Академический Документы
Профессиональный Документы
Культура Документы
Guidelines
Reference Data COOPER POWER
SERIES
Effective October 2021
TD900001EN Supersedes January 2019
*Refer to Occupational Safety & Health Administration (OSHA) for complete listing of NRTLs.
2 www.eaton.com/cooperpowerseries 2020 code options for the installation of listed less-flammable liquid-filled transformers
Reference Data TD900001EN
Effective October 2021
450.23 Less-flammable liquid-insulated transformers Oil insulated transformers installed indoors shall be installed in a
Transformers insulated with listed less-flammable liquids that vault constructed as specified in Part III of this article.
have a fire point of not less than 300°C shall be permitted to be Exception No. 1: Where the total capacity does not exceed 112½
installed in accordance with 450.23(A) or 450.23(B). kVA, the vault specified in Part III of this article shall be permitted
Table 1. NEC section 450.23 requirements – (A) indoor to be constructed of reinforced concrete that is less than 100
installation. Indoor installations shall be permitted in accordance mm (4 in.) thick.
with one of the following: Exception No. 2: Where the nominal voltage does not exceed
(1) In Type I or Type II buildings*, in areas where all of the 1000 volts, a vault shall not be required if suitable arrangements
following requirements are met: are made to prevent a transformer oil fire from igniting other
materials and the total capacity in one location does not exceed
a. The transformer is rated 35,000 volts or less 10 kVA in a section of the building classified as combustible
or 75 kVA where the surrounding structure is classified as fire-
b. No combustible materials are stored
resistant construction.
c. A liquid confinement area is provided
Exception No. 3: Electric furnace transformers that have a
d. The installation complies with all the restrictions provided for total rating not exceeding 75 kVA shall be permitted to be
in the listing of the liquid installed without a vault in a building or room of fire-resistant
construction, provided suitable arrangements are made
Informational note: Such restrictions may include, but are not to prevent a transformer oil fire from spreading to other
limited to: maximum pressure of the tank, use of a pressure combustible material.
relief valve, appropriate fuse types and proper sizing of
overcurrent protection. Exception No. 4: A transformer that has a total rating not
exceeding 75 kVA and a supply voltage of 1000 volts or less that
(2) With an automatic fire extinguishing system and a liquid is an integral part of charged-particle-accelerating equipment
confinement area, provided the transformer is rated 35,000 shall be permitted to be install without a vault in a building or
volts or less room of non-combustible or fire-resistant construction, providing
(3) In accordance with 450.26** suitable arrangements are made to prevent a transformer oil fire
from spreading to other combustible material.
Type I and Type II building definition
Exception No. 5: Transformers shall be permitted to be installed
Type I – Fire-resistive in a detached building that does not comply with Part III of this
article if neither the building nor its content present a fire hazard
This concrete and steel structure, called fire resistive when first
to any other building or property, and if the building is used only
built at the turn of the century, is supposed to confine a fire by
in supplying electric service and the interior is accessible only to
its construction. This type of construction in which the building
qualified persons.
elements are of non-combustible materials, such as concrete
and steel. The roof is also of non-combustible material, such as Exception No. 6: Oil insulated transformers shall be permitted
concrete or steel. to be used without a vault in portable or mobile surface mining
equipment (such as electric excavator) if each of the following
Type II – Non-combustible
conditions are met:
This type of building has steel or concrete walls, floors, and • Provisions are made for draining leaking fluid to the ground
structural framework similar to type I construction; however,
the roof covering material is combustible. The roof covering of • Safe egress is provided for personnel
a type II building can be a layer of asphalt waterproofing, with a
combustible felt paper covering. Another layer of asphalt may be • A minimum of 6 mm (1/4 in) steel barrier is provided for
mopped over the felt paper. personnel protection
* Refer to NFPA 220 for definition of non-combustible or limited combustible Type I and II building construction.
** N
o additional NEC article 450.23 safeguards are required if one or more of exceptions 1 - 6 of Section 450.26, Oil-Insulated Transformers Installed Indoors apply.
2020 code options for the installation of listed less-flammable liquid-filled transformers www.eaton.com/cooperpowerseries 3
Reference Data TD900001EN
Effective October 2021
*Refer to NFPA 220 for more information about Type I and Type II building construction.
