. If the
shaft is rotated counterclockwise (CCW), phase B leads phase A and the counter
decrements. X1 encoding is used: one pulse results in one increment or decrement
of the counter.
The output circuit of the encoder should be either a complementary output a) or open
collector output b).
44/114 12 ZUMBACH owned companies in Switzerland (H.Q.), Benelux, China, Czech Republic, France, Germany, Spark Tester AST L 15A/25A/40A
India, Italy, Spain, Taiwan, United Kingdom and USA, plus agents and service in more than 40 countries. 20210827_SPAT.010.5023.EN
For each pulse, the length counter increments or decrements. The following settings
are to be done for the spark tester:
• Select the desired unit of length: metric or imperial
• Switch the length detector on or off
• Enter the length between two pulses of the encoder
The settings can be done via serial interface or control and display unit BAE 2 SP
(menu "Config.", page 2 / 6).
The length between two pulses depends on the number of pulses per revolution and
the diameter of the measuring wheel:
len = (p * diam) / n
where as:
len: length between two pulses, in meter or inch
p: 3.14
diam: diameter of the measuring wheel
n: number of pulses per revolution
Spark Tester AST L 15A/25A/40A 12 ZUMBACH owned companies in Switzerland (H.Q.), Benelux, China, Czech Republic, France, Germany, 45/111
SPAT.010.5023.EN_20210827 India, Italy, Spain, Taiwan, United Kingdom and USA, plus agents and service in more than 40 countries.
4.6.5 Setting up the Service Ethernet interface
The service interface can be used for the web visualisation to configure and calibrate
the spark tester.
Reset button:
Resets the service interface to the factory settings.
Procedure: press the button for 5 sec. with a pointed object: for example, carefully press
the button using an opened out paper clip inserted through the hole on the connector
plate. The unit automatically restarts after releasing the button. The link LED goes off
briefly when the unit is connected to the Ethernet.
46/114 12 ZUMBACH owned companies in Switzerland (H.Q.), Benelux, China, Czech Republic, France, Germany, Spark Tester AST L 15A/25A/40A
India, Italy, Spain, Taiwan, United Kingdom and USA, plus agents and service in more than 40 countries. 20210827_SPAT.010.5023.EN
4.6.6 Potential free analog / digital input / output
The electrode units are equipped with the following interface connector on the rear
panel:
Electrode unit
1 ALARM_CO
2 ALARM_NO
3 ALARM_NC
4 BARE_CO
5 BARE_NO
6 BARE_NC
7 ST_ENABLED_CO
8 ST_ENABLED_NO
9 ST_ENABLED_NC
10 TV_ENABLED_CO
11 TV_ENABLED_NO
12 TV_ENABLED_NC
13 FAULT+
14 FAULT-
15 ACTUAL
16 GND2
17 NOMINAL
18 TV_ON+
19 TV_ON-
20 RESET+
21 RESET-
All interfaces are electrically separated from the electronics and from each other.
The potential of the interface signals must be close to earth.
Spark Tester AST L 15A/25A/40A 12 ZUMBACH owned companies in Switzerland (H.Q.), Benelux, China, Czech Republic, France, Germany, 47/111
SPAT.010.5023.EN_20210827 India, Italy, Spain, Taiwan, United Kingdom and USA, plus agents and service in more than 40 countries.
Assignment of the connector "Potential free I / O"
The relay coils are non polarized and there is no freewheeling diode needed.
Alarm output
• Extruding mode:
If a fault is detected, the normally closed contact (pin 1, 3) opens during the
fault and during the set alarm prolongation after the fault, and the normally open
contact (pin 1, 2) is closed accordingly. If another fault is detected within this time,
the time duration will be prolonged to the alarm duration after the last fault.
• Rewind mode:
If a fault is detected, the normally closed contact (pin 1, 3) opens and the
normally open contact (pin 1, 2) is closed.
A test voltage off-on sequence reactivated the test voltage and resets the alarm
output to default state.
48/114 12 ZUMBACH owned companies in Switzerland (H.Q.), Benelux, China, Czech Republic, France, Germany, Spark Tester AST L 15A/25A/40A
India, Italy, Spain, Taiwan, United Kingdom and USA, plus agents and service in more than 40 countries. 20210827_SPAT.010.5023.EN
Spark tester enabled output
If the spark tester is powered by mains and there are no internal faults, the normally
closed contact (pin 7, 9) is open and the normally open contact (pin 7, 8) is closed.
Spark Tester AST L 15A/25A/40A 12 ZUMBACH owned companies in Switzerland (H.Q.), Benelux, China, Czech Republic, France, Germany, 49/111
SPAT.010.5023.EN_20210827 India, Italy, Spain, Taiwan, United Kingdom and USA, plus agents and service in more than 40 countries.
4.6.7 Setting up the user configuration for RS host interface
Host
Description Value
parameter
7 -> Automatic output mode for USYS
a945 Output mode
(see grouped message d182)
a970 Baud rate 9 -> 57600 baud
a971 Bits per character 1 -> 7 bits
a972 Number of stop bits 0 -> 1 Stop bit
a973 Parity 0 -> Even
a983 Transmission mode 1 -> RS422, full duplex, RTS on zero
a986 Protocol selection 1 -> Host protocol
Pin 1 Pin 5
Pin 6
Pin 9
For further information and other settings possibilities, refer to the chapter 13.
50/114 12 ZUMBACH owned companies in Switzerland (H.Q.), Benelux, China, Czech Republic, France, Germany, Spark Tester AST L 15A/25A/40A
India, Italy, Spain, Taiwan, United Kingdom and USA, plus agents and service in more than 40 countries. 20210827_SPAT.010.5023.EN
4.6.8 Setting up the Ethernet interface
The measured values and parameters are, using a selectable Zumbach protocol
(ODAC or host protocol), integrated and transmitted in standardized packages of the
TCP / IP Protocol. This allows data transfer via existing networks such as company
internal networks.
The LEDs COM 0 + 1 are not used and are therefore always switched off.
Both Ethernet interfaces are internally connected via a switch and allow a through
looping of the connection to simplify wiring.
The spark testers are set as factory setting with IP address: 192.168.001.009, subnet
mask: 255.255.255.0 and Gateway address: 192.168.001.001 when delivered. These
addresses can be set and read via the service interface with the following ODAC / host
parameter IP: IL / a940 - subnet : IM / a941 – Gateway : IO / a942.
The TCP / IP port is permanently set to 2020 and cannot be changed.
Before connecting the Interface to the Ethernet network, it is necessary to adjust the
Ethernet parameters IP Address, Subnet Mask and Gateway Address with the service
interface (A940, A941, A942 see chapter 13):
The input of the parameters (A940, A941, A942) is not followed by an automatic
acknowledgement from the spark tester (because automatic software restart). A delay
of 3 – 5 seconds must be respected before treating the next parameter. The measuring
spark tester returns an [NAK] if wrong parameter has been given.
Spark Tester AST L 15A/25A/40A 12 ZUMBACH owned companies in Switzerland (H.Q.), Benelux, China, Czech Republic, France, Germany, 51/111
SPAT.010.5023.EN_20210827 India, Italy, Spain, Taiwan, United Kingdom and USA, plus agents and service in more than 40 countries.
4.6.9 Setting up the user configuration for Profibus DP interface
After a change of the Profibus DP slave address, the spark tester has to be restarted.
Unplug the mains plug and replug it after a short time of waiting. The new address is
only valid after new startup.
Termination resistor
If your slave is the last device on the Profibus network, you have to switch on
the termination resistor with the switch on the external 9 pin Sub-D connector.
This is absolutely necessary to insure a correct impedance adaptation of the network.
If your slave is not at the latest position, then disconnect this resistor with moving the
switch to position off.
For further information, refer to the Profibus DP norm DIN 19245-1.
52/114 12 ZUMBACH owned companies in Switzerland (H.Q.), Benelux, China, Czech Republic, France, Germany, Spark Tester AST L 15A/25A/40A
India, Italy, Spain, Taiwan, United Kingdom and USA, plus agents and service in more than 40 countries. 20210827_SPAT.010.5023.EN
Pin assignment on the Profibus DP 9p Sub-D female connector
Pin 5 Pin 1
Pin 9
LED signification
This interface complies with the Profibus DP standards IEC 61158 / IEC 61784
Spark Tester AST L 15A/25A/40A 12 ZUMBACH owned companies in Switzerland (H.Q.), Benelux, China, Czech Republic, France, Germany, 53/111
SPAT.010.5023.EN_20210827 India, Italy, Spain, Taiwan, United Kingdom and USA, plus agents and service in more than 40 countries.
4.6.10 Setting up the Profinet interface
This version has been developed especially for the integration in a real-time Ethernet
according to the Profinet IO standard. The PLC interface or the system computer
(Profinet controller, supervisor) communicates with the spark tester (Profinet device).
Both Ethernet interfaces are internally connected via a switch and allow a through
looping of the connection to simplify wiring.
The spark testers are set as factory setting with IP address: 192.168.001.009, subnet
mask: 255.255.255.0 and Gateway address: 192.168.001.001 when delivered. When
initially starting the unit the PLC development environment assigns a Profinet unit
name. The Ethernet address (00-02-A2-XX-XX-XX) is imprinted to distinguish the unit.
The Profinet controller assigns the IP addresses automatically to the units (as set in
the PLC project) when starting.
54/114 12 ZUMBACH owned companies in Switzerland (H.Q.), Benelux, China, Czech Republic, France, Germany, Spark Tester AST L 15A/25A/40A
India, Italy, Spain, Taiwan, United Kingdom and USA, plus agents and service in more than 40 countries. 20210827_SPAT.010.5023.EN
4.7 PROTECTION AGAINST OZONE
Refer to chapter 2.4.3 for further information about ozone.
If the concentration of ozone in the workplace is much higher than the odour threshold at
which ozone can be smelled, the following means of protection must be applied:
1. Connect an air duct with 80 mm inner diameter to the ozone extraction port of the
electrode unit and evacuate the air from the inside of the electrode unit.
2. Use one of the following methods for the extracted air:
– Exhaust the extracted air outside the building
– Use an activated carbon filter or ozone absorber to remove the ozone
– Use a thermal ozone converter to decay the ozone
Normally, the ozone concentration is so low, that also less ozone- resistant materials
can be used like:
– ABS plastic
– Acrylic
– Aluminium
– Copper, brass, bronce
– LDPE
– Polyacrylate
Spark Tester AST L 15A/25A/40A 12 ZUMBACH owned companies in Switzerland (H.Q.), Benelux, China, Czech Republic, France, Germany, 55/111
SPAT.010.5023.EN_20210827 India, Italy, Spain, Taiwan, United Kingdom and USA, plus agents and service in more than 40 countries.
5 OPERATING INSTRUCTIONS
• Familiarize yourself with all aspects of the operation. Pay particular attention
to safety instructions.
• Instruct the operating personnel on how to use spark tester and to avoid
hazards when operating spark testers.
Always earth the conductor or shielding of the cable to be tested on both sides.
Refer to chapter 5.1 for further information.
Follow the directions for cleaning the electrode given in chapter 5.2
For common aspects about operation refer to chapter 5.3 and 5.4.
For control via control and display unit BAE 2 SP, refer to chapter 5.5.
According to the remote interface built-in in the electrode unit, the information is given
in the following chapters:
– RS interface: Chapter 5.6
– Profibus DP:
Chapter 5.7 and the Profibus DP software instruction manual ZUMB.011.0700.E
– Ethernet: Chapter 5.8
– Profinet: Chapter 5.9
– Potential free inputs / outputs: Chapter 5.10
For further information about earthing, refer to chapter 2.4.1 and 4.5
56/114 12 ZUMBACH owned companies in Switzerland (H.Q.), Benelux, China, Czech Republic, France, Germany, Spark Tester AST L 15A/25A/40A
India, Italy, Spain, Taiwan, United Kingdom and USA, plus agents and service in more than 40 countries. 20210827_SPAT.010.5023.EN
5.3 TEST VOLTAGE
The value of the test voltage depends on the thickness of the outer insulation and the
standard used. The following standards, among others, contain concrete specifications
on the value of the test voltage.
• IEC 62230
• ISO 6722-1
• UL44, UL 444
• Leakage currents:
Depending on the electrical conductivity of the product to be tested, a leakage
current will flow from the high voltage electrode to the earthed conductor and
the bead chains for charge removal. At too high leakage currents, the current is
limited by reducing the output voltage. Therefore the desired value of the test
voltage cannot be reached.
Spark Tester AST L 15A/25A/40A 12 ZUMBACH owned companies in Switzerland (H.Q.), Benelux, China, Czech Republic, France, Germany, 57/111
SPAT.010.5023.EN_20210827 India, Italy, Spain, Taiwan, United Kingdom and USA, plus agents and service in more than 40 countries.
5.5 USING THE SPARK TESTER WITH CONTROL AND DISPLAY UNIT BAE 2 SP
Push button"Nominal"
for menu nominal
Numeric keypad
To enter numeric values in various input fields.
Key Function
0 .. 9 Numerals to enter values in input fields.
+/- Toggles the sign of certain inputs
Select Reserved for future use
Shifts the cursor to the next input field.
58/114 12 ZUMBACH owned companies in Switzerland (H.Q.), Benelux, China, Czech Republic, France, Germany, Spark Tester AST L 15A/25A/40A
India, Italy, Spain, Taiwan, United Kingdom and USA, plus agents and service in more than 40 countries. 20210827_SPAT.010.5023.EN
Function keys
for selecting menus, scroll pages and activating or deactivating functions:
Key Function
Test Toggles the high voltage on and off each time the key is pressed.
voltage In rewind mode, the test voltage is switched off after a fault.
Press the test voltage key twice to reactivate the test voltage.
Config. Opens the menu configuration or shows the next page of the menu
configuration. This menu is intended for the service personnel to
configure the spark tester.
Press this key repeatedly to display successive pages of the menu
configuration.
Actual Opens the menu actual or shows the next page of the menu actual.
This menu displays actual values, like the test voltage, faults and and
setpoints. Press this key repeatedly to display successive pages of
the menu actual.
Calib. Opens the menu calibration or shows the next page of the menu
calibration. This menu is intended for the service personnel to adjust
the the spark tester if needed during calibration. Press this key
repeatedly to display successive pages of the menu calibration.
Nominal Opens the menu nominal or shows the next page of the menu
nominal. This menu is for entering setpoints. Press this key
repeatedly to display successive pages of the menu nominal.
Fault Resets the fault counter, pin hole counter, bare patch counter and
reset the actual length. All measured fault position values are cleared.
Signalization lamps
Lamp Function
Red LED The red indicator lamp "Alarm" lights up during the fault and during 0.7 s
"Alarm" after each fault. If another fault is detected within this time, the time
duration will be prolonged to 0.7 seconds after the last fault.
In rewind mode, the red indicator lamp "Alarm" remains on until the test
voltage is reactivated.
The function of the red LED is the same as the red indicator lamp on
the electrode unit.
Yellow LED The yellow lamp is on when the test voltage is switched on. The function
"Test of the yellow LED is the same as the yellow indicator lamp on the
voltage" electrode unit.
Green LED The green lamp is on when the cover is closed and the emergency stop
"Ready" input is activated.
Spark Tester AST L 15A/25A/40A 12 ZUMBACH owned companies in Switzerland (H.Q.), Benelux, China, Czech Republic, France, Germany, 59/111
SPAT.010.5023.EN_20210827 India, Italy, Spain, Taiwan, United Kingdom and USA, plus agents and service in more than 40 countries.
Graphic display
The graphic display is subdivided in the following areas:
Actual page
of the menu
Indicator
panel
Information
line
If a menu has more than one page, the symbol ">>>" and the number of the actual
page are indicated in the upper right corner. Press the corresponding menu key again
to display the next page of the menu.
The information line displays error messages and normal operating state messages.
The information line is displayed in the same way on all pages.
60/114 12 ZUMBACH owned companies in Switzerland (H.Q.), Benelux, China, Czech Republic, France, Germany, Spark Tester AST L 15A/25A/40A
India, Italy, Spain, Taiwan, United Kingdom and USA, plus agents and service in more than 40 countries. 20210827_SPAT.010.5023.EN
5.5.2 Control spark testers with control and display unit BAE 2 SP
For control with BAE 2 SP, the BAE 2 SP must be the active control position, and
therefore, the internal changeover switch inside the BAE 2 SP must be set in position
C = control. For further information, refer to chapters 3.10 and 4.6.1.
• Introduce the product to be tested into the electrode, then close the electrode
• Earth the metal conductor of the cable to be tested on both cable heads
(see also chapters 2.4.1 and 5.1) .
• The spark tester must be connected to mains via the mains cord
• The green signalization lamp on the BAE 2 SP should light up (electrode closed
and test voltage activated via emergency stop input )
• Reset the fault counter if needed by pushing the button "Fault reset"
• Set the desired test voltage and test frequency:
– Select the page 1 / 2 of the menu nominal by pushing the button "Nominal"
– Enter the desired test voltage by using the numeric keypad and confirm with
the key "Enter"
– Enter the voltage tolerance (normally 5 -20 % of the test voltage) accordingly
– Select the page 2 / 2 of the menu nominal by pushing the button "Nominal"
– Enter the sensitivity of the fault detector by using the numeric keypad and
confirm with the key "Enter". The highest sensitivity (10 % voltage drop) is
suitable for most of the products.
– Enter the minimum duration of the bare patch event accordingly
• Switch on the test voltage by pushing the button "Test voltage"
• The yellow signalization lamps "Test voltage on" on the electrode unit and on the
BAE 2 SP lights up.
• If an insulation fault occurs, the fault counter is incremented and the red alarm
signalization lamps on the electrode unit and on the BAE 2 SP lights up.
When working in rewind mode (switch in the rear of the electrode unit in position
rewind), the test voltage is automatically switched off when an insulation fault
occurs and the red signalization lamps "Alarm" remain on.
Spark Tester AST L 15A/25A/40A 12 ZUMBACH owned companies in Switzerland (H.Q.), Benelux, China, Czech Republic, France, Germany, 61/111
SPAT.010.5023.EN_20210827 India, Italy, Spain, Taiwan, United Kingdom and USA, plus agents and service in more than 40 countries.
To reactivate the test voltage and deactivate the red indicator lamps, push the button
"Test voltage" twice.
• To display the current test voltage and the number of faults, select the page 1 / 3
of the menu actual by pushing the button "Actual":
One count per discrete fault is registered in the fault counter and indicated as "Total
faults". In addition, if the fault duration is shorter than the time duration of a bare patch
event a fault named "pin hole" is registered, else a "bare patch" is registered.
• If the length detector is configured, select the page 2 / 3 of the menu actual by
pushing the button "Actual" to display the position of the faults:
• To display the current test parameters, select the page 3 / 3 of the menu actual by
pushing the button "Actual":
The current length position is shown only when the length detector is configured.
• Switch off the test voltage after the test or at standstill line by pushing the button
"Test voltage". If the test voltage is switched off, the yellow signalization lamps
"Test voltage" on the electrode unit and on the BAE 2 SP are in off-state.
• Disconnect the spark tester from mains if not used for some time.