4 www.eaton.com/cooperpowerseries 2020 code options for the installation of listed less-flammable liquid-filled transformers
Reference Data TD900001EN
Effective October 2021
2020 code options for the installation of listed less-flammable liquid-filled transformers www.eaton.com/cooperpowerseries 5
Reference Data TD900001EN
Effective October 2021
Example of outdoors on or adjacent to Type I and Type II NEC options for transformer listing **
buildings non-combustible building* and no combustible Indoor installation
material stored in the area
At the time of the publication of this guide, two nationally
recognized testing entities list less-flammable insulating liquids
and publish their respective listing requirements:
A. Underwriters Laboratories classifications
B. FM Global approvals
It is optional which of the listings are used to comply with
450.23.
For indoor installations, if the transformers are provided with
less-flammable liquid insulation and are installed without a
vault in a Type I or Type II non-combustible building* where no
combustible material is storage, it requires:
1) A liquid confinement area be provided.
Liquid containment may include:
- Containment pan
- Curbing
- Room containment (e.g. door sill)
2) The transformer be filled with a listed less-flammable
insulating liquid with a minimum of 300°C fire point.
3) The installation complies with all restrictions provided for in
the listing of the liquid.
or
A liquid confinement area, as indicated above and an automatic
fire extinguishing system.
If the transformer has a non-listed insulating liquid, provide
individual containment for the content of the transformer to
prevent spills from flowing to another transformers or important
equipment in the room.
or
It must be installed in a vault complying with the NEC 450 Part
III, Transformer vaults.
Section 450.26 may be followed in lieu of any requirements
listed in Section 450.23. Exceptions to vault requirements
are listed.
Points in Section 450.26 are also valid for less-flammable
liquid-filled installations. Construction requirements for vaults
are detailed in Part III of Article 450.
Section 450.42 in Part III, Transformer vaults, allows an
exception to the three-hour vault requirement permitting a
one-hour rated fire resistant rated room if equipped with an
automatic extinguishing system.
*Refer to NFPA 220 for more information about Type I and Type II building construction.
**No additional NEC article 450.23 safeguards are required if one or more of exceptions 1-6 of Section 450.26, Oil-Insulated Transformers Installed
Indoors, apply.
6 www.eaton.com/cooperpowerseries 2020 code options for the installation of listed less-flammable liquid-filled transformers
Reference Data TD900001EN
Effective October 2021
75 500,000 800,000 35
(+) T
his is an additional requirement to the overcurrent protection required in
accordance with Section 450.3 of the current National Electrical Code®.
(++) Opening pressure, 10 psig maximum.
Reprinted from the Online Certifications Directory with permission from UL © 2018 UL LLC.
2020 code options for the installation of listed less-flammable liquid-filled transformers www.eaton.com/cooperpowerseries 7
Reference Data TD900001EN
Effective October 2021
Main building
(Plant view)
3
4
1 = Detached building
2 = Outside room with direct access from outside only
3,4 = Inside room with direct access from outside only
a Transformers in location 1 may also be treated as outdoor transformers in accordance with Section 2.3
b With no oil-filled bushings, oil-filled tap changer or other oil-filled accessories that could increase the fire hazard
c See also Section 2.2.3.4 for protection of combustibles other than transformer liquids
d Section 3.3 describes FM approved and equivalent transformers
e Provide liquid spill containment in accordance with section 2.2.1.4
f utomatic sprinklers, foam-water sprinklers or water mist. Also provide emergency drainage for sprinklers
A
discharge per Section 2.2.1.5
g Subdivide room or building with three-hour fire-rated construction for each transformer if multiple transformers
are present
* Fig. 1 is based on the information provided on Fig. 2 of the FM document DS 5-4 dated 07-2019.
** Table 4 is based on the information provided on Table 4 of the FM document DS 5-4 dated 07-2019.
8 www.eaton.com/cooperpowerseries 2020 code options for the installation of listed less-flammable liquid-filled transformers
Reference Data TD900001EN
Effective October 2021
Listing option - B
FM Global requirements
The FM indoor installation requirements for all transformer and According to FM Global Standard 3990 dated 1-2018, the key
fluid types are given in FM Global Property Loss Prevention Data protection features are as listed below. Refer to the FM standard
Sheets 5-4 - Transformers (LPD). Specific requirements for less- for complete requirements:
flammable liquid-insulated transformers are included. Refer to
Section 2.2.1.2 of FM LPD for special installation requirements
• The transformer tank rupture strength shall be a m inimum of
for network transformers. 15 psig for rectangular and 20 psig for cylindrical tanks. All
transformer tanks shall be designed to withstand a pressure
General transformer requirements are as follows: of 7 psig without p
ermanent distortion, and
• Minimum 3 ft. clear from building walls, and • The transformer tank shall be provided with a p ressure relief
device to vent internal over-pressures. The device must be
• Liquid containment provisions, and capable of venting a minimum s pecified flow rate, based
• Room fire resistance rating based on fluid and transformer on the kVA as noted in Table 4 and Section 3.2.3 of the FM
type, and Global Standard 3990. Proper pressure venting coordinated
with proper tank pressure withstand rating has proven highly
• Room ventilation, if necessary, to prevent non-thermal effective in preventing tank rupture from overpressure due to
damage, and internal fault currents below the trip rating of primary circuit
• Smoke detection with alarm in the electrical room current limiting fuses, and
* For a listing of FM Global less-flammable liquids, refer to the less-flammable fluids section of the FM Global Approval Guide - Electrical Equipment.
2020 code options for the installation of listed less-flammable liquid-filled transformers www.eaton.com/cooperpowerseries 9
Reference Data TD900001EN
Effective October 2021
Listing option - B
FM Global requirements (continued)
• For grounded wye secondary windings of 150 volts or more Table 6. FM maximum I2t let through required ratings
and rated at 1,000 or more nominal amperes, a n otification
tag shall be provided by the manufacturer, secured to the
kVA rating Current-limiting Other protection
low voltage neutral bushing, advising that the transformer 3-phase (1-phase) fusing
installation requires ground fault relay protection prior to
energization (if not installed at time of manufacturing), Indoor 45 (15) 500,000 700,000
units greater than 500 kVA should be provided with alarm 75 (25) 500,000 800,000
contacts on the pressure relief device and units greater
than 2500 kVA, in all locations shall be equipped with alarm 112.5 (37.5) 550,000 900,000
contacts on the pressure relief device and a rapid-rise 150 (50) 600,000 1,000,000
relay, and
225 (75) 650,000 1,200,000
• Three-phase pad-mounted and substation transformers
300 (100) 750,000 1,400,000
shall be equipped with an oil level gauge. Additionally, all
transformers rated 750 kVA or higher shall be equipped with a 500 (167) 900,000 1,900,000
liquid temperature indicator and pressure-vacuum gauge, and 750 (250) 1,100,000 2,200,000
• Transformers shall be capable of passing Basic Lightning 1,000 (333) 1,250,000 3,400,000
Impulse Insulation Level (BIL) testing at a minimum tilt of 1.5°
from vertical 1,500 (500) 1,500,000 4,500,000
2,000 (667) 1,750,000 6,000,000
Table 5: FM pressure relief device required ratings 2,500 (833) 2,000,000 7,500,000
3,000 (1,000) 2,250,000 9,000,000
kVA rating Flow rate
3-phase (1-phase) SCFM @ 15psi (103 pKa) 3,750 (1,250) 2,500,000 11,000,000
112.5 (37.5) 35 5,000 (1,667) 3,000,000 14,000,000
150 (50) 50 7,500 (2,500) 3,000,000 14,000,000
300 (100) 100 10,000 (3,333) and over 3,000,000 14,000,000
1,000 (333) 350 Note: For kVA ratings not listed use next lowest rating in table.
2,000 (667) 700
10,000 (3,333) 5,000
Over 10000 KVA (3333 1Ø) 12600
Note: For kVA ratings not listed use next highest rating in table.
10 www.eaton.com/cooperpowerseries 2020 code options for the installation of listed less-flammable liquid-filled transformers
Reference Data TD900001EN
Effective October 2021
NEC options for transformer listing – A fine print note states that combustible material**, combustible
outdoor installations buildings, fire escapes and door and window openings
may require additional safeguarding, as describe in Section
The NEC allows two different options for the listing of the 450.27. Fine Print Notes (FNP) are defined in Section 90.5 as
installed liquid transformers: informational only and are not enforceable as code requirements
(A) Underwriters Laboratories
(B) FM Global
For outdoor installations, the FM approval indicates that the Spill
containment requirements for environmental protection and
related regulations are outside the scope of the DS 5-4. Some
considerations can still be provided.