62/114 12 ZUMBACH owned companies in Switzerland (H.Q.), Benelux, China, Czech Republic, France, Germany, Spark Tester AST L 15A/25A/40A
India, Italy, Spain, Taiwan, United Kingdom and USA, plus agents and service in more than 40 countries. 20210827_SPAT.010.5023.EN
5.5.3 Using the control and display unit BAE 2 SP as local display
The spark tester is operated via the built-in remote interface.
For use as display, the internal changeover switch in the BAE 2 SP must be set to D
= display.
In display mode, the BAE 2 SP is not the active control position, and therefore, the
following controls are deactivated:
– inactive keys: "Test voltage", "Fault reset"
– inactive settings in menu: Nominal, configuration and calibration
Inactive functions are indicated in the information line "INACTIVE KEY".
In display mode, current values and settings can be monitored by selecting the menus
actual and nominal. For further information about the displayed values, refer to chapter
5.5.2.
Refer to chapter 4.6.6 for information about the potential free inputs / outputs.
• Introduce the product to be tested into the electrode, then close the electrode
• Earth the metal conductor of the cable to be tested on both cable heads
(see also chapter 2.4.1 and 5.1) .
• The spark tester must be connected to mains via the mains cord. If there are no
internal faults, the spark tester enabled output (pin 7, 8 and 9) is activated.
• Set the desired test voltage:
Apply a control voltage in the range of 0 … 10 V and proportional to the desired
test voltage to pin 17 Nominal and pin 16 GND2 .
The maximum value of 10 V corresponds to the maximum test voltage of 15 kV,
25 kV or 40 kV.
• Reset the fault counter if needed by applying a 24 V pulse to pin 20, 21.
• Switch on the test voltage by applying 24 Vdc to the test voltage on input
(pin 18, 19).
The yellow signalization lamps on the electrode unit and on the control and
display unit BAE 2 SP light up if the test voltage is switched on.
• The output signal on Actual pin 15 and pin 16 GND2 is proportional to the actual
test voltage. 10 V corresponds to the maximum voltage 15 kV, 25 kV or 40 kV.
• If an insulation fault occurs, the red alarm signalization lamps on the electrode
unit and on the BAE 2 SP light up during at least 0.7 s. The fault is signalled
via the output alarm (pin 1, 2 and 3). In addition in extrude mode, if the fault
lasts longer than the duration of the bare patch event, the bare patch output is
activated (pin 4, 5 and 7).
Spark Tester AST L 15A/25A/40A 12 ZUMBACH owned companies in Switzerland (H.Q.), Benelux, China, Czech Republic, France, Germany, 63/111
SPAT.010.5023.EN_20210827 India, Italy, Spain, Taiwan, United Kingdom and USA, plus agents and service in more than 40 countries.
When working in rewind mode (switch in the rear of the electrode unit in position
rewind), the test voltage is automatically switched off when an insulation fault
occurs and the red signalization lamps "Alarm" remain on.
To reactivate the test voltage and deactivate the red indicator lamps, make the
test voltage on input (pin 18, 19) free of tension and apply again 24 Vdc to switch
the test voltage on.
• Switch off the test voltage after the test or at standstill line by make the test
voltage on input (pin 18, 19) free of tension. If the test voltage is switched off, the
yellow signalization lamps "Test voltage on" on the electrode unit and on the BAE
2 SP are in off-state.
• Disconnect the spark tester from mains if not used for some time.
64/114 12 ZUMBACH owned companies in Switzerland (H.Q.), Benelux, China, Czech Republic, France, Germany, Spark Tester AST L 15A/25A/40A
India, Italy, Spain, Taiwan, United Kingdom and USA, plus agents and service in more than 40 countries. 20210827_SPAT.010.5023.EN
• Switch off the test voltage after the test or at standstill line:
Test voltage on / off command F710 0 → off
• Before touching the product, deactivate the test voltage via connector
"Emergency stop" or open the electrode
• Disconnect the spark tester from mains if not used for some time.
Spark Tester AST L 15A/25A/40A 12 ZUMBACH owned companies in Switzerland (H.Q.), Benelux, China, Czech Republic, France, Germany, 65/111
SPAT.010.5023.EN_20210827 India, Italy, Spain, Taiwan, United Kingdom and USA, plus agents and service in more than 40 countries.
6 MAINTENANCE
WARNING
When working on the open system, be aware that certain parts of the circuitry
are hazardous life. Disconnect from mains before access.
Cleaning
• Clean the chain or brush electrodes of the spark tester with a cloth and isopropyl
alcohol or methylated spirits. Eliminate deposits on the chains or brushes. Use a
metallic brush to remove the dirt that adheres too tenaciously to the electrode.
• Clean regularly the inside of the electrode unit and the insulators. Check if there
are creepage paths on the insulator (erosion, brown or black traces eroded into
the surface of the insulator). Defective insulators must be replaced. Refer to
chapter 2.4.2 "Fire hazard due to deposits in the electrode unit".
Defective parts:
Regularly inspect the spark tester and replace defective parts, e. g. damage cables,
viewing glass, insulators, defective signalization lamps, charge removal devices etc.
Use only original spare parts. The spare parts are listed in chapter 7.3.
Calibration:
It is recommended that the calibration is carried out once a year. Refer to chapter 6.3.
Safety check:
The safety check as described in chapter 6.2 must be done at least once a year and
every time when in doubt on the proper operation of the spark tester.
66/114 12 ZUMBACH owned companies in Switzerland (H.Q.), Benelux, China, Czech Republic, France, Germany, Spark Tester AST L 15A/25A/40A
India, Italy, Spain, Taiwan, United Kingdom and USA, plus agents and service in more than 40 countries. 20210827_SPAT.010.5023.EN
6.2 SAFETY CHECK OF THE SPARK TESTER
This check must be performed at least once a year and every time when in doubt on
the proper operation of the spark tester:
If this test does not proceed correctly, do not use the electrode unit anymore and take
it out of service. Return the electrode unit for repair.
In addition, check all protective earth conductors of the spark tester system, as
described in chapter 4.5.
Report all measured values in the calibration report form shown in chapter 6.5.
Spark Tester AST L 15A/25A/40A 12 ZUMBACH owned companies in Switzerland (H.Q.), Benelux, China, Czech Republic, France, Germany, 67/111
SPAT.010.5023.EN_20210827 India, Italy, Spain, Taiwan, United Kingdom and USA, plus agents and service in more than 40 countries.
A calibration can only be done:
– Via control and display unit BAE 2 SP: Chapter 6.6
– Via service port, RS or Ethernet interface: Chapter 6.7
• Test frequency:
AST L xxA: The test frequency corresponds to the adjusted value and is in the
range of 50 Hz to 120 Hz.
AST H 15A: The test frequency depends on the load capacitance and is in the
range of 2 ... 4 kHz
• Test Voltage:
RMS value, positive or negative peak value, average value
• Sensitivity of the fault detector:
The Calibrator SP is equipped with an artificial fault device
according to IEC 62230
• Test frequency
• Short circuit current:
RMS value, average value
Contact the Zumbach sales organisation for more information.
68/114 12 ZUMBACH owned companies in Switzerland (H.Q.), Benelux, China, Czech Republic, France, Germany, Spark Tester AST L 15A/25A/40A
India, Italy, Spain, Taiwan, United Kingdom and USA, plus agents and service in more than 40 countries. 20210827_SPAT.010.5023.EN
6.5 CALIBRATION FORM FOR SPARK TESTER
The following form can be used for the calibration and the verification of spark testers
according to the standard IEC 62230 and the prescriptions in this manual.
calibration report
Calibration done by Calibration number
Address Calibration date
Calibration location
Manufacturer Zumbach As received (in / out of tol.)
Spark tester model As returned (in / out of tol.)
Order number Asset number
Serial number Accessories
The results reported herein apply only to the calibration of the item described above and no
limitations of use apply to the calibrated unit.
1
) According to the specification for this spark tester the admissible error is: ± 4 %
Used standard
ID number Model Calibration date Due date Traceability
number
The control and display unit BAE 2 SP must be connected to the electrode unit and
the internal changeover switch must be in position C = control, refer to chapter 4.4.1.
2. Select the page 1 / 2 of the menu nominal and set the test voltage to 3 kV
3. Switch the test voltage on
4. Measure the test voltage with the calibrator SP.
5. Select the page 1 / 6 of the menu calibration and enter the measured test voltage
value.
6. Select the page 1 / 2 of the menu nominal and set the test voltage to 13 kV, 23 kV
or 36 kV (25 kV max with the Calibrator SP) according to the maximum voltage of
the spark tester.
70/114 12 ZUMBACH owned companies in Switzerland (H.Q.), Benelux, China, Czech Republic, France, Germany, Spark Tester AST L 15A/25A/40A
India, Italy, Spain, Taiwan, United Kingdom and USA, plus agents and service in more than 40 countries. 20210827_SPAT.010.5023.EN
7. Measure the test voltage with the calibrator SP.
8. Select the page 2 / 6 of the menu calibration and enter the measured test voltage
value.
9. To finish the calibration and save the values, enter "1".
After pushing the button "Enter" the result of the calibration is displayed on the
input field for short duration:
– "OK" the calibration is passed
– "ERROR" the calibration failed due to too large deviation.
Verify if the procedure has been done correctly and calibrate again.
10. Verify the calibration: Set the test voltage to the two operating points used
above and measure the test voltage with the calibrator SP.
11. Switch the test voltage off.
1. Apply a control voltage of 2Vdc to the input nominal pin 17 and GND2 pin 16 of
the connector "Potential free I / O" in the rear of the electrode unit.
Measure this control voltage with a digital voltmeter.
2. Select the page 3 / 6 of the menu calibration and enter the measured control
voltage value.
3. Apply a control voltage of 9 Vdc to the input nominal pin 17 and GND2 pin 16.
Measure this control voltage with a digital voltmeter.
Spark Tester AST L 15A/25A/40A 12 ZUMBACH owned companies in Switzerland (H.Q.), Benelux, China, Czech Republic, France, Germany, 71/111
SPAT.010.5023.EN_20210827 India, Italy, Spain, Taiwan, United Kingdom and USA, plus agents and service in more than 40 countries.
4. Select the page 4 / 6 of the menu calibration and enter the measured control
voltage value.
5. To finish the calibration and save the values, enter "1".
After pushing the button "Enter" the result of the calibration is displayed on the
input field for short duration:
– "OK" the calibration is passed
– "ERROR" the calibration failed due to too large deviation.
Verify if the procedure has been done correctly and calibrate again.
6. Verify the calibration: Set the control voltage to the two operating points used
above and measure the test voltage with the calibrator SP.
Therefore, the control and display unit BAE 2 SP must be disconnected to
activate the potential free inputs / outputs as active control position.
7. Switch the test voltage off.
1. Select the page 1 / 2 of the menu nominal and set the test voltage to 3 kV.
2. Switch the test voltage on.
3. Use a digital voltmeter to measure the voltage on actual pin 15 and GND2 pin 16
of the connector "Potential free I / O" in the rear of the electrode unit.
4. Select the page 5 / 6 of the menu calibration and enter the measured voltage
value.
72/114 12 ZUMBACH owned companies in Switzerland (H.Q.), Benelux, China, Czech Republic, France, Germany, Spark Tester AST L 15A/25A/40A
India, Italy, Spain, Taiwan, United Kingdom and USA, plus agents and service in more than 40 countries. 20210827_SPAT.010.5023.EN
5. Select the page 1 / 2 of the menu nominal and set the test voltage to 13 kV 23 kV
or 36 kV (25 kV max with the Calibrator SP) according to the maximum voltage of
the spark tester.
6. Use a digital voltmeter to measure the voltage on actual pin 15 and GND2 pin 16
of the connector "Potential free I / O"
7. Select the page 6 / 6 of the menu calibration and enter the measured voltage
value.
8. To finish the calibration and save the values, enter "1".
After pushing the button "Enter" the result of the calibration is displayed on the
input field for short duration:
– "OK" the calibration is passed
– "ERROR" the calibration failed due to too large deviation.
Verify if the procedure has been done correctly and calibrate again.
9. Verify the calibration: Set the test voltage to the two operating points used
above and measure the voltage on actual pin 15 and GND2 pin 16 of the
connector "Potential free I / O" with a digital voltmeter
10. Switch the test voltage off.
Spark Tester AST L 15A/25A/40A 12 ZUMBACH owned companies in Switzerland (H.Q.), Benelux, China, Czech Republic, France, Germany, 73/111
SPAT.010.5023.EN_20210827 India, Italy, Spain, Taiwan, United Kingdom and USA, plus agents and service in more than 40 countries.
6.7 CALIBRATION VIA INTERFACE
Refer to chapter 6.3 to 6.5 on how to do the calibration.
The adjustments described in this chapter should only be done in the rare events
where test voltage values are out of the required tolerance of 5 %.
To perform the adjustments, the interface must be the active control position, i.e.
– No control and display unit BAE 2 SP connected, or if connected, the internal
changeover switch of the BAE 2 SP must be in position D = display.
– The changeover switch in the rear of the electrode unit must be in position
"Interface"
– Activate the interface as active control position by transmitting the command
S006 1 via the interface.
74/114 12 ZUMBACH owned companies in Switzerland (H.Q.), Benelux, China, Czech Republic, France, Germany, Spark Tester AST L 15A/25A/40A
India, Italy, Spain, Taiwan, United Kingdom and USA, plus agents and service in more than 40 countries. 20210827_SPAT.010.5023.EN
6.7.2 Calibration of the analog input nominal
This signal is only available on electrode units with potential free inputs / outputs.
1. Apply a control voltage of 2Vdc to the input nominal pin 17 and GND2 pin 16 of
the connector "Potential free I / O" in the rear of the electrode unit.
Measure this control voltage with a digital voltmeter.
2. Enter the measured control voltage:
Calibration of the analog input voltage step 1 command S020 xx.xx
whereas xx.xx is the measured control voltage in volts.
3. Apply a control voltage of 9Vdc to the input nominal pin 17 and GND2 pin 16.
Measure this control voltage with a digital voltmeter.
4. Enter the measured control voltage:
Calibration of the analog input voltage step 2 command S022 xx.xx
whereas xx.xx is the measured control voltage in volts.
5. To finish the calibration and save the values, enter the following command:
Calibration of the analog input voltage step 3 command S024 1
6. Read the result of the calibration: Enter the command e718
Result:
– e718 0: The calibration is passed
– e718 1: Calibration error, the calibration failed due to too large deviation.
Verify if the procedure has been done correctly and calibrate again.
7. Verify the calibration: Set the control voltage to the two operating points used
above and measure the test voltage with the calibrator SP.
Spark Tester AST L 15A/25A/40A 12 ZUMBACH owned companies in Switzerland (H.Q.), Benelux, China, Czech Republic, France, Germany, 75/111
SPAT.010.5023.EN_20210827 India, Italy, Spain, Taiwan, United Kingdom and USA, plus agents and service in more than 40 countries.
7 REPAIRING
Instruct the repair personnel on the proper repair and the prevention of risks in
the repair of the electrode unit.
WARNING
Dangerous voltages inside. Be sure to disconnect the device from the power
supply before working inside the device: Pull the power plug! It is the respon-
sibility of qualified electricians to recognise the resulting dangers and to take
appropriate safety measures.
Chapter 7.3 contains a list of spare parts that can be replaced by the user.
▶ Our service and sales subsidiaries can of course also contacted by phone,
fax or email. The addresses are listed in chapter 1.2.
To replace the mains cord, use a cord that meets the requirements of IEC 60227
or IEC 60245, i.e. rated voltage at least 300 Vac, three wires with cross section at
least 1 mm2 and conductors coloured brown, blue and green-and-yellow, operating
temperature at least 70 °C.
76/114 12 ZUMBACH owned companies in Switzerland (H.Q.), Benelux, China, Czech Republic, France, Germany, Spark Tester AST L 15A/25A/40A
India, Italy, Spain, Taiwan, United Kingdom and USA, plus agents and service in more than 40 countries. 20210827_SPAT.010.5023.EN
7.3 TROUBLE-SHOOTING
In case of malfunction check the following points before contacting servicing:
Malfunction Cause
1 Electrode unit not powered • Mains cord not connected to mains
• Mains interrupted
• Fuses in the mains inlet blown
• Check if the green LED in the rear of the electrode unit
is blinking. If the LED is continuous on or off, return the
spark tester for repair.
2 • The green signalization • Check if the cover of the electrode unit is properly
lamp "Ready" on BAE 2 closed
SP is off • Test voltage not activated via emergency stop input
• Error message 300 via
interface "Spark tester not
ready"
3 Potential free output • Spark tester not powered
"spark tester enabled" not • Internal fault, e. g.:
activated The temperature inside the electrode unit is too high.
Do not operate the spark tester at ambient temperatures
higher than 50 °C or at direct exposure to sunlight or
other heat sources.
4 No high voltage on the • Electrode unit in rewind mode and test voltage
electrode switched off after detection of a fault
• Check if the cover of the electrode unit is properly
closed
• Test voltage not switched on
• Test voltage not activated via emergency stop input
• Electrode short-circuited
• Remove the product from the electrode. Inspect the
electrode and clean if dirty. Switch the test voltage off
and on when the electrode is empty.
• High voltage source defective. Return the spark tester
for repair.
5 Not possible to switch the Check if the internal changeover switch in the BAE 2 SP
test voltage on via push is in position C = Control.
button "Test voltage" on
BAE 2 SP
6 Not possible to switch the If a BAE 2 SP is connected, check if the internal
test voltage on via remote changeover switch in the BAE 2 SP is in position
interface D = Display.
7 No detection of faults or • Verify if both cable heads are earthed properly
faults detected where there • Verify if the test voltage applied corresponds to the
is no defect in the cable values given in chapter 5.3
• Use another value of the sensibility of the fault detector,
refer to chapter 3.9
8 The test voltage remains • Too high leakage currents: Product to be tested is
clearly below the setpoint conductive or wet.
value • Remove the product from the electrode. inspect the
electrode and clean if dirty. Switch the test voltage off
and on when the electrode is empty.
• High voltage source defective. Return the spark tester
for repair.
Spark Tester AST L 15A/25A/40A 12 ZUMBACH owned companies in Switzerland (H.Q.), Benelux, China, Czech Republic, France, Germany, 77/111
SPAT.010.5023.EN_20210827 India, Italy, Spain, Taiwan, United Kingdom and USA, plus agents and service in more than 40 countries.
7.4 LIST OF SPARE PARTS OF THE ELECTRODE UNIT Electrode unit
AST L 15A / 25A / 40A AST L 15A/25A/40A
Photocopy this page, enter the desired quantities, and mail it or fax it to one of the
Zumbach addresses in chapter 1.2 of this instruction manual.
When ordering spare parts, please make sure to always note the order number and
serial number from the technical label.
Order Serial
Nr.: Nr.:
Company ..............................................................
Name ..............................................................
Title ..............................................................
Adress ..............................................................
Phone ..............................................................
Fax ..............................................................
E-mail ..............................................................
Website www......................................................
7.4.1 Common spare parts for all AST L 15A / 25A / 40A electrode units
Number/ Order
Illust. Order number Description
unit qty
Mains plug
A10 200 0032 1
250 V / 10 Amp 70°, black for cable
78/114 12 ZUMBACH owned companies in Switzerland (H.Q.), Benelux, China, Czech Republic, France, Germany, Spark Tester AST L 15A/25A/40A
India, Italy, Spain, Taiwan, United Kingdom and USA, plus agents and service in more than 40 countries. 20210827_SPAT.010.5023.EN
7.4.2 Spare electrodes and component parts of electrodes
For servicing electrodes, it is possible to replace component parts only. Bead chains
are delivered as single piece and need to be cut in pieces of the required length.