1. If an accidental release of transformer fluid could expose a
main building or adjacent equipment or storage, provide the
liquid filled transformer with a spill containment
2. Design the spill containment system in accordance with
Chapter 7 of IEEE STD 980.
or
It must be installed in accordance with NEC section 450.27, oil
insulated transformers installed outdoors, i.e. space separation,
fire barriers or water spray systems
Less-flammable liquid-insulated transformers are permitted
to be installed outdoors, attached to, on, or adjacent to
non-combustible* buildings. The installation must comply with
the requirements of a recognized listing of the fluid.
*Refer to NFPA 220 for definition of non-combustible or limited-combustible Type I and II building construction.
**Per NFPA 220, the definition of combustible material refers to material not classified as non-combustible or limited-combustible.
2020 code options for the installation of listed less-flammable liquid-filled transformers www.eaton.com/cooperpowerseries 11
Reference Data TD900001EN
Effective October 2021
The same UL classification of less-flammable liquids per the The outdoor installation requirements, according to FM Global
NEC Section 450.23 for 3-phase 45-10,000 kVA transformers Property Loss Prevention Data Sheets 5-4 - Transformers,
applies to both indoor and outdoor applications and requires: consist of requirements for transformer and fluid types. Specific
requirements for less-flammable liquid-insulated transformers are
• Transformers be equipped with tanks capable of withstanding included.
12 psig without rupture, and
FM outdoor installation requirements are based on the FM
• Transformers be equipped with pressure relief devices with Approval status of the transformer and both the volume and
minimum pressure relief capacity per the UL classification FM Approval status of the fluid. If transformers filled with
marking, and conventional mineral oil or non-approved fluids would expose
• Transformer primaries be protected with overcurrent buildings and equipment to a release of oil, the transformer
protection options per the UL classification marking must comply with FM LPD requirements. This may include
containment, separation distances, fire barriers, or water
Overcurrent protection option I, available exclusively with spray systems. Installation of FM Approved transformers
Envirotemp FR3 fluid’s UL classification, allows internal expulsion or transformers with FM Approved less-flammable liquids
fuses (e.g. bay-o-net fuses) in series with current limiting fuses. must comply with FM LPD requirements for containment
Overcurrent protection option II allows stand-alone expulsion and separation distances. The FM LPD provides detailed
fuses, but they must be located outside the transformer tank. requirements for fire barriers in Section 2.3.1.1.1 and water spray
To specify a UL Classified Envirotemp FR3 fluid-filled transformer exposure protection in Section 2.3.2.1.
for a specific kVA rating, refer to the UL classification marking for Fluid containment requirements as detailed in Section 2.3.1.4 of
the fluid shown in Table 3. the FM LPD are:
• Provide a liquid containment when accidental release of fluid
could expose the main building, adjacent equipment
or storage
• Design the containment per IEEE 980
• Where water spray is provided, install additional containment
or direct discharge water, this per DS 7-83
• Provide system for removal of rainwater from the
containment area
• Extend containment perimeter at least 5 ft for transformers
with up to 1000 gal and 8 ft for transformers with more than
1000 gal
12 www.eaton.com/cooperpowerseries 2020 code options for the installation of listed less-flammable liquid-filled transformers
Reference Data TD900001EN
Effective October 2021
Listing option - B
FM Global requirements (continued)
Per approval standard 3990 dated 1-2018, the transformer must be located 5 ft (1.5 m) from
doors, fire escapes and windows
Transformer
Main X Main
building building
Containment
Table 7. Separation for exposure protection of main building walls (see Fig. 2) **
* Figure 2 is based on the information provided on Fig. 3 of the FM document DS 5-4 dated 07-2019.
** Table 7 is based on the information provided on Table 5 of the FM document DS 5-4 dated 07-2019.
2020 code options for the installation of listed less-flammable liquid-filled transformers www.eaton.com/cooperpowerseries 13
Reference Data TD900001EN
Effective October 2021
Listing option - B
FM Global requirements (continued)
Roof
Y
Transformer
Main X Main
building building Z
Containment
* Information taken from FM data sheet 5-4. There seems to be an inconsistency in the data sheet, Eaton's calculation for 30 in. is 0.76 m.
Fig 3. Use of two-hour fire barriers and separation distances for protection of exposed main building walls*
Table 8. Separation and extent of two-hour fire barrier for protection of main building walls (for dimensions refer to Fig. 3)**
* Figure 3 is based on the information provided on Fig. 4 of the FM document DS 5-4 dated 07-2019.