Spark Tester AST L 15A/25A/40A 12 ZUMBACH owned companies in Switzerland (H.Q.), Benelux, China, Czech Republic, France, Germany, 79/111
SPAT.010.5023.EN_20210827 India, Italy, Spain, Taiwan, United Kingdom and USA, plus agents and service in more than 40 countries.
AST.15A.50.1000UL-x and AST.25A.50.1000UL-x
Order number AST.261.05991y and AST.262.05991y
80/114 12 ZUMBACH owned companies in Switzerland (H.Q.), Benelux, China, Czech Republic, France, Germany, Spark Tester AST L 15A/25A/40A
India, Italy, Spain, Taiwan, United Kingdom and USA, plus agents and service in more than 40 countries. 20210827_SPAT.010.5023.EN
AST.15A.90.300UL-x and AST.25A.90.300UL-x
Order number AST.261.09301y and AST.262.09301y
Spark Tester AST L 15A/25A/40A 12 ZUMBACH owned companies in Switzerland (H.Q.), Benelux, China, Czech Republic, France, Germany, 81/111
SPAT.010.5023.EN_20210827 India, Italy, Spain, Taiwan, United Kingdom and USA, plus agents and service in more than 40 countries.
8 DECOMMISSIONING / DISPOSAL
WARNING
Dangerous voltages inside. Be sure to disconnect the device from the power
supply before working inside the device: Pull the power plug! It is the respon-
sibility of qualified electricians to recognise the resulting dangers and to take
appropriate safety measures.
8.1 DECOMMISSIONING
The sparker can be removed from the line and disposed of without taking any additional
measures.
The disposal must be done in accordance with the directives on waste electrical and
electronic equipment (WEEE), i.e.:
– Separate collection of electrical and electronic equipment
– Return of the material according to national directives for recycling according to
national directives
82/114 12 ZUMBACH owned companies in Switzerland (H.Q.), Benelux, China, Czech Republic, France, Germany, Spark Tester AST L 15A/25A/40A
India, Italy, Spain, Taiwan, United Kingdom and USA, plus agents and service in more than 40 countries. 20210827_SPAT.010.5023.EN
9 SERVICE PORT
The Ethernet based service port can be used for the web visualisation to configure
and calibrate the spark tester.
If the spark tester is equipped with a control and display unit BAE 2 SP, the configurations
and calibration can be done with the BAE 2 SP.
To make settings via Ethernet based service port, the following equipment is needed:
– Laptop, PC or similar with Ethernet interface and terminal program that supports
TCP / IP
– Ethernet cable
2. After power up, connect an Ethernet cable to the laptop and the jack "Service" on
the rear panel of the spark tester.
Spark Tester AST L 15A/25A/40A 12 ZUMBACH owned companies in Switzerland (H.Q.), Benelux, China, Czech Republic, France, Germany, 83/111
SPAT.010.5023.EN_20210827 India, Italy, Spain, Taiwan, United Kingdom and USA, plus agents and service in more than 40 countries.
9.2 SETTING UP THE TERMINAL PROGRAM
By way of example, Tera Term is used as terminal program. Tera Term is the terminal
emulator for Microsoft Windows and supports TCP / IP connections.
This program is free software and can be downloaded from the following URL:
http://ttssh2.sourceforge.jp/
84/114 12 ZUMBACH owned companies in Switzerland (H.Q.), Benelux, China, Czech Republic, France, Germany, Spark Tester AST L 15A/25A/40A
India, Italy, Spain, Taiwan, United Kingdom and USA, plus agents and service in more than 40 countries. 20210827_SPAT.010.5023.EN
9.3 USING THE SERVICE PORT
5. Tera Term is now ready for entering commands and reading transmitted values.
Refer to the host protocol codes given in chapter 13.
An upper case (capital) letter is used for a download sequence, a lower case
letter is used for an upload sequence.
To perform active commands, the service port must be the active control position, i.e.
– No control and display unit BAE 2 SP connected, or if connected, the internal
changeover switch of the BAE 2 SP must be in position D = display.
– The changeover switch in the rear of the electrode unit must be in position
"Interface"
– Activate the service port as active control position by transmitting the command
S006 1 via service port.
This is a download command from terminal to the spark tester (write) and therefore
a capital letter must be used.
Use the enter key to terminate the commands.
6. After using the service port, the LAN connection of the laptop must again be set
to obtain the IP address automatically. Make the reverse settings as described in
chapter 9.1.
Spark Tester AST L 15A/25A/40A 12 ZUMBACH owned companies in Switzerland (H.Q.), Benelux, China, Czech Republic, France, Germany, 85/111
SPAT.010.5023.EN_20210827 India, Italy, Spain, Taiwan, United Kingdom and USA, plus agents and service in more than 40 countries.
10 RS INTERFACE
RS-485 Connection
T+/R+ 1 T+/R+
T-/R- 6 T-/R-
R+ 4 R+
R- 9 R-
GND 5 GND
RS-422 Connection
T+ 1 T+
T- 6 T-
R+ 4 R+
R- 9 R-
GND 5 GND
RS-232 Connection
TxD 3 TxD
RxD 2 RxD
GND 5 GND
86/114 12 ZUMBACH owned companies in Switzerland (H.Q.), Benelux, China, Czech Republic, France, Germany, Spark Tester AST L 15A/25A/40A
India, Italy, Spain, Taiwan, United Kingdom and USA, plus agents and service in more than 40 countries. 20210827_SPAT.010.5023.EN
Electrical interface
The RS interface lines are electrically isolated from any circuit. The signal ground and
cable shield must be connected at the both extremities.
Termination impedance: The factory setting is not connected.
When the spark tester is located at the end of the transmission line (ANSI X3.28
network), the termination resistors should be connected (switch ON / OFF beside the
connector).
Watchdog
For safety reason, a watchdog can be activated to supervise the presence of the
remote link by means of a time out in the range of 1 to 99 seconds, see up / download
code s008. The test voltage is switched off if the spark tester is waiting for a message
during more than the time given and when the watchdog is active.
Factory setting: Watchdog deactivated.
ASCII protocol
This communication protocol is a simple ASCII protocol. It is the standard Zumbach
ASCII protocol implemented in almost all Zumbach electronics units. The protocol is
well suited for point to point connections. Some of the advantages of this protocol are:
A simple terminal or terminal program may be used (no block check character must
be calculated). It can be used by service personnel to trouble shoot or inspect the
system without special software.
It's very easy to implement on a Host computer. Debugging of the communication link
is easy. Automatic output of measuring data without request from Master is possible.
Multidrop protocol
The implemented protocol corresponds to the ANSI standard ANSI X 3.28 rev. 1976,
subcategories 2.5 and A4. It is a simple and safe Fieldbus Master-Slave protocol.
Spark Tester AST L 15A/25A/40A 12 ZUMBACH owned companies in Switzerland (H.Q.), Benelux, China, Czech Republic, France, Germany, 87/111
SPAT.010.5023.EN_20210827 India, Italy, Spain, Taiwan, United Kingdom and USA, plus agents and service in more than 40 countries.
10.2 COMMUNICATION SYNTAX
For the purposes of the following explanations the names of single non printable ASCII
characters are indicated by placing the name of the character between "["and "]". The
following non printable characters are used in the descriptions:
Command Format
A command tells the Slave to either supply data to, or accept data from the Host
computer.
A command is identified in the following explanations by <CMD>.
Group
Transmitted parameters and data are divided into groups. Each group is
designated with a letter.
Letter
An upper case (capital) letter is used for a download sequence.
lower case letter is used for an upload sequence.
Number
Each member of a group is designated with a three digit number. The numbers range
from 000 to 999. Leading zeros are mandatory.
Data Format
The data may be a value, a string, a selection or nothing at all. Data is identified in
the following explanations as <DATA>.
Value
A value consists only of numbers, sign prefixes, and a decimal point.
String
A string is a series of characters. Any printable ASCII character is allowed.
The maximum length of a downloaded string depends on the definition.
88/114 12 ZUMBACH owned companies in Switzerland (H.Q.), Benelux, China, Czech Republic, France, Germany, Spark Tester AST L 15A/25A/40A
India, Italy, Spain, Taiwan, United Kingdom and USA, plus agents and service in more than 40 countries. 20210827_SPAT.010.5023.EN
Selection
A selection from a list can be made by sending a number that corresponds to the
placement of the desired selection in the list. The first selection is 0.
Multiple (Selection)
A multiple selection is used when more than one selection may be selected at one time.
Example
e720 Hardware Self test Alarm Multiple R
0 = No alarm
300 = Spark tester not ready
303 = Spark tester voltage out of tolerance
Function
Does not have a value (although any value must be downloaded to conform with the
protocol). Triggers an action.
Spark Tester AST L 15A/25A/40A 12 ZUMBACH owned companies in Switzerland (H.Q.), Benelux, China, Czech Republic, France, Germany, 89/111
SPAT.010.5023.EN_20210827 India, Italy, Spain, Taiwan, United Kingdom and USA, plus agents and service in more than 40 countries.
10.4 ZUMBACH ASCII PROTOCOL
Refer to chapter 13 for the list of parameters and results.
10.4.1 Upload
Masters request
<CMD> Four character sequence, C1, C2, C3, C4, representing the parameter
code.
For example, the Slave software version number is requested with the
<CMD> of 'a'‚9' ‚9' ‚0' (lower case letter!).
[CR] ASCII carriage return terminates the request.
[LF] ASCII Line Feed. (Optional) Ignored by the Slave.
<CMD> Echo of the four character sequence representing the parameter code.
[SP] ASCII space character.
<DATA> A variable number of characters (D1, D2, D3, ... Dn), representing the
value requested.
[CR] ASCII carriage return. Indicates the end of the data.
[LF] ASCII Line Feed. (Note: The output of this character may be disabled in
some devices, to reduce the telegram length. Refer to manual)
90/114 12 ZUMBACH owned companies in Switzerland (H.Q.), Benelux, China, Czech Republic, France, Germany, Spark Tester AST L 15A/25A/40A
India, Italy, Spain, Taiwan, United Kingdom and USA, plus agents and service in more than 40 countries. 20210827_SPAT.010.5023.EN
10.5 ANSI X3.28-2.5-A4 STANDARD PROTOCOL
10.5.1 Upload
[NAK]
[EOT]
(Wrong <CMD> or no Message)
Masters request
[EOT] ASCII control character. Resets the communication link passing control
back to the control station (Master). Alerts all devices on the link to
examine the next four characters to see if they correspond with their
group / unit address identifier.
<ADDR> Four character sequence representing the address of the instrument.
The address is broken down into a most significant digit (MSD) and a
least significant digit (LSD). Each digit is repeated for security.
The format of the address, is MSD MSD LSD LSD. For example,
the "<ADDR>" for device number 10 is '1' '1' '0' '0'.
<CMD> Four character sequence, C1, C2, C3, C4, representing the parameter
code. For example, the Slave software version number is requested with
the <CMD> of 'a' '9' '9' '0' (lower case letter!).
[ENQ] ASCII control character. Indicates the end of an inquire message.
[EOT] ASCII control character. If the <CMD> is not recognized or if the Slave
has no value to send, the Slave will send an [EOT] to return control to the
control station (your PCB).
or
[STX] ASCII control character indicating the Start of Text.
<CMD> Echo of the four character sequence representing the parameter code.
[SP] ASCII space character.
<DATA> A variable number of characters (D1, D2, D3, ... Dn), representing the
value requested.
[ETX] ASCII control character. Indicates the end of the message.
[BCC] Block Check Character. Generated by taking the Exclusive OR of the
values of the ASCII characters following and excluding [STX] up to and
including [ETX].
i.e.: [BCC] = C1 XOR C2 XOR C3 XOR C4 XOR SP XOR D1 XOR D2
XOR D3 XOR D4...XOR Dn XOR ETX.
Spark Tester AST L 15A/25A/40A 12 ZUMBACH owned companies in Switzerland (H.Q.), Benelux, China, Czech Republic, France, Germany, 91/111
SPAT.010.5023.EN_20210827 India, Italy, Spain, Taiwan, United Kingdom and USA, plus agents and service in more than 40 countries.
10.5.2 Download
[ETO] <ADD> [STX] <CDM> [SP] <DATA> [EXT] <BCC> No reply [EOT]
[ACK]
[NAK]
Masters Message
[EOT] ASCII control character. Resets the communication link passing control
back to the control station (your PCB). Alerts all devices on the link to
examine the next four characters to see if they correspond with their
group / unit address identifier.
<ADDR> Four character sequence representing the address of the instrument.
The address is broken down into a most significant digit (MSD) and
a least significant digit (LSD). Each digit is repeated for security.
The format of the address, is MSD MSD LSD LSD.
For example, the "<ADDR>" for device number 10 is '1' '1' '0' '0'.
[STX] ASCII control character indicating the Start of Text.
<CMD> Four character sequence, C1, C2, C3, C4, representing the parameter
code. For example, the diameter averaging time is downloaded with the
<CMD> of 'B' '0' '3' '0' (upper case letter!).
[SP] ASCII space character.
<DATA> A variable number of characters (D1, D2, D3, ... Dn), representing the
value downloaded.
ETX] ASCII control character. Indicates the end of the message.
[BCC] Block Check Character. Generated by taking the Exclusive OR of the
values of the ASCII characters following and excluding [STX] up to and
including [ETX].
92/114 12 ZUMBACH owned companies in Switzerland (H.Q.), Benelux, China, Czech Republic, France, Germany, Spark Tester AST L 15A/25A/40A
India, Italy, Spain, Taiwan, United Kingdom and USA, plus agents and service in more than 40 countries. 20210827_SPAT.010.5023.EN
Response from Slave
[ACK] ASCII control character. Used to indicate a successful receipt of a
message.
or
[NAK] ASCII control character. Used to indicate an unsuccessful receipt of a
message. This may cause the Master to repeat the transmission.
Spark Tester AST L 15A/25A/40A 12 ZUMBACH owned companies in Switzerland (H.Q.), Benelux, China, Czech Republic, France, Germany, 93/111
SPAT.010.5023.EN_20210827 India, Italy, Spain, Taiwan, United Kingdom and USA, plus agents and service in more than 40 countries.
11 ETHERNET
94/114 12 ZUMBACH owned companies in Switzerland (H.Q.), Benelux, China, Czech Republic, France, Germany, Spark Tester AST L 15A/25A/40A
India, Italy, Spain, Taiwan, United Kingdom and USA, plus agents and service in more than 40 countries. 20210827_SPAT.010.5023.EN
12 PROFINET
Spark Tester AST L 15A/25A/40A 12 ZUMBACH owned companies in Switzerland (H.Q.), Benelux, China, Czech Republic, France, Germany, 95/111
SPAT.010.5023.EN_20210827 India, Italy, Spain, Taiwan, United Kingdom and USA, plus agents and service in more than 40 countries.
13 LIST OF PARAMETERS AND RESULTS
The following tables list all parameters for the Host protocol, ODAC protocol, Profibus
and Profinet protocol.
Profibus
ODAC Host Description Range of values
Profinet
Output interval for service and host
0 -> 0.04 s
ports (or update rate for Profibus).
- CA a138 0.04 - 99.99 s
Factory setting 0.1 s.
xx.xx s
Fieldbus: Factory setting 0.04 s
IP address of the service Ethernet
- SL a930 interface xxx.xxx.xxx.xxx
This command will restart the system
Subnet mask of the service Ethernet
- SM a931 interface xxx.xxx.xxx.xxx
This command will restart the system
Gateway address of the service
- SO a932 Ethernet interface xxx.xxx.xxx.xxx
This command will restart the system
IP address of the Ethernet host
- IL a940 interface xxx.xxx.xxx.xxx
This command will restart the system
Subnet mask of the Ethernet host
- IM a941 interface xxx.xxx.xxx.xxx
This command will restart the system
Gateway address of the Ethernet host
- IO a942 interface xxx.xxx.xxx.xxx
This command will restart the system
2 -> Standard
masterslave
(all parameters
on request only)
- - a945 Host port output mode:
7 -> Automatic output
mode for USYS
(see grouped
message d182)
3 -> 1200 baud
4 -> 2400 baud
5 -> 4800 baud
6 -> 9600 baud
- AM a970 Host port: Baud rate
7 -> 19200 baud
8 -> 38400 baud
9 -> 57600 baud
10 -> 115200 baud
1 -> 7 bits
- AP a971 Host port: Bits per character
2 -> 8 bits
0 -> 1 Stop bit
- AO a972 Host port: Number of stop bits
1 -> 2 Stop bit
96/114 12 ZUMBACH owned companies in Switzerland (H.Q.), Benelux, China, Czech Republic, France, Germany, Spark Tester AST L 15A/25A/40A
India, Italy, Spain, Taiwan, United Kingdom and USA, plus agents and service in more than 40 countries. 20210827_SPAT.010.5023.EN
Profibus
ODAC Host Description Range of values
Profinet
0 -> Even
- AN a973 Host port: Parity 1 -> Odd
2 -> No parity check
Read Profibus address switches.
Returns the actual setting of the
- SC a978 0 - 126
Profibus address switches
(only for version with Profibus)
Write Profibus address.
- SD a979 Select Profibus address 1 - 125
(only for version with Profibus)
0 -> RS-485, half
duplex, with RTS
1 -> RS-422,
full duplex,
- SB a983 Host port: Transmission mode
RTS on zero
2 -> RS-232,
full duplex,
RTS on zero
0 -> ODAC protocol
- SP a986 Host port: Protocol selection
1 -> Host protocol
0 -> no length counter
Operating mode of length counter
485 SQ a987 1 -> length counter
Factory setting: No length counter
in use
CP software name and corresponding
- - a989
GSD file version
- ZA a990 CP software name
- ZB a991 CP software date
CP printed circuit board assembly
- ZC a992
version
Initialisation
- AZ a995 0 = nil 0/1
1 = for version with host protocol
- ZI a996 Actual CPU charge in % 0 - 100
- ZP a998 Software version power part xxxx
- ZQ a999 Hardware version power part xxxx
Profibus
ODAC Host Description Range of values
Profinet
Alarm prolongation:
0.003 - 9.9
Range 0.003 - 9.9s, Factory setting:
46 BT b100 Fieldbus:
0.7s
3 - 9900
Fieldbus: Alarm prolongation in ms
Calibration for the length counter: x.xxxxx m /
- SR b310 Distance between two pulses. x.xxxxx inch
Factory setting: 1.00000
Measuring unit for the length detection 0 -> metric m
493 SY b400
Factory setting: metric 1 -> imperial feet
Spark Tester AST L 15A/25A/40A 12 ZUMBACH owned companies in Switzerland (H.Q.), Benelux, China, Czech Republic, France, Germany, 97/111
SPAT.010.5023.EN_20210827 India, Italy, Spain, Taiwan, United Kingdom and USA, plus agents and service in more than 40 countries.