** Table 8 is based on the information provided on Table 6 of the FM document DS 5-4 dated 07-2019.
14 www.eaton.com/cooperpowerseries 2020 code options for the installation of listed less-flammable liquid-filled transformers
Reference Data TD900001EN
Effective October 2021
Listing option - B
FM Global requirements (continued)
Transformer
Main X
building
with non-
combustible X
roof
W
Containment
* Information taken from FM data sheet 5-4. There seems to be an inconsistency in the data sheet, Eaton's
calculation for 30 in. is 0.76 m.
Table 9. Transformer fire exposure to non-combustible building roof where separation from wall is based on three-hour fire
barrier or water spray protection**
Liquid type Maximum liquid volume gal (m3) Building height ft (m) W (see Fig. 4) ft (m)
<1000 (3.8) Any Not exposed
Any ≥50 (15) Not exposed
Non-approved transformer fluid 1000 – 5000 (3.8 – 19) ≥25 (7.5) Not exposed
1000 – 5000 (3.8 – 19) <25 (7.5) 15 (4.5)
>5000 (19) <50 (15) 25 (7.5)
FM Approved transformer
Liquid type or equivalent Liquid volume gal (m3) Distance ft (m)
Yes N/A 3 (0.9)
FM Approved transformer fluid No <10000 (38) 5 (1.5)
No >10000 (38) 25 (7.6)
N/A <500 (1.9) 5 (1.5)
Non-approved transformer fluid N/A <5000 (19) 25 (7.6)
N/A >5000 (19) 50 (15.2)
Note: If the separation distance between transformers on Table 10 are not met and barriers are not provided, install water spray
protection on each transformer per Section 2.3.2 of the FMDS0504 dated 07-2019.
* Figure 4 is based on the information provided on Fig. 5 of the FM document DS 5-4 dated 07-2019.
** Table 9 is based on the information provided on Table 7 of the FM document DS 5-4 dated 07-2019.
*** Table 10 is based on the information provided on Table 8 of the FM document DS 5-4 dated 07-2019.
2020 code options for the installation of listed less-flammable liquid-filled transformers www.eaton.com/cooperpowerseries 15
Reference Data TD900001EN
Effective October 2021
Installation type
For installations other than Type I and Type II* buildings or for
installations that do not comply with all the restrictions provided
for in the listing of the liquid.
NEC requirement
• Per NEC Section 450.27, Oil-insulated transformers
installed outdoors
Section 450.23 refers to Section 450.27, Oil insulated
transformers outdoors, for installation requirements when less-
flammable liquid-filled transformers are installed on or adjacent
to combustible buildings or near combustible materials. As for
conventional oil-filled transformers, it requires the safeguarding
of combustible material, combustible buildings, fire escapes
and door and window openings. Recognized safeguards include
space separation, fire barriers, spray extinguishing systems and
confinement areas for spilled fluid. The NEC requires that one
or more of the above safeguards be applied according to the
degree of fire hazard p resent in cases where the installation
presents a fire hazard. Obviously, less-flammable liquid-filled
transformers significantly reduce the possibility that the
installation presents a fire hazard compared to c onventional
mineral oil.
*Refer to NFPA 220 for definition of non-combustible or limited-combustible Type I and II building construction.
16 www.eaton.com/cooperpowerseries 2020 code options for the installation of listed less-flammable liquid-filled transformers
Reference Data TD900001EN
Effective October 2021
Requirement highlights
Transformer ≤ 35 kV and
liquid confinement area
No
available
Yes
Automatic fire
extinguishing No
system available
Non-combustible building
(Type I or Type II)* and No
No combustibles in the area Yes
In accordance
with one or more
Yes Yes of the exceptions
of NEC 450.26
Yes
Vault requirements
Installation incorporates per NEC 450, Part III
UL classification** marking No
requirements
Yes
or or
UL OPTION I UL OPTION II
• Pressure relief device • Pressure relief device
• Minimum 12 psig tank pressure • Minimum 12 psig tank pressure rupture withstand
rupture withstand • Overcurrent protection per UL classification
• Primary current-limiting fusing per marking.**
UL classification marking.** Note: Devices that vent during operation such as
bay-o-net fuses may not be liquid-immersed.