13.3 PARAMETERS GROUP C – PRODUCT PARAMETERS
The parameters of group C cannot be modified if a control and display unit BAE 2
SP is connected and in mode C = Control or if the changeover switch is in position
"Potential free I/O". In this case, these parameters are read only.
Profibus
ODAC Host Description Range of values
Profinet
Output voltage setpoint in kV:
xx.xx kV
DST 10: 1 to 10 kV, factory setting 5 kV
DST 28A: 1 to 28 kV, factory setting 5 kV
AST H 15A: 0.5 to 15 kV, factory setting 4 kV
42 BP c780
AST L 15A: 0.5 to 15 kV, factory setting 3 kV
AST L 25A: 0.5 to 25 kV, factory setting 3 kV
Fieldbus:
AST L 40A: 0.5 to 40 kV, factory setting 3 kV
xxxxx V
Fieldbus: Output voltage setpoint in volts
Test frequency (AST L xxA only):
78 CZ c782 xxx
Range 50 - 120 Hz, factory setting 50 Hz
Voltage tolerance in kV: xx.xx kV
43 BQ c786 Range 0 - 40 kV, factory setting 2 kV Fieldbus:
Fieldbus: Voltage tolerance in volts xxxxx V
Fault detector sensitivity in percent voltage
44 BR c788 drop of the output voltage setpoint. 10 - 40
Factory setting 10 % (highest sensitivity)
Minimum duration of bare patch event in 0.1 - 9.9
seconds.
45 BS c790 Range 0.1 s to 9.9 s, factory setting 1 s
Fieldbus: Minimum duration of bare patch Fieldbus:
event in milliseconds 100 - 9900
Profibus
ODAC Host Description Range of values
Profinet
xxxxx.x m / xxxxxx ft
actual length in m or ft
96 DR d000
Fieldbus: Actual length in cm or ft
Fieldbus: xxxxxxx cm
Measured output voltage in kV xx.xx kV
79 DA d042 Fieldbus: Mesured output
voltage in volts Fieldbus: xxxxx V
322 MJ d070 Spark tester total fault counter 0 - 9999 faults
323 MK d072 Spark tester bare patch counter 0 - 9999 bare patch events
Format: d182[SP][v1][SP][v2]
[SP][v3][SP][v4][CR][LF]
Automatic output for each fault v1: e720
- - d182
(see mode selection a945) v2: d042
v3: d070
v4: d072
Length counter value of the last xxxxx.x m or xxxxx ft
fault in m or ft.
102 DX d184 Value 0 for no fault
Fieldbus: Length counter value of
the last fault in cm Fieldbus: xxxxxxx cm or ft
98/114 12 ZUMBACH owned companies in Switzerland (H.Q.), Benelux, China, Czech Republic, France, Germany, Spark Tester AST L 15A/25A/40A
India, Italy, Spain, Taiwan, United Kingdom and USA, plus agents and service in more than 40 countries. 20210827_SPAT.010.5023.EN
Profibus
ODAC Host Description Range of values
Profinet
Length counter value of the 20 times xxxxx.x m or
last 20 faults in m or ft. xxxxx ft
- DY d185 Fixed data format with 20
numbers, empty if no fault
Fieldbus: 0 Fieldbus: 0
Profibus
ODAC Host Description Range of values
Profinet
Calibration error 0 = no error
- EA e718
1 = calibration error
0 -> TV off / no alarm
300 -> TV off / spark tester not ready
301 -> TV off / overtemperature
Error and status 302 -> TV off / spark tester alarm
messages. 303 -> TV off / test voltage out of tolerance
The status 304 -> TV off / overload (AST L xxA only)
on / off of the 305 -> TV off / Mains out of operating range
test voltage is (AST L xxA only)
80 EB e720
combined in
this message by 1000 -> TV on / no alarm
adding 1000 if 1301 -> TV on / overtemperature
the test voltage 1302 -> TV on / spark tester alarm
is on 1303 -> TV on / test voltage out of tolerance
1304 -> TV on / overload (AST L xxA only)
1305 -> TV on / Mains out of operating range
(AST L xxA only)
Profibus
ODAC Host Description Range of values
Profinet
Reset fault counter
0 -> counter running
72 1) CT f020 See also at Profibus device
1 -> counter reset to zero
specific parameters
Test voltage on / off
0 -> turn test voltage off
77 1) CY f710 See also at Profibus device
1 -> turn test voltage on
specific parameters
1)
These two parameters are included into the device command and control word
(see parameter1000).
Spark Tester AST L 15A/25A/40A 12 ZUMBACH owned companies in Switzerland (H.Q.), Benelux, China, Czech Republic, France, Germany, 99/111
SPAT.010.5023.EN_20210827 India, Italy, Spain, Taiwan, United Kingdom and USA, plus agents and service in more than 40 countries.
13.7 PARAMETERS GROUP S – MEASUREMENT HEAD AND CALIBRATION
The parameters s000, s002 and s004 cannot be modified by the user. These
parameters are read only.
Profibus
ODAC Host Description Range of values
Profinet
0 -> AST 15 (RI)
1 -> AST 25 (RI)
2 -> AST 40 (RI)
3 -> AST 15 HF
4 -> DST 10
5 -> DST 25
6 -> IST SP20
Electrode type: 7 -> DST SP20
665 ZO s000
This parameter is read only. 8 -> SP10 simul (SP20)
9 -> AST 15 HF (SP20)
10 -> DST 28A
11 -> AST H 15A
12 -> AST L 15A
13 -> AST L 25A
14 -> AST L 40A
15 -> DST 10
0 -> none
Indicates the active control 1 -> BAE 2 SP
444 RB s002 position. This parameter is 2 -> Host port
read only. 3 -> Service port
4 -> Potential free I/O
0 -> BAE not connected
Status of the control and display 1 -> BAE connected and
- RC s004 unit BAE 2 SP active control position
This parameter is read only. 2 -> BAE connected and
in display mode
Select the active control position:
This parameter can only be used
0 -> another interface is the
if the changeover switch is in posi-
active control position
443 RA s006 tion "Interface" and if no control
1 -> this interface is the
and display unit BAE 2 SP is con-
active control position
nected or the BAE 2 SP is in mode
display only.
Host communication watchdog 0 -> watchdog is off
- RD s008 Factory setting: Watchdog off 1 - 99 -> watchdog is on
with time in xx seconds
Calibration of the measured test
voltage, step 1: xx.xx kV
Enter the external measured
- RF s010
voltage 1 in kV
Fieldbus: External measured volt- Fieldbus: xxxxx V
age 1 in volts
100/114 12 ZUMBACH owned companies in Switzerland (H.Q.), Benelux, China, Czech Republic, France, Germany, Spark Tester AST L 15A/25A/40A
India, Italy, Spain, Taiwan, United Kingdom and USA, plus agents and service in more than 40 countries. 20210827_SPAT.010.5023.EN
Profibus Range of
ODAC Host Description
Profinet values
xx.xx kV
Calibration of the measured test voltage, step 2:
Enter the external measured
- RG s012
voltage 2 in kV
Fieldbus:
Fieldbus: External measured voltage 2 in volts
xxxxx V
Calibration of the measured test voltage, step 3: 1 ->
- RH s014
Accomplish calibration and store values accomplish
Calibration of the analog input voltage, step 1: xx.xx V
Enter the external measured voltage 1 in volts
- RI s020
Fieldbus: Enter the external measured voltage 1 Fieldbus:
in millivolts xxxxx mV
Calibration of the analog input voltage, step 2: xx.xx V
Enter the external measured voltage 2 in volts
- RJ s022
Fieldbus: Enter the external measured voltage 2 Fieldbus:
in millivolts xxxxx mV
Calibration of the analog input voltage, step 3: 1 ->
- RK s024
Accomplish calibration and store values accomplish
Calibration of the analog output voltage
xx.xx V
step 1:
- RL s030 Enter the external measured voltage 1 in volts
Fieldbus:
Fieldbus: Enter the external measured voltage 1
xxxxx mV
in millivolts
Calibration of the analog output voltage, step 2: xx.xx V
Enter the external measured voltage 2 in volts
- RM s032
Fieldbus: Enter the external measured voltage 2 Fieldbus:
in millivolts xxxxx mV
Calibration of the analog output voltage, step 3: 1 ->
- RN s034
Accomplish calibration and store values accomplish
Spark Tester AST L 15A/25A/40A 12 ZUMBACH owned companies in Switzerland (H.Q.), Benelux, China, Czech Republic, France, Germany, 101/111
SPAT.010.5023.EN_20210827 India, Italy, Spain, Taiwan, United Kingdom and USA, plus agents and service in more than 40 countries.
13.9 PROFIBUS AND PROFINET SPECIFIC PARAMETERS
102/114 12 ZUMBACH owned companies in Switzerland (H.Q.), Benelux, China, Czech Republic, France, Germany, Spark Tester AST L 15A/25A/40A
India, Italy, Spain, Taiwan, United Kingdom and USA, plus agents and service in more than 40 countries. 20210827_SPAT.010.5023.EN
14 WEB VISUALISATION
Article-No.: VISU.001.01XXX
Spark Tester AST L 15A/25A/40A 12 ZUMBACH owned companies in Switzerland (H.Q.), Benelux, China, Czech Republic, France, Germany, 103/111
SPAT.010.5023.EN_20210830 India, Italy, Spain, Taiwan, United Kingdom and USA, plus agents and service in more than 40 countries.
14.3 USING AND DISPLAYING MENUS
The layout of the pages is the same when using a VISU-Touch or when opening a
page in a web browser.
Confirmation key
Delete backwards
Enter/return
104/114 12 ZUMBACH owned companies in Switzerland (H.Q.), Benelux, China, Czech Republic, France, Germany, Spark Tester AST L 15A/25A/40A
India, Italy, Spain, Taiwan, United Kingdom and USA, plus agents and service in more than 40 countries. 20210827_SPAT.010.5023.EN
14.3.1 Main page
The main page displays the test voltage value, the total number of faults, the number
of pinholes and the bare platches. The field with the test voltage value is coloured red
when the voltage is zero and yellow when the high voltage is switched on.
Spark Tester AST L 15A/25A/40A 12 ZUMBACH owned companies in Switzerland (H.Q.), Benelux, China, Czech Republic, France, Germany, 105/111
SPAT.010.5023.EN_20210827 India, Italy, Spain, Taiwan, United Kingdom and USA, plus agents and service in more than 40 countries.
Navigation in windows
106/114 12 ZUMBACH owned companies in Switzerland (H.Q.), Benelux, China, Czech Republic, France, Germany, Spark Tester AST L 15A/25A/40A
India, Italy, Spain, Taiwan, United Kingdom and USA, plus agents and service in more than 40 countries. 20210827_SPAT.010.5023.EN
14.3.2 Settings page
To access the settings page, press the setting button on the main page:
Spark Tester AST L 15A/25A/40A 12 ZUMBACH owned companies in Switzerland (H.Q.), Benelux, China, Czech Republic, France, Germany, 107/111
SPAT.010.5023.EN_20210827 India, Italy, Spain, Taiwan, United Kingdom and USA, plus agents and service in more than 40 countries.
– Information about the spark tester will be displayed, such as electrode type or
software version.
– Calibration, to calibrate the spark tester. Access to the menu is protected by
password 954728.
– Fault positions displays a list with the position of each fault. For the list to be
created, the spark tester must be equipped with an encoder.
– Length sensor that allows you to activate or deactivate an encoder to measure
the fault position. Access to the menu is protected by password 954728.
– Access right that allows you to activate the protection of certain menus with
a password and to change the password. Access to the menu is protected by
password 954728.
– Terminal enabling communication with the spark tester via the Ethernet service
port. Only the ODAC protocol is supported. Access to the menu is protected by
password 954728.
108/114 12 ZUMBACH owned companies in Switzerland (H.Q.), Benelux, China, Czech Republic, France, Germany, Spark Tester AST L 15A/25A/40A
India, Italy, Spain, Taiwan, United Kingdom and USA, plus agents and service in more than 40 countries. 20210827_SPAT.010.5023.EN
15 INDEX
A
Activation of control positions..........................................................................................................................30
Addresses – The ZUMBACH Group..................................................................................................................8
ANSI X3.28-2.5-A4 standard protocol.............................................................................................................91
C
Calibration form for spark tester......................................................................................................................69
Calibration of spark testers..............................................................................................................................67
Calibration of the analog input nominal.....................................................................................................71 ,75
Calibration of the analog output actual......................................................................................................72, 75
Calibration of the test voltage....................................................................................................................70, 74
Calibration via Interface...................................................................................................................................74
Calibration with control and display unit BAE 2 SP......................................................................................... 70
Cleaning of the electrode................................................................................................................................56
Common spare parts for all AST L 15A / 25A / 40A electrode units................................................................... 78
Communication syntax....................................................................................................................................88
Components of the AST L 15A / 25A / 40A spark tester.................................................................................... 19
Conditions applying to spare parts..................................................................................................................76
Configuration menu of the control and display unit BAE 2 SP........................................................................ 40
Connections to the electrode unit....................................................................................................................34
Connections to the spark tester.......................................................................................................................34
Connection to mains........................................................................................................................................35
Control and display unit BAE 2 SP..................................................................................................................20
Control spark testers with control and display unit BAE 2 SP......................................................................... 61
Correct earthing of the spark tester.................................................................................................................36
D
Data and parameter access............................................................................................................................89
Dear customer...................................................................................................................................................7
Decommissioning............................................................................................................................................82
Decommissioning / Disposal............................................................................................................................82
Defined only for ODAC protocol....................................................................................................................101
Dimensional drawing AST.xxA.50 and AST.xxA.90......................................................................................... 24
Dimensional drawing AST.xxA.250..................................................................................................................25
Dimensional drawing BAE 2 SP......................................................................................................................21
Download........................................................................................................................................................92
E
Earthing of the product to be tested................................................................................................................56
Electrode length and test frequency................................................................................................................27
Electrode unit..................................................................................................................................................22
EMC.................................................................................................................................................................17
Emergency stop connector..............................................................................................................................42
Encoder...........................................................................................................................................................44
Ethernet...........................................................................................................................................................94
EU Declaration of conformity (Copy)...............................................................................................................12
Extruding and rewind mode.............................................................................................................................30
F
Fault detection.................................................................................................................................................28
Fire hazard due to deposits and water in the electrode unit ........................................................................... 16
Front panel of the control and display unit BAE 2 SP...................................................................................... 58
Spark Tester AST L 15A/25A/40A 12 ZUMBACH owned companies in Switzerland (H.Q.), Benelux, China, Czech Republic, France, Germany, 109/111
SPAT.010.5023.EN_20210827 India, Italy, Spain, Taiwan, United Kingdom and USA, plus agents and service in more than 40 countries.
G
General definitions..........................................................................................................................................88
General disposal.............................................................................................................................................82
H
High voltage....................................................................................................................................................15
I
If you run into problems in your application..................................................................................................... 57
index..............................................................................................................................................................109
Inspection of goods upon arrival.......................................................................................................................7
Installation.......................................................................................................................................................32
Instruction for lifting and carrying....................................................................................................................32
Introduction........................................................................................................................................................7
L
List of parameters and results.........................................................................................................................96
List of spare parts of the electrode unitAST L 15A / 25A / 40A.......................................................................... 78
Local display of a page with a web browser.................................................................................................. 103
Local display with a VISU-Touch...................................................................................................................103
Location of the spark tester.............................................................................................................................32
M
Main page......................................................................................................................................................105
maintenance....................................................................................................................................................66
Mounting instructions......................................................................................................................................33
Mounting the control and display unit BAE 2 SP............................................................................................. 35
O
Operating instructions.....................................................................................................................................56
Operating mode of the control and display unit BAE 2 SP.............................................................................. 39
Operating spark testers with potential free I / O............................................................................................... 63
Operating spark testers with Profibus DP or profinet host interface ............................................................... 65
Operating spark testers with RS or Ethernet host interface............................................................................ 64
Ozone..............................................................................................................................................................16
P
Parameters Group A – System........................................................................................................................96
Parameters Group B – Line parameters.........................................................................................................97
Parameters Group C – Product parameters.................................................................................................... 98
Parameters Group D – Measurements...........................................................................................................98
Parameters Group E – Alarm messages and device status............................................................................ 99
Parameters Group F – Control functions......................................................................................................... 99
Parameters Group S – Measurement head and calibration.......................................................................... 100
Potential free analog / digital input / output....................................................................................................... 47
Production line to manufacture cables and wires............................................................................................ 18
Profibus and Profinet specific parameters..................................................................................................... 102
Profinet............................................................................................................................................................95
Prohibited use.................................................................................................................................................14
Protection against ozone ................................................................................................................................55
110/114 12 ZUMBACH owned companies in Switzerland (H.Q.), Benelux, China, Czech Republic, France, Germany, Spark Tester AST L 15A/25A/40A
India, Italy, Spain, Taiwan, United Kingdom and USA, plus agents and service in more than 40 countries. 20210827_SPAT.010.5023.EN
R
Regular maintenance......................................................................................................................................66
Repairing.........................................................................................................................................................76
Requirements for UL Certification of wire and cable products ....................................................................... 27
Residual risk....................................................................................................................................................15
Return for repairs............................................................................................................................................76
Risks and transportation....................................................................................................................................7
RS interface.....................................................................................................................................................86
S
Safety..............................................................................................................................................................13
Safety check of the spark tester......................................................................................................................67
Safety measures in the unit.............................................................................................................................13
Serial link.........................................................................................................................................................86
Service port.....................................................................................................................................................83
Settings and user interfaces............................................................................................................................38
Settings page................................................................................................................................................107
Setting up the Ethernet interface.....................................................................................................................51
Setting up the laptop.......................................................................................................................................83
Setting up the Profinet interface......................................................................................................................54
Setting up the Service Ethernet interface........................................................................................................ 46
Setting up the terminal program......................................................................................................................84
Setting up the user configuration for Profibus DP interface............................................................................. 52
Setting up the user configuration for RS host interface................................................................................... 50
Spare electrodes and component parts of electrodes..................................................................................... 79
Spark tester calibrator.....................................................................................................................................68
Spark test principle..........................................................................................................................................18
Spark test standards applying to AST L 15A / 25A / 40A spark testers............................................................. 27
Symbols.............................................................................................................................................................9
System overview.............................................................................................................................................18
T
Technical data.................................................................................................................................................26
Technical description.......................................................................................................................................18
Test voltage.....................................................................................................................................................57
Trouble-shooting..............................................................................................................................................77
U
Upload.......................................................................................................................................................90, 91
Use according to destination...........................................................................................................................14
Using and displaying menus.........................................................................................................................104
Using the control and display unit BAE 2 SP as local display......................................................................... 63
Using the service port......................................................................................................................................85
Using the spark tester with control and display unit BAE 2 SP....................................................................... 58
W
Warranty............................................................................................................................................................7
Web Visualisation..........................................................................................................................................103
Z
ZUMBACH ASCII protocol...............................................................................................................................90
ZUMBACH Product overview..........................................................................................................................10
Spark Tester AST L 15A/25A/40A 12 ZUMBACH owned companies in Switzerland (H.Q.), Benelux, China, Czech Republic, France, Germany, 111/111
SPAT.010.5023.EN_20210827 India, Italy, Spain, Taiwan, United Kingdom and USA, plus agents and service in more than 40 countries.