COMPLIANCE
WITH
NEC 450.23
NEC Code requirements
UL Listing requirements
* Refer to NFPA 220 for definition of non-combustible Type I and II building construction
** Transformer Fluids (EOVK), Underwriters Laboratories Certifications Directory
Note: UL classification dielectric mediums (EOUV) states that “Liquids intended for use as dielectric and cooling mediums in
electrical transformers are covered under transformer fluids (EOVK).”
Reprinted from the Online Certifications Directory with permission from UL © 2018 UL LLC.
2020 code options for the installation of listed less-flammable liquid-filled transformers www.eaton.com/cooperpowerseries 17
Reference Data TD900001EN
Effective October 2021
Requirement highlights
Non-combustible building
(Type I or Type II)* and No
no combustibles in the area
Yes
Requirements per NEC 450.27
If installation presents fire hazard one
or more of the following
safeguards shall be applied:
UL Classified less-flammable liquid** No
• Space separation
• Fire barriers
• Automatic water spray
Yes • Enclosure
Installation incorporates UL
classification** marking No
requirements
or or
UL OPTION I
UL OPTION II
• Pressure relief device
• Pressure relief device
• Minimum 12 psig tank pressure
• Minimum 12 psig tank pressure rupture
rupture withstand
withstand
• Primary current-limiting fusing per
• Overcurrent protection
UL classification marking.**
per UL classification marking.**
Note: Devices that vent during operation such
as bay-o-net fuses may not be liquid-immersed.
COMPLIANCE
WITH
NEC 450.23
NEC Code requirements
UL Listing requirements
* R efer to NFPA 220 for definition of non-combustible Type I and II building construction
** Transformer Fluids (EOVK), Underwriters Laboratories Certifications Directory
Reprinted from the Online Certifications Directory with permission from UL © 2018 UL LLC.
18 www.eaton.com/cooperpowerseries 2020 code options for the installation of listed less-flammable liquid-filled transformers
Reference Data TD900001EN
Effective October 2021
Appendix 3
‡ This list includes all the insulating liquid manufacturers listed by UL and FM Global as of the date of this publication. Refer to UL and FM Global for the latest lists.
Reprinted from the Online Certifications Directory with permission from UL © 2018 UL LLC.
2020 code options for the installation of listed less-flammable liquid-filled transformers www.eaton.com/cooperpowerseries 19
Reference Data TD900001EN
Effective October 2021
Appendix 3 (continued)
‡ This list includes all the insulating liquid manufacturers listed by UL and FM Global as of the date of this publication. Refer to UL and FM Global for the latest lists.
Reprinted from the Online Certifications Directory with permission from UL © 2018 UL LLC.
20 www.eaton.com/cooperpowerseries 2020 code options for the installation of listed less-flammable liquid-filled transformers
Reference Data TD900001EN
Effective October 2021
Appendix 3 (continued)
Reprinted from the Online Certifications Directory with permission from UL © 2018 UL LLC.
2020 code options for the installation of listed less-flammable liquid-filled transformers www.eaton.com/cooperpowerseries 21
Reference Data TD900001EN
Effective October 2021
Appendix 3 (continued)
[PRODUCT IDENTITY]
CLASSED ____
AS TO FIRE HAZARD ONLY
Control No.
Reprinted from the Online Certifications Directory with permission from UL © 2018 UL LLC.
22 www.eaton.com/cooperpowerseries 2020 code options for the installation of listed less-flammable liquid-filled transformers
Reference Data TD900001EN
Effective October 2021
Appendix 3 (continued)
Notice of disclaimer
The appearance of a company’s name or product in this
database does not in itself assure that products so identified
have been manufactured under UL’s follow-up service. Only
those products bearing the UL mark should be considered to be
certified and covered under UL’s follow-up service. Always look
for the mark on the product.
Reprinted from the Online Certifications Directory with permission from UL © 2018 UL LLC.
2020 code options for the installation of listed less-flammable liquid-filled transformers www.eaton.com/cooperpowerseries 23
Reference Data TD900001EN
Effective October 2021
Appendix 3 (continued)
Related products
UL Classified less-flammable liquids and
Liquids intended for use as dielectric and cooling mediums are
UL Listed & Classified transformers covered under dielectric mediums (EOUV).
24 www.eaton.com/cooperpowerseries 2020 code options for the installation of listed less-flammable liquid-filled transformers
Reference Data TD900001EN
Effective October 2021
Appendix 3 (continued)
Notice of disclaimer
The appearance of a company’s name or product in this
database does not in itself assure that products so identified
have been manufactured under UL’s follow-up service. Only
those products bearing the UL mark should be considered to be
certified and covered under UL’s follow-up service. Always look
for the mark on the product.
Reprinted from the Online Certifications Directory with permission from UL © 2018 UL LLC.
2020 code options for the installation of listed less-flammable liquid-filled transformers www.eaton.com/cooperpowerseries 25
Reference Data TD900001EN
Effective October 2021
Requirement highlights
Transformer
≤ 35 kV and liquid No
confinement area
available
Yes
Automatic fire
extinguishing No
system available
Non-combustible
building (Type I
or Type II)* and No
no combustibles
in the area
Yes
Yes
Vault
requirements per
Installation NEC 450, Part III
incorporates
FM LPD sheet*** No
requirements
Yes
Yes
FM Approved
transformer** or
equivalent includes
a) Tank rupture strength COMPLIANCE NEC Code requirements
b) Tank pressure relief
c) Low current fault protection
Yes WITH FM Listing requirements
d) High current fault protection NEC 450.23
e) Approved less-flammable liquid
* R
efer to NFPA 220 for definition of non-combustible Type I and II building construction ‡ This list includes all the insulating liquid
Less-flammable liquid-insulated transformers compliance to NEC Section 450.23 per FM*** Listing
Requirement highlights
Non-combustible
building (Type I or Type II)* No
and no combustibles in the
area
Yes
FM Approved less-
No
flammable liquid**
Yes
Installation incorporates
FM LPD sheet*** requirements No
Yes
Requirements
Requirements per liquid listing per NEC 450.27 if
installation presents fire
hazard one or more of the
COMPLIANCE following safeguards shall be
Yes WITH Yes applied:
NEC 450.23 • Space separation
• Fire barriers
See Page 22 for FM • Automatic water spray
requirements detail • Enclosure
Note: NEC Section 110.3 (b) applies if the listing chosen for compliance specifically addresses outdoor application.
2020 code options for the installation of listed less-flammable liquid-filled transformers www.eaton.com/cooperpowerseries 27
Reference Data TD900001EN
Effective October 2021
Yes FM Approved
No
transformer*
Spill containment
NOT REQUIRED
Installation options for mineral Installation options for Where exposure
oil or non-approved fluid. mineral oil or non- protection is
Minimum separation distance approved fluid provided for
per Table 7 For two-hour fire alternatives C, D or
• 5-100 feet horizontal barriers per Table 8 E of 2.3.1.1.1 of
U.S. EPA Environmental (depending on fluid volume) • 5-25 feet horizontal the FM LPD***
Technology Verification** follow Table 9
• 25-100 feet vertical
status for ready information in this
(Both depending on
biodegradation document.
fluid volume)
Minimum separation
distance per Table 7
• 3 ft Yes Transformer
No
slopes towards
build?
For two-hour fire
barriers per Table 8
• 5-15 feet horizontal
• 25-50 feet vertical Spill containment Spill containment
(depending on fluid IS REQUIRED IS NOT REQUIRED
volume)
COMPLIANCE
WITH
NEC 450.23
28 www.eaton.com/cooperpowerseries 2020 code options for the installation of listed less-flammable liquid-filled transformers
Reference Data TD900001EN
Effective October 2021
Notes
2020 code options for the installation of listed less-flammable liquid-filled transformers www.eaton.com/cooperpowerseries 29
Reference Data TD900001EN
Effective October 2021
30 www.eaton.com/cooperpowerseries 2020 code options for the installation of listed less-flammable liquid-filled transformers
Reference Data TD900001EN
Effective October 2021
2020 code options for the installation of listed less-flammable liquid-filled transformers www.eaton.com/cooperpowerseries 31
Reference Data TD900001EN
Effective October 2021
Eaton
1000 Eaton Boulevard
Cleveland, OH 44122
United States
Eaton.com
© 2021 Eaton
All Rights Reserved Eaton is a registered trademark.
Printed in USA For Eaton‘s Cooper Power series product
Publication No. TD900001EN All other trademarks are property information call 1-877-277-4636 or visit:
October 2021 of their respective owners. www.eaton.com/cooperpowerseries.